Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES

Section 2704

California Fire Code (Title 24, Part 9) · 2019 edition · updated 2026-09-10 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

2704.1 General. Storage of hazardous materials shall comply

with Section 2703 and this section and other applicable provisions of this code.

Exceptions & meaning →

2704.2 Fabrication areas. Hazardous materials storage and

the maximum quantities of hazardous materials in use and storage allowed in fabrication areas shall be in accordance with Sections 2704.2.1 through 2704.2.2.1.

2704.2.1 Location of HPM storage in fabrication areas. Storage of HPM in fabrication areas shall be within approved or listed storage cabinets, gas cabinets, exhausted enclosures or within a workstation as follows:

  1. Flammable and combustible liquid storage cabinets shall comply with Section 5704.3.2.

  2. Hazardous materials storage cabinets shall comply with Section 5003.8.7.

  3. Gas cabinets shall comply with Section 5003.8.6. Gas cabinets for highly toxic or toxic gases shall also comply with Section 6004.1.2.

  4. Exhausted enclosures shall comply with Section 5003.8.5. Exhausted enclosures for highly toxic or toxic gases shall also comply with Section 6004.1.3.

  5. Workstations shall comply with Section 2705.2.3.

2704.2.2 Maximum aggregate quantities in fabrication areas. The aggregate quantities of hazardous materials stored or used in a single fabrication area shall be limited as specified in this section.

Exception: Fabrication areas containing quantities of hazardous materials not exceeding the maximum allowable quantities per control area established by Sections 5003.1.1, 5704.3.4 and 5704.3.5.

2704.2.2.1 Storage and use in fabrication areas. The maximum quantities of hazardous materials stored or used in a single fabrication area shall not exceed the quantities set forth in Table 2704.2.2.1.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

SEMICONDUCTOR FABRICATION FACILITIES

TABLE 2704.2.2.1 QUANTITY LIMITS FOR HAZARDOUS MATERIALS IN A SINGLE FABRICATION AREA IN GROUP H-5 a

HAZARD CATEGORY SOLIDS
(pounds/square foot)
LIQUIDS
(gallons/square foot)
GAS
(cubic feet @ NTP/square foot)
Physical-hazard materials Physical-hazard materials Physical-hazard materials Physical-hazard materials
Combustible dust Note b Not Applicable Not Applicable
Combustible fiber
Loose
Baled
Note b
Notes b and c
Not Applicable Not Applicable
Combustible liquid
Class II
Class IIIA
Class IIIB
Combination Class I, II and IIIA
Not Applicable 0.01
0.02
Not Limited
0.04
Not Applicable
Cryogenic gas
Flammable
Oxidizing
Not Applicable Not Applicable Note d
1.25
Explosives Note b Note b Note b
Flammable gas
Gaseous
Liquefied
Not Applicable Not Applicable Note d
Note d
Flammable liquid
Class IA
Class IB
Class IC
Combination Class IA, IB and IC
Combination Class I, II and IIIA
Not Applicable 0.0025
0.025
0.025
0.025
0.04
Not Applicable
Flammable solid 0.001 Not Applicable Not Applicable
Organic peroxide
Unclassified detonable
Class I
Class II
Class III
Class IV
Class V
Note b
Note b
0.025
0.1
Not Limited
Not Limited
Not Applicable Not Applicable
Oxidizing gas
Gaseous
Liquefied
Combination of Gaseous and
Liquefied
Not Applicable Not Applicable 1.25
1.25
1.25
Oxidizer
Class 4
Class 3
Class 2
Class 1
Combination oxidizer Class 1, 2, 3
Note b
0.003
0.003
0.003
0.003
Note b
0.03
0.03
0.03
0.03
Not
Applicable
Pyrophoric 0.01 0.00125 Notes d and e
Unstable reactive
Class 4
Class 3
Class 2
Class 1
Note b
0.025
0.1
Not Limited
Note b
0.0025
0.01
Not Limited
Note b
Note b
Note b
Not Limited

(continued)

400 2019 CALIFORNIA FIRE CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

SEMICONDUCTOR FABRICATION FACILITIES

TABLE 2704.2.2.1—continued QUANTITY LIMITS FOR HAZARDOUS MATERIALS IN A SINGLE FABRICATION AREA IN GROUP H-5 a

HAZARD CATEGORY SOLIDS
(pounds/square foot)
LIQUIDS
(gallons/square foot)
GAS
(cubic feet @ NTP/square foot)
Physical-hazard materials Physical-hazard materials Physical-hazard materials Physical-hazard materials
Water reactive
Class 3
Class 2
Class 1
Note b
0.25
Not Limited
0.00125
0.025
Not Limited
Not
Applicable
Health-hazard materials Health-hazard materials Health-hazard materials Health-hazard materials
Corrosives Not Limited Not Limited Not Limited
Highly toxics Not Limited Not Limited Note d
Toxics Not Limited Not Limited Note d

For SI: 1 pound per square foot = 4.882 kg/m 2, 1 gallon per square foot = 40.7 L/m 2, 1 cubic foot @ NTP/square foot = 0.305 m 3 @ NTP/m 2,

1 cubic foot = 0.02832 m 3 . a. Hazardous materials within piping shall not be included in the calculated quantities. b. Quantity of hazardous materials in a single fabrication area shall not exceed the maximum allowable quantities per control area in Tables 5003.1.1(1) and

5003.1.1(2). c. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class. d. The aggregate quantity of flammable, pyrophoric, toxic and highly toxic gases shall not exceed the greater of 0.2 cubic feet at NTP/square foot or 9,000 cubic

feet at NTP. e. The aggregate quantity of pyrophoric gases in the building shall not exceed the amounts set forth in Table 5003.8.2.

Exceptions & meaning →

2704.3 Indoor storage outside of fabrication areas. The

indoor storage of hazardous materials outside of fabrication areas shall be in accordance with Sections 2704.3.1 through 2704.3.3.

2704.3.1 HPM storage. The indoor storage of HPM in quantities greater than those listed in Sections 5003.1.1 and 5704.3.4 shall be in a room complying with the requirements of the California Building Code and this code for a liquid storage room, HPM room or gas room as appropriate for the materials stored.

2704.3.2 Other hazardous materials storage. The indoor storage of other hazardous materials shall comply with Sections 5001, 5003 and 5004 and other applicable provisions of this code.

2704.3.3 Separation of incompatible hazardous materi- als. Incompatible hazardous materials in storage shall be separated from each other in accordance with Section 5003.9.8.