Section 1016 — EXIT ACCESS
2025 California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
[BE] 1016.1 General. The exit access shall comply with the applicable provisions of Sections 1003 through 1015. Exit access arrangement shall comply with Sections 1016 through 1021.
[BE] 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section.
- Exit access through an enclosed elevator lobby is permitted in other than a Group I-2. Where access to two or more exits or exit access doorways is required in Section 1006.2.1, access to not less than one of the required exits shall be provided without travel through the enclosed elevator lobbies required by Section 3006 of the California Building Code . Where the path of exit access travel passes through an enclosed elevator lobby the level of protection required for the enclosed elevator lobby is not required to be extended to the exit unless direct access to an exit is required by other sections of this code.
- In other than Group H occupancies, egress from a room or space is allowed to pass through adjoining or intervening rooms or areas provided that such adjoining rooms or areas and the area served are accessory to one or the other and provide a discernible path of egress travel to an exit.
- In Group H occupancies, egress from a room or space is allowed to pass through adjoining or intervening rooms or areas provided that such adjoining rooms or areas are the same or lesser hazard occupancy group and provide a discernible path of egress travel to an exit.
- An exit access shall not pass through a room that can be locked to prevent egress.
Exception: An electrically locked exit access door providing egress from an elevator lobby shall be permitted in accordance with Section 1010.2.14.
- Means of egress from dwelling units or sleeping areas shall not lead through other sleeping areas, toilet rooms or bathrooms.
- Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes.
Exceptions:
- Means of egress are not prohibited through a kitchen area serving adjoining rooms constituting part of the same dwelling unit or sleeping unit.
- Means of egress are not prohibited through stockrooms in Group M occupancies where all of the following are met:
2.1. The stock is of the same hazard classification as that found in the main retail area.
2.2. Not more than 50 percent of the exit access is through the stockroom.
10-40 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
2.3. The stockroom is not subject to locking from the egress side. 2.4. There is a demarcated, minimum 44-inch-wide (1118 mm) aisle defined by full- or partial-height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions.
7. The means of egress shall not pass through any room subject to locking except in Group I-3 occupancies classified as detention facilities and psychiatric treatment areas in Group I-2 occupancies.
[BE] 1016.2.1 Multiple tenants. Where more than one tenant occupies any one floor of a building or structure, each tenant space, dwelling unit and sleeping unit shall be provided with access to the required exits without passing through adjacent tenant spaces, dwelling units and sleeping units.
Exception: The means of egress from a smaller tenant space shall not be prohibited from passing through a larger adjoining tenant space where such rooms or spaces of the smaller tenant occupy less than 10 percent of the area of the larger tenant space through which they pass; are the same or similar occupancy group; a discernable path of egress travel to an exit is provided; and the means of egress into the adjoining space is not subject to locking from the egress side. A required means of egress serving the larger tenant space shall not pass through the smaller tenant space or spaces.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Fire Code (Title 24, Part 9)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REQUIREMENTS
- Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
- Chapter 5 — FIRE SERVICE FEATURES
- Chapter 6 — BUILDING SERVICES AND SYSTEMS
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
-
▸ Chapter 10 — MEANS OF EGRESS
Overview- Section 1001 — ADMINISTRATION
- Section 1002 — DEFINITIONS
- Section 1003 — GENERAL MEANS OF EGRESS
- Section 1004 — OCCUPANT LOAD
- Section 1005 — MEANS OF EGRESS SIZING
- Section 1006 — NUMBERS OF EXITS AND EXIT ACCESS DOORWAYS
- Section 1007 — EXIT AND EXIT ACCESS DOORWAY CONFIGURATION
- Section 1008 — MEANS OF EGRESS ILLUMINATION
- Section 1009 — ACCESSIBLE MEANS OF EGRESS
- Section 1010 — DOORS, GATES AND TURNSTILES
- Section 1011 — STAIRWAYS
- Section 1012 — RAMPS
- Section 1013 — EXIT SIGNS
- Section 1014 — HANDRAILS
- Section 1015 — GUARDS
- Section 1016 — EXIT ACCESS
- Section 1017 — EXIT ACCESS TRAVEL DISTANCE
- Section 1018 — AISLES
- Section 1019 — EXIT ACCESS STAIRWAYS AND RAMPS
- Section 1020 — CORRIDORS
- Section 1021 — EGRESS BALCONIES
- Section 1022 — EXITS
- Section 1023 — INTERIOR EXIT STAIRWAYS AND RAMPS
- Section 1024 — EXIT PASSAGEWAYS
- Section 1025 — LUMINOUS EGRESS PATH MARKINGS
- Section 1026 — HORIZONTAL EXITS
- Section 1027 — EXTERIOR EXIT STAIRWAYS AND RAMPS
- Section 1028 — EXIT DISCHARGE
- Section 1029 — EGRESS COURTS
- Section 1030 — ASSEMBLY
- Section 1031 — EMERGENCY ESCAPE AND RESCUE
- Section 1032 — MAINTENANCE OF THE MEANS OF EGRESS
- Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
- Chapter 12 — ENERGY SYSTEMS
- Chapter 20 — AVIATION FACILITIES
- Chapter 21 — DRY CLEANING
- Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
- Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
- Chapter 24 — FLAMMABLE FINISHES
- Chapter 25 — FRUIT AND CROP RIPENING
- Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
- Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
- Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
- Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
- Chapter 30 — INDUSTRIAL OVENS
- Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
- Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
- Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
- Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
- Chapter 35 — WELDING AND OTHER HOT WORK
- Chapter 36 — MARINAS
- Chapter 37 — COMBUSTIBLE FIBERS
- Chapter 38 — RESERVED
- Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
- Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
- Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
- Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
- Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
- Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
- Chapter 51 — AEROSOLS
- Chapter 52 — RESERVED
- Chapter 53 — COMPRESSED GASES
- Chapter 54 — CORROSIVE MATERIALS
- Chapter 55 — CRYOGENIC FLUIDS
- Chapter 56 — EXPLOSIVES AND FIREWORKS
- Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
- Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
- Chapter 59 — FLAMMABLE SOLIDS
- Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
- Chapter 61 — LIQUEFIED PETROLEUM GASES
- Chapter 62 — ORGANIC PEROXIDES
- Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
- Chapter 64 — PYROPHORIC MATERIALS
- Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
- Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
- Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
- Chapter 80 — REFERENCED STANDARDS
- Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
- Appendix A — BOARD OF APPEALS
- Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix D — FIRE APPARATUS ACCESS ROADS
- Appendix E — HAZARD CATEGORIES
- Appendix F — HAZARD RANKING
- Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
- Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
- Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
- Appendix J — BUILDING INFORMATION SIGN
- Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
- Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
- Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
- Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
- Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
- Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
- Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…