Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS

Section A403 — ANALYSIS AND DESIGN

2025 California Existing Building Code (Title 24, Part 10) · 2025 edition · updated 2026-07-27 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

[BS] A403.1 General. Modifications required by the provisions in this chapter shall be designed in accordance with the California Building Code provisions for new construction, except as modified by this chapter.

Exception: Buildings for which the prescriptive measures provided in Section A404 apply and are used.

Alteration of the existing lateral force-resisting system or vertical load-carrying system shall not reduce the strength or stiffness of the existing structure, unless the altered structure would remain in conformance to the building code and this chapter.

[BS] A403.2 Scope of analysis. This chapter requires the alteration, repair, replacement or addition of structural elements and their connections to meet the strength and stiffness requirements herein. The lateral load-path analysis shall include the resisting elements and connections from the wood diaphragm immediately above any soft, weak or open-front wall lines to the foundation soil interface or to the uppermost story of a podium structure comprised of steel, masonry, or concrete structural systems that supports the upper woodframed structure. Stories above the uppermost story with a soft, weak or open-front wall line shall be considered in the analysis but need not be modified. The lateral load-path analysis for added structural elements shall include evaluation of the allowable soil-bearing and lateral pressures in accordance with the building code. Where any portion of a building within the scope of this chapter is constructed on or into a slope steeper than one unit vertical in three units horizontal (33-percent slope), the lateral force-resisting system at and below the base level diaphragm shall be analyzed for the effects of concentrated lateral forces at the base caused by this hillside condition.

[BS] A403.3 Design base shear and design parameters. The design base shear in a given direction shall be permitted to be 75 percent of the value required for similar new construction in accordance with the building code. The value of R used in the design of the strengthening of any story shall not exceed the lowest value of R used in the same direction at any story above. The system overstrength factor, Ω 0, and the deflection amplification factor, C d, shall be not less than the largest respective value corresponding to the R factor being used in the direction under consideration.

Exceptions:

  1. For structures assigned to Seismic Design Category B, values of R, Ω 0 and C d shall be permitted to be based on the seismic force-resisting system being used to achieve the required strengthening.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX A—GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS

  1. For structures assigned to Seismic Design Category C or D, values of R, Ω 0 and C d shall be permitted to be based on the seismic force-resisting system being used to achieve the required strengthening, provided that when the strengthening is complete, the strengthened structure will not have an extreme weak story irregularity defined as Type 5b in ASCE 7, Table 12.3-2.

  2. For structures assigned to Seismic Design Category E, values of R, Ω 0 and C d shall be permitted to be based on the seismic force-resisting system being used to achieve the required strengthening, provided that when the strengthening is complete, the strengthened structure will not have an extreme soft story, a weak story, or an extreme weak story irregularity defined, respectively, as Types 1b, 5a and 5b in ASCE 7, Table 12.3-2.

  3. For retrofit systems involving different seismic force-resisting systems in the same direction within the same story, resisting elements are permitted to be designed using the least value of R for the different structural systems found in each independent line of resistance if all of the following conditions are met: 4.1. The building is assigned to Risk Category I or II. 4.2. The building height is no more than four stories above grade plane. 4.3. The seismic force-resisting systems of the retrofitted building comprise only wood structural panel shear walls, steel moment-resisting frames, steel cantilever columns and steel-braced frames. Values for C and Ω 0 shall be consistent with the R value used.

  4. With reference to ASCE 7, Table 12.2-1, ordinary, intermediate and special steel systems, and all light-frame systems shall be permitted without limitation where those systems are used only for retrofit to comply with the requirements of this chapter.

[BS] A403.3.1 Expected story strength. Despite any other requirement of Section A403.3 or A403.4, the total expected strength of retrofit elements added to any story need not exceed 1.7 times the expected strength of the story immediately above in a twostory building, or 1.3 times the expected strength of the story immediately above in a three-story or taller building, as long as the retrofit elements are located symmetrically about the center of mass of the story above, or so as to minimize torsion in the retrofitted story. Calculation of expected story strength and identification of irregularities in Section A403.3 shall be based on the expected strength of all wall lines, even if sheathed with nonconforming materials. The strength of a wall line above the retrofitted story shall be permitted to be reduced to account for inadequate load path or overturning resistance.

[BS] A403.3.2 Seismicity parameters, site class and geologic hazards. For any site designated as Site Class E, the value of F shall be taken as 1.2. Site-specific procedures are not required for compliance with this chapter. Mitigation of existing geologic site hazards such as liquefiable soil, fault rupture or landslide is not required for compliance with this chapter.

[BS] A403.4 Story drift limitations. The calculated story drift for each retrofitted story shall not exceed the allowable deformation compatible with all vertical load-resisting elements and 0.025 times the story height. The calculated story drift shall not be reduced by the effects of horizontal diaphragm stiffness but shall be increased where these effects produce rotation. Drift calculations shall be in accordance with the building code.

culated story drift for each retrofitted story shall not exceed the allowable deformation compatible with all vertical load-resisting elements and 0.025 times the story height. The calculated story drift shall not be reduced by the effects of horizontal diaphragm stiffness but shall be increased where these effects produce rotation. Drift calculations shall be in accordance with the building code.

[BS] A403.4.1 Pole structures. The effects of rotation and soil stiffness shall be included in the calculated story drift where lateral loads are resisted by vertical elements whose required depth of embedment is determined by pole formulas. The coefficient of subgrade reaction used in deflection calculations shall be based on a geotechnical investigation conducted in accordance with the building code.

[BS] A403.5 Deformation compatibility and P Δ effects. The requirements of the building code shall apply, except as modified herein. Structural framing elements and their connections not required by design to be part of the lateral force-resisting system shall be designed and detailed to be adequate to maintain support of expected gravity loads when subjected to the expected deformations caused by seismic forces. Increased demand caused by P Δ effects and story sidesway stability shall be considered in retrofit stories that rely on the strength and stiffness of cantilever columns for lateral resistance.

[BS] A403.6 Ties and continuity. All parts of the structure included in the scope of Section A403.2 shall be interconnected as required by the building code.

[BS] A403.7 Collector elements. Collector elements shall be provided to transfer the seismic forces between the elements within the scope of Section A403.2.

[BS] A403.8 Floor diaphragms. Floor diaphragms within the scope of Section A403.2 shall be shown to have adequate strength at the following locations:

  1. For straight lumber sheathed diaphragms without integral hardwood flooring throughout the diaphragm: The code official is authorized to waive the requirement where it is shown that the condition occurs in areas small enough not to affect overall building performance.
  2. For all other diaphragms adequate strength shall be shown to be provided at locations where forces are transferred between the diaphragm and each new or strengthened vertical element of the seismic force-resisting system. Collector elements shall be provided where needed to distribute the transferred force over a greater length of diaphragm.

Exception: Where the existing vertical elements of the seismic force-resisting system are shown to comply with this chapter, diaphragms need not be evaluated.

[BS] A403.9 Wood-framed shear walls. Wood-framed shear walls shall have strength and stiffness sufficient to resist the seismic loads and shall conform to the requirements of this section. Where new sheathing is applied to existing studs to create new wood

APPENDIX A-46 2025 CALIFORNIA EXISTING BUILDING CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX A—GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS

framed shear walls, the new wall elements shall be considered bearing wall systems for purposes of determining seismic design parameters.

[BS] A403.9.1 Gypsum or cement plaster products. Gypsum or cement plaster products shall not be used to provide the strength required by Section A403.3 or the stiffness required by Section A403.4.

[BS] A403.9.2 Wood structural panels.

[BS] A403.9.2.1 Drift limit. Wood structural panel shear walls shall meet the story drift limitation of Section A403.4. Conformance to the story drift limitation shall be determined by approved testing or calculation. Individual shear panels shall be permitted to exceed the maximum aspect ratio, provided that the allowable story drift and allowable shear capacities are not exceeded.

[BS] A403.9.2.2 Openings. Shear walls are permitted to be designed for continuity around openings in accordance with the building code. Blocking and steel strapping shall be provided at corners of the openings to transfer forces from discontinuous boundary elements into adjoining panel elements. Alternatively, perforated shear wall provisions of the building code are permitted to be used.

[BS] A403.9.3 Hold-down connectors.

[BS] A403.9.3.1 Expansion anchors in tension. Expansion anchors that provide tension strength by friction resistance shall not be used to connect hold-down devices to existing concrete or masonry elements.

[BS] A403.9.3.2 Required depth of embedment. The required depth of embedment or edge distance for the anchor used in the hold-down connector shall be provided in the concrete or masonry below any plain concrete slab unless satisfactory evidence is submitted to the code official that shows that the concrete slab and footings are of monolithic construction.

A403.10 Steel retrofit systems.

Steel retrofit systems shall have strength and stiffness sufficient to resist the seismic loads and shall conform to the requirements of this section.

A403.10.1 Special moment frames. Steel special moment frames shall comply with all applicable provisions of AISC 341, except that Section E3.4a addressing strong-column/weak-beams of AISC 341, is not required for columns that carry no gravity load.

A403.10.2 Inverted moment frame systems. Cantilevered column systems shall be permitted to be designed as inverted special, intermediate or ordinary moment frames, with corresponding moment frame seismic design coefficients, where the system satisfies the following conditions:

  1. The columns carry no gravity load.

  2. The columns are configured in pairs or larger groups connected by a continuous reinforced concrete foundation or grade beam.

  3. The foundation or grade beam shall be designed to resist the expected plastic moment at the base of each column, computed as R y F y Z in accordance with AISC 341.

  4. The flexibility of the foundation or grade beam, considering cracked section properties of the reinforced concrete, shall be included in computing the deformation of the steel frame system.

  5. The column height shall be taken as twice the actual height when checking lateral torsional buckling.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Existing Building Code (Title 24, Part 10)
2025 California Existing Building Code (Title 24, Part 10)
  1. 104.11 for consideration of alternative means of compliance.
  2. Chapter 1 — ADMINISTRATION
  3. Chapter 2 — DEFINITIONS
  4. Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
  5. Chapter 3A — PROVISIONS FOR ALL COMPLIANCE METHODS
  6. Chapter 4 — REPAIRS
  7. Chapter 4A — REPAIRS
  8. Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
  9. Chapter 5A — PRESCRIPTIVE COMPLIANCE METHOD
  10. Chapter 6 — CLASSIFICATION OF WORK
  11. Chapter 7 — ALTERATIONS—LEVEL 1
  12. Chapter 8 — ALTERATIONS—LEVEL 2
  13. Chapter 9 — ALTERATIONS—LEVEL 3
  14. Chapter 10 — CHANGE OF OCCUPANCY
  15. Chapter 11 — ADDITIONS
  16. Chapter 12 — HISTORIC BUILDINGS
  17. Chapter 13 — PERFORMANCE COMPLIANCE METHODS
  18. Chapter 14 — RELOCATED OR MOVED BUILDINGS
  19. Chapter 15 — CONSTRUCTION SAFEGUARDS
  20. Chapter 16 — REFERENCED STANDARDS
  21. Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING B…
  22. Appendix B — SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS FOR EXIS…
  23. Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUIL…
  24. Appendix D — BOARD OF APPEALS
  25. Appendix E — TEMPORARY EMERGENCY USES
  26. Appendix A — GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS A…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.