Section 1017 — EXIT ACCESS TRAVEL DISTANCE
2025 California Fire Code (Title 24, Part 9) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
[BE] 1017.1 General. Travel distance within the exit access portion of the means of egress system shall be in accordance with this section. [BE] 1017.2 Limitations. Exit access travel distance shall not exceed the values given in Table 1017.2. [BE] TABLE 1017.2—EXIT ACCESS TRAVEL DISTANCEaCol2Col3 --------- OCCUPANCYWITHOUT AUTOMATIC SPRINKLER SYSTEM<br(feet)WITH AUTOMATIC SPRINKLER SYSTEM<br(feet) A, E, F-1, M, R, S-1200250b, e R-2.1Not Permitted250b B200300c F-2, S-2, U300400c H-1Not Permitted75d H-2Not Permitted100d H-3Not Permitted150d H-4Not Permitted175d H-5Not Permitted200c I-2,…