Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
Section 2703
California Fire Code (Title 24, Part 9) · 2019 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
2703.1 Emergency control station. An emergency control¶
station shall be provided in accordance with Sections 2703.1.1 through 2703.1.3.
2703.1.1 Location. The emergency control station shall be located on the premises at an approved location outside the fabrication area.
2703.1.2 Staffing. Trained personnel shall continuously staff the emergency control station.
2703.1.3 Signals. The emergency control station shall receive signals from emergency equipment and alarm and detection systems. Such emergency equipment and alarm and detection systems shall include, but not be limited to, the following where such equipment or systems are required to be provided either in this chapter or elsewhere in this code:
Automatic sprinkler system alarm and monitoring systems.
Manual fire alarm systems.
Emergency alarm systems.
Gas detection systems.
Smoke detection systems.
Emergency power systems.
Automatic detection and alarm systems for pyrophoric liquids and Class 3 water-reactive liquids required by Section 2705.2.3.4.
Exhaust ventilation flow alarm devices for pyrophoric liquids and Class 3 water-reactive liquids and cabinet exhaust ventilation systems required by Section 2705.2.3.4.
2703.2 Systems, equipment and processes.¶
Systems, equipment and processes shall be in accordance with Sections 2703.2.1 through 2703.2.3.2.
2703.2.1 Application. Systems, equipment and processes shall include, but not be limited to, containers, cylinders, tanks, piping, tubing, valves and fittings.
2703.2.2 General requirements. In addition to the requirements in Section 2703.2, systems, equipment and processes shall comply with Section 5003.2, other applica
¬