Section 1009 — ACCESSIBLE MEANS OF EGRESS
2025 California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
[BE] 1009.1 Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by Section 1006.2 or 1006.3 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress in at least the same number as required by Section 1006.2 or 1006.3. In addition to the requirements of this chapter, means of egress, which provide access to, or egress from, buildings for persons with disabilities, shall also comply with the requirements of Chap- ter 11A or 11B of the California Building Code, as applicable. Exceptions:
- One accessible means of egress is required from an accessible mezzanine level in accordance with Section 1009.3, 1009.4 or 1009.5 and Chapter 11A or 11B of the California Building Code.
- In assembly areas with ramped aisles or stepped aisles, one accessible means of egress is permitted where the common path of travel is accessible and meets the requirements in Section 1030.8 and Chapter 11A or 11B of the California Building Code.
[BE] 1009.2 Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components:
- Accessible routes complying with and Chapter 11A or 11B of the California Building Code.
- Interior exit stairways complying with Sections 1009.3 and 1023 of this code and Chapter 11A or 11B of the California Building Code.
- Exit access stairways complying with Sections 1009.3 and 1019.3 or 1019.4 of this code and Chapter 11A or 11B of the Califor- nia Building Code.
- Exterior exit stairways complying with Sections 1009.3 and 1027 and serving levels other than the level of exit discharge of this code and Chapter 11A or 11B of the California Building Code.
- Elevators complying with Section 1009.4 of this code and Chapter 11A or 11B of the California Building Code.
- Platform lifts complying with Section 1009.5 of this code and Chapter 11A or 11B of the California Building Code.
- Horizontal exits complying with Section 1026.
- Ramps complying with Section 1012 of this code and Chapter 11A or 11B of the California Building Code.
- Areas of refuge complying with Section 1009.6.
- Exterior areas for assisted rescue complying with Section 1009.7 serving exits at the level of exit discharge.
[BE] 1009.2.1 Elevators required. In buildings where a required accessible floor is four or more stories above or below a level of exit discharge or where an accessible occupiable roof is above a story that is three or more stories above the level of exit discharge, not less than one required accessible means of egress shall include an elevator complying with Section 1009.4. Exceptions:
- In buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the elevator shall not be required as part of the accessible means of egress on floors provided with a horizontal exit and located at or above the levels of exit discharge.
- In buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the elevator shall not be required as part of the accessible means of egress on floors or occupiable roofs provided with a ramp conforming to the provisions of Section 1012.
[BE] 1009.2.2 Doors. Where doors are part of an accessible route to provide access to an exit area of refuge or exterior area of assisted rescue, maneuvering clearances shall be provided at such doors as required by ICC A117.1 in the direction of egress. Where doors lead to an area of refuge or exterior area for assisted rescue and reentry to the floor is possible, door maneuvering clearances shall be provided on both sides of the door. Exception: Maneuvering clearances are not required at doors to exit stairways for levels above and below the level of exit discharge where the exit enclosure does not include an area of refuge.
[BE] 1009.3 Stairways. In order to be considered part of an accessible means of egress, a stairway between stories shall comply with Sections 1009.3.1 through 1009.3.3.
[BE] 1009.3.1 Exit access stairways. Exit access stairways that connect levels in the same story are not permitted as part of an accessible means of egress. Exception: Exit access stairways providing means of egress from mezzanines are permitted as part of an accessible means of egress.
[BE] 1009.3.2 Stairway width. Stairways shall have a clear width of 48 inches (1219 mm) minimum between handrails. Exceptions:
- The clear width of 48 inches (1219 mm) between handrails is not required in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
- The clear width of 48 inches (1219 mm) between handrails is not required for stairways accessed from a refuge area in conjunction with a horizontal exit.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
[BE] 1009.3.3 Area of refuge. Stairways shall either incorporate an area of refuge within an enlarged floor-level landing or shall be accessed from an area of refuge complying with Section 1009.6.
Exceptions:
Areas of refuge are not required at exit access stairways where two-way communication is provided at the elevator landing in accordance with Section 1009.8.
Areas of refuge are not required at stairways in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
Areas of refuge are not required at stairways serving open parking garages.
Areas of refuge are not required for smoke-protected or open-air assembly seating areas complying with Sections 1030.6.2 and 1030.6.3.
Areas of refuge are not required at stairways in Group R-2 occupancies.
Areas of refuge are not required for stairways accessed from a refuge area in conjunction with a horizontal exit.
[BE] 1009.4 Elevators. In order to be considered part of an accessible means of egress, an elevator shall comply with California Code of Regulations, Title 8, Division 1, Chapter 4, Subchapter 6, Elevator Safety Orders.
[BE] 1009.4.1 Standby power. The elevator shall meet the emergency operation and signaling device requirements of California Code of Regulations, Title 8, Division 1, Chapter 4, Subchapter 6, Elevator Safety Orders . Standby power shall be provided in accordance with Chapter 27 and Section 3003 of the California Building Code .
[BE] 1009.4.2 Area of refuge. The elevator shall be accessed from an area of refuge complying with Section 1009.6.
Exceptions:
Areas of refuge are not required at the elevator in open parking garages.
Areas of refuge are not required in buildings and facilities equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
Areas of refuge are not required at elevators not required to be located in a shaft in accordance with Section 712 of the California Building Code .
Areas of refuge are not required at elevators serving smoke protected or open-air assembly seating areas complying with Sections 1030.6.2 and 1030.6.3.
Areas of refuge are not required for elevators accessed from a refuge area in conjunction with a horizontal exit.
[BE] 1009.5 Platform lifts. Platform lifts shall be permitted to serve as part of an accessible means of egress where allowed as part of a required accessible route in Chapter 11B of the California Building Code except for Item 10. Standby power for the platform lift shall be provided in accordance with Chapter 27 of the California Building Code .
[BE] 1009.6 Areas of refuge. Every required area of refuge shall be accessible from the space it serves by an accessible means of egress.
[BE] 1009.6.1 Travel distance. The maximum travel distance from any accessible space to an area of refuge shall not exceed the exit access travel distance permitted for the occupancy in accordance with Section 1017.1.
[BE] 1009.6.2 Stairway or elevator access. Every required area of refuge shall have direct access to a stairway complying with Sections 1009.3 and 1023 or an elevator complying with Section 1009.4.
Exception: An interior area of refuge at the level of exit discharge that provides direct access to an exterior exit door.
[BE] 1009.6.3 Size. Each area of refuge shall be sized to accommodate two wheelchair space s that are not less than of 30 inches by 52 inches (762 mm by 1321 mm) for each 200 occupants or portion thereof, based on the occupant load of the area of refuge and areas served by the area of refuge. The total number of such 30-inch by 52-inch (762 mm by 1320 mm) spaces per story shall be not less than one for every 200 persons of calculated occupant load served by the area of refuge. Such wheelchair spaces shall not reduce the means of egress minimum width or required capacity. Access to any of the required wheelchair spaces in an area of refuge shall not be obstructed by more than one adjoining wheelchair space.
Exception: The enforcing agency may reduce the size of each required area of refuge to accommodate one wheelchair space that is not less than 30 inches by 52 inches (762 mm by 1320 mm) on floors where the occupant load is less than 200.
[BE] 1009.6.4 Separation. Each area of refuge shall be separated from the remainder of the story by a smoke barrier complying with Section 709 of the California Building Code or a horizontal exit complying with Section 1026. Each area of refuge shall be designed to minimize the intrusion of smoke.
Exceptions:
- Areas of refuge located within an enclosure for interior exit stairways complying with Section 1023.
- Areas of refuge in outdoor facilities where exit access is essentially open to the outside.
[BE] 1009.6.5 Two-way communication. Areas of refuge shall be provided with a two-way communication system complying with Sections 1009.8.1 and 1009.8.2.
[BE] 1009.7 Exterior areas for assisted rescue. Exterior areas for assisted rescue shall be accessed by an accessible route from the area served.
Where the exit discharge does not include an accessible route from an exit located on the level of exit discharge to a public way, an exterior area of assisted rescue shall be provided on the exterior landing in accordance with Sections 1009.7.1 through 1009.7.4.
10-18 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
[BE] 1009.7.1 Size. Each exterior area for assisted rescue shall be sized to accommodate wheelchair spaces in accordance with Section 1009.6.3.
[BE] 1009.7.2 Separation. Exterior walls separating the exterior area of assisted rescue from the interior of the building shall have a minimum fire-resistance rating of 1 hour, rated for exposure to fire from the inside. The fire-resistance-rated exterior wall construction shall extend horizontally not less than 10 feet (3048 mm) beyond the landing on either side of the landing or equivalent fire-resistance-rated construction is permitted to extend out perpendicular to the exterior wall not less than 4 feet (1219 mm) on the side of the landing. The fire-resistance-rated construction shall extend vertically from the ground to a point not less than 10 feet (3048 mm) above the floor level of the area for assisted rescue or to the roof line, whichever is lower. Openings within such fire-resistance-rated exterior walls shall be protected in accordance with Section 716 of the California Building Code . Exception: The fire-resistance rating and opening protectives are not required in the exterior wall where the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
[BE] 1009.7.3 Openness. The exterior area for assisted rescue shall be open to the outside air. The sides other than the separation walls shall be not less than 50 percent open, and the open area shall be distributed so as to minimize the accumulation of smoke or toxic gases.
[BE] 1009.7.4 Stairways. S tairways that are part of the means of egress for the exterior area for assisted rescue shall provide a minimum clear width of 48 inches (1219 mm) between handrails. Exception: The minimum clear width of 48 inches (1219 mm) between handrails is not required at stairways serving buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
[BE] 1009.8 Two-way communication. A two-way communication system complying with Sections 1009.8.1 and 1009.8.2 shall be provided at the landing serving each elevator or bank of elevators on each accessible floor that is one or more stories above or below the level of exit discharge. Exceptions:
Two-way communication systems are not required at the landing serving each elevator or bank of elevators where the two-way communication system is provided within areas of refuge in accordance with Section 1009.6.5.
Two-way communication systems are not required on floors provided with ramps conforming to the provisions of Section 1012.
Two-way communication systems are not required at the landings serving only service elevators that are not designated as part of the accessible means of egress or serve as part of the required accessible route into a facility.
Two-way communication systems are not required at the landings serving only freight elevators.
Two-way communication systems are not required at the landing serving a private residence elevator.
Two-way communication systems are not required in Group I-2 or I-3 facilities.
signated as part of the accessible means of egress or serve as part of the required accessible route into a facility. 4. Two-way communication systems are not required at the landings serving only freight elevators. 5. Two-way communication systems are not required at the landing serving a private residence elevator. 6. Two-way communication systems are not required in Group I-2 or I-3 facilities.
[BE] 1009.8.1 System requirements. Two-way communication systems shall provide communication between each required location and the fire command center or a central control point location approved by the fire department. Where the central control point is not a constantly attended location, the two-way communication system shall have a timed automatic telephone dial-out capability that provides two-way communication with an approved supervising station or emergency services. The twoway communication system shall include both audible and visible signals. Systems shall be listed in accordance with UL 2525 and installed in accordance with NFPA 72.
[BE] 1009.8.2 Directions. Directions for the use of the two-way communication system, instructions for summoning assistance via the two-way communication system and written identification of the location shall be posted adjacent to the two-way communication system. Signage shall comply with Chapter 11A, Section 1143A of the California Building Code requirements for visual characters.
[BE] 1009.9 Signage. Signage indicating special accessibility provisions shall be provided as shown:
Each door providing access to an area of refuge from an adjacent floor area shall be identified by a sign stating: “AREA OF REFUGE.”
Each door providing access to an exterior area for assisted rescue shall be identified by a sign stating: “EXTERIOR AREA FOR ASSISTED RESCUE.”
Signage shall comply with the ICC A117.1 requirements for visual characters and include the International Symbol of Accessibility. Where exit sign illumination is required by Section 1013.3, the signs shall be illuminated. Additionally, visual characters, raised character and braille signage complying with ICC A117.1 shall be located at each door to an area of refuge and exterior area for assisted rescue in accordance with Section 1013.4.
[BE] 1009.10 Directional signage. Directional signage complying with Chapter 11B, Section 11B-703.5, indicating the location of all other means of egress and which of those are accessible means of egress shall be provided at the following:
- At exits serving a required accessible space but not providing an approved accessible means of egress.
- At elevator landings.
- Within areas of refuge.
[BE] 1009.11 Instructions. In areas of refuge, exterior areas for assisted rescue and locations required to provide two-way communications systems complying with Section 1009.8, instructions on the use of the area under emergency conditions shall be posted. Signage shall comply with the ICC A117.1 requirements for visual characters. The instructions shall include all of the following:
- Persons able to use the exit stairway do so as soon as possible, unless they are assisting others.
ations required to provide two-way communications systems complying with Section 1009.8, instructions on the use of the area under emergency conditions shall be posted. Signage shall comply with the ICC A117.1 requirements for visual characters. The instructions shall include all of the following:
- Persons able to use the exit stairway do so as soon as possible, unless they are assisting others.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
�
�
�
MEANS OF EGRESS
Information on planned availability of assistance in the use of stairs or supervised operation of elevators and how to summon such assistance.
Directions for use of the two-way communication system where provided.
1009.12 Alarms and emergency warning systems and two-way communication systems. ¶
Required emergency warning systems shall activate a means of warning the hearing impaired. Emergency warning systems provided as part of the fire-alarm system and two-way communication systems required by Chapter 10 shall be designed and installed in accordance with NFPA 72 as amended in Chapter 80.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Fire Code (Title 24, Part 9)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REQUIREMENTS
- Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
- Chapter 5 — FIRE SERVICE FEATURES
- Chapter 6 — BUILDING SERVICES AND SYSTEMS
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
-
▸ Chapter 10 — MEANS OF EGRESS
Overview- Section 1001 — ADMINISTRATION
- Section 1002 — DEFINITIONS
- Section 1003 — GENERAL MEANS OF EGRESS
- Section 1004 — OCCUPANT LOAD
- Section 1005 — MEANS OF EGRESS SIZING
- Section 1006 — NUMBERS OF EXITS AND EXIT ACCESS DOORWAYS
- Section 1007 — EXIT AND EXIT ACCESS DOORWAY CONFIGURATION
- Section 1008 — MEANS OF EGRESS ILLUMINATION
- Section 1009 — ACCESSIBLE MEANS OF EGRESS
- Section 1010 — DOORS, GATES AND TURNSTILES
- Section 1011 — STAIRWAYS
- Section 1012 — RAMPS
- Section 1013 — EXIT SIGNS
- Section 1014 — HANDRAILS
- Section 1015 — GUARDS
- Section 1016 — EXIT ACCESS
- Section 1017 — EXIT ACCESS TRAVEL DISTANCE
- Section 1018 — AISLES
- Section 1019 — EXIT ACCESS STAIRWAYS AND RAMPS
- Section 1020 — CORRIDORS
- Section 1021 — EGRESS BALCONIES
- Section 1022 — EXITS
- Section 1023 — INTERIOR EXIT STAIRWAYS AND RAMPS
- Section 1024 — EXIT PASSAGEWAYS
- Section 1025 — LUMINOUS EGRESS PATH MARKINGS
- Section 1026 — HORIZONTAL EXITS
- Section 1027 — EXTERIOR EXIT STAIRWAYS AND RAMPS
- Section 1028 — EXIT DISCHARGE
- Section 1029 — EGRESS COURTS
- Section 1030 — ASSEMBLY
- Section 1031 — EMERGENCY ESCAPE AND RESCUE
- Section 1032 — MAINTENANCE OF THE MEANS OF EGRESS
- Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
- Chapter 12 — ENERGY SYSTEMS
- Chapter 20 — AVIATION FACILITIES
- Chapter 21 — DRY CLEANING
- Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
- Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
- Chapter 24 — FLAMMABLE FINISHES
- Chapter 25 — FRUIT AND CROP RIPENING
- Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
- Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
- Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
- Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
- Chapter 30 — INDUSTRIAL OVENS
- Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
- Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
- Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
- Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
- Chapter 35 — WELDING AND OTHER HOT WORK
- Chapter 36 — MARINAS
- Chapter 37 — COMBUSTIBLE FIBERS
- Chapter 38 — RESERVED
- Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
- Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
- Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
- Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
- Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
- Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
- Chapter 51 — AEROSOLS
- Chapter 52 — RESERVED
- Chapter 53 — COMPRESSED GASES
- Chapter 54 — CORROSIVE MATERIALS
- Chapter 55 — CRYOGENIC FLUIDS
- Chapter 56 — EXPLOSIVES AND FIREWORKS
- Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
- Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
- Chapter 59 — FLAMMABLE SOLIDS
- Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
- Chapter 61 — LIQUEFIED PETROLEUM GASES
- Chapter 62 — ORGANIC PEROXIDES
- Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
- Chapter 64 — PYROPHORIC MATERIALS
- Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
- Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
- Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
- Chapter 80 — REFERENCED STANDARDS
- Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
- Appendix A — BOARD OF APPEALS
- Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix D — FIRE APPARATUS ACCESS ROADS
- Appendix E — HAZARD CATEGORIES
- Appendix F — HAZARD RANKING
- Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
- Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
- Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
- Appendix J — BUILDING INFORMATION SIGN
- Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
- Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
- Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
- Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
- Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
- Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
- Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…