Section 1023 — INTERIOR EXIT STAIRWAYS AND RAMPS
2025 California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
[BE] 1023.1 General. Interior exit stairways and ramps serving as an exit component in a means of egress system shall comply with the requirements of this section. Interior exit stairways and ramps shall be enclosed and lead directly to the exterior of the building or shall be extended to the exterior of the building with an exit passageway conforming to the requirements of Section 1024, except as permitted in Section 1028.2. An interior exit stairway or ramp shall not be used for any purpose other than as a means of egress and a circulation path.
[BE] 1023.2 Construction. Enclosures for interior exit stairways and ramps shall be constructed as fire barriers in accordance with Section 707 of the California Building Code or horizontal assemblies constructed in accordance with Section 711 of the California Building Code, or both. Interior exit stairway and ramp enclosures shall have a fire-resistance rating of not less than 2 hours where connecting four stories or more and not less than 1 hour where connecting less than four stories. The number of stories connected by the interior exit stairways or ramps shall include any basements, but not any mezzanines. Enclosure for interior exit stairways and ramps shall have a fire-resistance rating not less than the floor assembly penetrated, but need not exceed 2 hours.
Exceptions:
- Interior exit stairways and ramps in Group I-3 occupancies in accordance with the provisions of Section 408.3.8 of the California Building Code .
- Interior exit stairways within an atrium enclosed in accordance with Section 404.6 of the California Building Code .
- Interior exit stairways in accordance with Section 510.2 of the California Building Code . 4. Fixed guideway transit stations, constructed in accordance with Section 443 of the California Building Code.
10-46 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
[BE] 1023.3 Termination. Interior exit stairways and ramps shall terminate at an exit discharge or a public way.
Exception: A combination of interior exit stairways, interior exit ramps and exit passageways, constructed in accordance with Sections 1023.2, 1023.3.1 and 1024, respectively, and forming a continuous protected enclosure, shall be permitted to extend an interior exit stairway or ramp to the exit discharge or a public way.
[BE] 1023.3.1 Extension. Where interior exit stairways and ramps are extended to an exit discharge or a public way by an exit passageway, the interior exit stairway and ramp shall be separated from the exit passageway by a fire barrier constructed in accordance with Section 707 of the California Building Code or a horizontal assembly constructed in accordance with Section 711 of the California Building Code, or both. The fire-resistance rating shall be not less than that required for the interior exit stairway and ramp. A fire door assembly complying with Section 716 of the California Building Code shall be installed in the fire barrier to provide a means of egress from the interior exit stairway and ramp to the exit passageway. Openings in the fire barrier other than the fire door assembly are prohibited. Penetrations of the fire barrier are prohibited.
Exceptions:
- Penetrations of the fire barrier in accordance with Section 1023.5 shall be permitted.
- Separation between an interior exit stairway or ramp and the exit passageway extension shall not be required where there are no openings into the exit passageway extension.
- Separation between an interior exit stairway or ramp and the exit passageway extension shall not be required where the interior exit stairway and the exit passageway extension are pressurized in accordance with Section 909.20.4 of the California Building Code .
[BE] 1023.4 Openings. Interior exit stairway and ramp opening protectives shall be in accordance with the requirements of Section 716 of the California Building Code .
Openings in interior exit stairways and ramps other than unprotected exterior openings shall be limited to those required for exit access to the enclosure from normally occupied spaces and for egress from the enclosure.
Elevators shall not open into interior exit stairways and ramps.
[BE] 1023.5 Penetrations. Penetrations into or through interior exit stairways and ramps are prohibited except for the following:
Equipment and ductwork necessary for independent ventilation or pressurization.
Fire protection systems.
Security systems.
Two-way communication systems.
Electrical raceway for fire department communication systems.
Electrical raceway serving the interior exit stairway and ramp and terminating at a steel box not exceeding 16 square inches (0.010 m [2] ).
Structural elements, such as beams or joists, supporting the interior exit stairway or ramp or enclosure.
Structural elements, such as beams or joists, supporting a roof at the top of the interior exit stairway or ramp.
Such penetrations shall be protected in accordance with Section 714 of the California Building Code . There shall not be penetrations or communication openings, whether protected or not, between adjacent interior exit stairways and ramps.
Exception: Membrane penetrations shall be permitted on the outside of the interior exit stairway and ramp. Such penetrations shall be protected in accordance with Section 714.4.2 of the California Building Code .
[BE] 1023.6 Ventilation. Equipment and ductwork for interior exit stairway and ramp ventilation as permitted by Section 1023.5 shall comply with one of the following items:
- Such equipment and ductwork shall be located exterior to the building and shall be directly connected to the interior exit stairway and ramp by ductwork enclosed in construction as required for shafts.
- Where such equipment and ductwork is located within the interior exit stairway and ramp, the intake air shall be taken directly from the outdoors and the exhaust air shall be discharged directly to the outdoors, or such air shall be conveyed through ducts enclosed in construction as required for shafts.
- Where located within the building, such equipment and ductwork shall be separated from the remainder of the building, including other mechanical equipment, with construction as required for shafts.
In each case, openings into the fire-resistance-rated construction shall be limited to those needed for maintenance and operation and shall be protected by opening protectives in accordance with Section 716 of the California Building Code for shaft enclosures.
The interior exit stairway and ramp ventilation systems shall be independent of other building ventilation systems.
[BE] 1023.7 Interior exit stairway and ramp exterior walls. Exterior walls of the interior exit stairway or ramp shall comply with the requirements of Section 705 of the California Building Code for exterior walls. Where nonrated walls or unprotected openings enclose the exterior of the stairway or ramps and the walls or openings are exposed by other parts of the building at an angle of less than 180 degrees (3.14 rad), building construction within 10 feet (3048 mm) of the exterior walls of the interior exit stairway or ramp shall comply with Sections 1023.7.1 and 1023.7.2.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
[BE] 1023.7.1 Building exterior walls. Building exterior walls within 10 feet (3048 mm) horizontally of a nonrated wall or unprotected opening in an interior exit stairway or ramp shall have a fire-resistance rating of not less than 1 hour. Openings within such exterior walls shall be protected by opening protectives having a fire protection rating of not less than [3] / 4 hour. This construction shall extend vertically from the ground to a point 10 feet (3048 mm) above the topmost landing of the stairway or ramp, or to the roof line, whichever is lower.
[BE] 1023.7.2 Roof assemblies. Where the interior exit stairway or ramp extends above an adjacent roof of the same building, the adjacent roof assembly shall have a fire-resistance rating of not less than 1 hour and openings shall be protected by opening protectives having a fire protection rating of not less than [3] / 4 hour. The fire-resistance rating and opening protection shall extend horizontally not less than 10 feet (3048 mm) from the exterior wall of the stairway or ramp, or to the perimeter of the adjacent roof, whichever is less.
embly shall have a fire-resistance rating of not less than 1 hour and openings shall be protected by opening protectives having a fire protection rating of not less than [3] / 4 hour. The fire-resistance rating and opening protection shall extend horizontally not less than 10 feet (3048 mm) from the exterior wall of the stairway or ramp, or to the perimeter of the adjacent roof, whichever is less.
Exceptions:
- The roof assembly need not be rated and openings in the roof need not be protected where they are adjacent to the penthouse of the stairway or ramp, unless otherwise required by this code.
- The adjacent roof assembly need not be rated and adjacent openings in the roof need not be protected where the exterior wall of the stairway or ramp has a fire-resistance rating of 1 hour and openings are protected by opening protectives having a fire protection rating of not less than [3] / 4 hour, extending not less than 10 feet (3048 mm) above the roof.
[BE] 1023.8 Barriers at level of exit discharge. An interior exit stairway and ramp shall not continue below its level of exit discharge unless an approved barrier is provided at the level of exit discharge to prevent persons from unintentionally continuing into levels below. Directional exit signs shall be provided as specified in Section 1013.
[BE] 1023.9 Stairway identification signs. A sign shall be provided at each floor landing in an interior exit stairway and ramp connecting more than three stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stairway or ramp. The signage shall state the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The bottom of the sign shall be located not less than 5 feet (1524 mm) above the floor landing in a position that is readily visible when the doors are in the open and closed positions.
In addition to the stairway identification sign, raised characters and braille floor identification signs that comply with Chapter 11B of the California Building Code shall be located at the landing of each floor level, placed adjacent to the door on the latch side, in all enclosed stairways in buildings two or more stories in height to identify the floor level. At the exit discharge level, the sign shall include a raised five pointed star located to the left of the identifying floor level. The outside diameter of the star shall be the same as the height of the raised characters.
nding of each floor level, placed adjacent to the door on the latch side, in all_ enclosed stairways in buildings two or more stories in height to identify the floor level. At the exit discharge level, the sign shall include a raised five pointed star located to the left of the identifying floor level. The outside diameter of the star shall be the same as the height of the raised characters.
[BE] 1023.9.1 Signage requirements. Stairway identification signs shall comply with all of the following requirements:
- The signs shall be a minimum size of 18 inches (457 mm) by 12 inches (305 mm).
- The letters designating the identification of the stair enclosure, such as STAIR NO. 1 or WEST STAIR, shall be placed at the top of the sign and shall be not less than 1 [1] / 2 inches (38 mm) in height block lettering with [1] / 4 -inch (6 mm) strokes.
- The number designating the floor level shall be not less than 5 inches (127 mm) in height with [3] / 4 -inch (19 mm) strokes and located in the center of the sign. The mezzanine levels shall have the letter “M” preceding the floor level. basement levels shall have the letter “B” preceding the floor number.
- Other lettering and numbers shall be not less than 1 inch (25 mm) in height. 5. The stairway’s upper terminus, such as ROOF ACCESS or NO ROOF ACCESS, shall be placed under the stairway identification in 1-inch-high (25 mm) block lettering with [1] / 4 -inch (6 mm) strokes. 6. The lower and upper terminus of the stairway shall be placed at the bottom of the sign in 1-inch-high (25 mm) block lettering with [1] / 4 -inch (6 mm) strokes. 7. Characters and their background shall have a nonglare finish. Characters shall contrast with their background, with either light characters on a dark background or dark characters on a light background. 8. Where signs required by Section 1023.9 are installed in the interior exit stairways and ramps of buildings subject to Section 1025, the signs shall be made of the same materials as required by Section 1025.4.
[BE] 1023.10 Elevator lobby identification signs. At landings in interior exit stairways where two or more doors lead to the floor level, any door with direct access to an enclosed elevator lobby shall be identified by signage located on the door or directly adjacent to the door stating “Elevator Lobby.” Signage shall be in accordance with Section 1023.9.1, Items 4, 5 and 6.
[BE] 1023.11 Tactile floor-level signs. Where floor-level signs are provided in interior exit stairways and ramps, a floor-level sign identifying the floor level in visual characters, raised characters and braille complying with ICC A117.1 shall be located at each floorlevel landing adjacent to the door leading from the interior exit stairway and ramp into the corridor.
[BE] 1023.12 Smokeproof enclosures. Where required by Section 403.5.4, 405.7.2 or 412.2.2.1 of the California Building Code, interior exit stairways and ramps shall be smokeproof enclosures in accordance with Section 909.20.
[BE] 1023.12.1 Termination and extension. A smokeproof enclosure shall terminate at an exit discharge or a public way. The smokeproof enclosure shall be permitted to be extended by an exit passageway in accordance with Section 1023.3. The exit passageway shall be without openings other than the fire door assembly required by Section 1023.3.1 and those necessary for egress from the exit passageway. The exit passageway shall be separated from the remainder of the building by 2-hour fire barri
10-48 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
ers constructed in accordance with Section 707 of the California Building Code or horizontal assemblies constructed in accordance with Section 711 of the California Building Code, or both.
Exceptions:
Openings in the exit passageway serving a smokeproof enclosure are permitted where the exit passageway is protected and pressurized in the same manner as the smokeproof enclosure, and openings are protected as required for access from other floors.
The fire barrier separating the smokeproof enclosure from the exit passageway is not required, provided that the exit passageway is protected and pressurized in the same manner as the smokeproof enclosure.
A smokeproof enclosure shall be permitted to egress through areas on the level of exit discharge or vestibules as permitted by Section 1028.
[BE] 1023.12.2 Enclosure access. Access to the stairway or ramp within a smokeproof enclosure shall be by way of a vestibule or an open exterior balcony.
Exception: Access is not required by way of a vestibule or exterior balcony for stairways and ramps using the pressurization alternative complying with Section 909.20.4 of the California Building Code .
[BE] 1023.13 Standpipes. Standpipes and standpipe hose connections shall be provided where required by Sections 905.3 and 905.4.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Fire Code (Title 24, Part 9)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REQUIREMENTS
- Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
- Chapter 5 — FIRE SERVICE FEATURES
- Chapter 6 — BUILDING SERVICES AND SYSTEMS
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
-
▸ Chapter 10 — MEANS OF EGRESS
Overview- Section 1001 — ADMINISTRATION
- Section 1002 — DEFINITIONS
- Section 1003 — GENERAL MEANS OF EGRESS
- Section 1004 — OCCUPANT LOAD
- Section 1005 — MEANS OF EGRESS SIZING
- Section 1006 — NUMBERS OF EXITS AND EXIT ACCESS DOORWAYS
- Section 1007 — EXIT AND EXIT ACCESS DOORWAY CONFIGURATION
- Section 1008 — MEANS OF EGRESS ILLUMINATION
- Section 1009 — ACCESSIBLE MEANS OF EGRESS
- Section 1010 — DOORS, GATES AND TURNSTILES
- Section 1011 — STAIRWAYS
- Section 1012 — RAMPS
- Section 1013 — EXIT SIGNS
- Section 1014 — HANDRAILS
- Section 1015 — GUARDS
- Section 1016 — EXIT ACCESS
- Section 1017 — EXIT ACCESS TRAVEL DISTANCE
- Section 1018 — AISLES
- Section 1019 — EXIT ACCESS STAIRWAYS AND RAMPS
- Section 1020 — CORRIDORS
- Section 1021 — EGRESS BALCONIES
- Section 1022 — EXITS
- Section 1023 — INTERIOR EXIT STAIRWAYS AND RAMPS
- Section 1024 — EXIT PASSAGEWAYS
- Section 1025 — LUMINOUS EGRESS PATH MARKINGS
- Section 1026 — HORIZONTAL EXITS
- Section 1027 — EXTERIOR EXIT STAIRWAYS AND RAMPS
- Section 1028 — EXIT DISCHARGE
- Section 1029 — EGRESS COURTS
- Section 1030 — ASSEMBLY
- Section 1031 — EMERGENCY ESCAPE AND RESCUE
- Section 1032 — MAINTENANCE OF THE MEANS OF EGRESS
- Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
- Chapter 12 — ENERGY SYSTEMS
- Chapter 20 — AVIATION FACILITIES
- Chapter 21 — DRY CLEANING
- Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
- Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
- Chapter 24 — FLAMMABLE FINISHES
- Chapter 25 — FRUIT AND CROP RIPENING
- Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
- Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
- Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
- Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
- Chapter 30 — INDUSTRIAL OVENS
- Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
- Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
- Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
- Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
- Chapter 35 — WELDING AND OTHER HOT WORK
- Chapter 36 — MARINAS
- Chapter 37 — COMBUSTIBLE FIBERS
- Chapter 38 — RESERVED
- Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
- Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
- Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
- Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
- Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
- Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
- Chapter 51 — AEROSOLS
- Chapter 52 — RESERVED
- Chapter 53 — COMPRESSED GASES
- Chapter 54 — CORROSIVE MATERIALS
- Chapter 55 — CRYOGENIC FLUIDS
- Chapter 56 — EXPLOSIVES AND FIREWORKS
- Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
- Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
- Chapter 59 — FLAMMABLE SOLIDS
- Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
- Chapter 61 — LIQUEFIED PETROLEUM GASES
- Chapter 62 — ORGANIC PEROXIDES
- Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
- Chapter 64 — PYROPHORIC MATERIALS
- Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
- Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
- Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
- Chapter 80 — REFERENCED STANDARDS
- Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
- Appendix A — BOARD OF APPEALS
- Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix D — FIRE APPARATUS ACCESS ROADS
- Appendix E — HAZARD CATEGORIES
- Appendix F — HAZARD RANKING
- Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
- Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
- Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
- Appendix J — BUILDING INFORMATION SIGN
- Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
- Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
- Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
- Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
- Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
- Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
- Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…