[BS] A110.1 Minimum design lateral forces. Buildings shall be analyzed to resist minimum lateral forces assumed to act nonconcurrently in the direction of each of the main axes of the structure in accordance with the following:

Equation A1-5

V = 0.75----------------------- S DS W - R

APPENDIX A-10 2025 CALIFORNIA EXISTING BUILDING CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX A—GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS

[BS] A110.2 Seismic forces on elements of structures. Parts and portions of a structure not covered in Section A110.3 shall be analyzed and designed per the current building code, using force levels defined in Section A110.1.

Exceptions:

  1. Unreinforced masonry walls for which height-to thickness ratios do not exceed ratios set forth in Table A110.2 need not be analyzed for out-of-plane loading. Unreinforced masonry walls that exceed the allowable h/t ratios of Table A110.2 shall be braced according to Section A113.5.
  2. Parapets complying with Section A113.6 need not be analyzed for out-of-plane loading.
  3. Where walls are to be anchored to flexible floor and roof diaphragms, the anchorage shall be in accordance with Section A113.1.

A110.2 need not be analyzed for out-of-plane loading. Unreinforced masonry walls that exceed the allowable h/t ratios of Table A110.2 shall be braced according to Section A113.5. 2. Parapets complying with Section A113.6 need not be analyzed for out-of-plane loading. 3. Where walls are to be anchored to flexible floor and roof diaphragms, the anchorage shall be in accordance with Section A113.1.

[BS] TABLE A110.2—ALLOWABLE VALUE OF HEIGHT-TO-THICKNESS RATIO OF UNREINFORCED MASONRY WALLS

WALL TYPES 0.13g ≤ S_D_1 < 0.25g 0.25g ≤****_SD_1 < 0.4g _SD_1 ≥ 0.4g
BUILDINGS WITH
CROSSWALLSa
_SD_1 ≥ 0.4g
ALL OTHER
BUILDINGS
Walls of one-story buildings 20 16 16b, c 13
First-story wall of multiple-story building 20 18 16 15
Walls in top story of multiple-story building 14 14 14b, c 9
All other walls 20 16 16 13
For SI:1 pound per square inch = 6894.75 N/m2.
a. Applies to the special procedures of Section A111 only. See Section A111.7 for other restrictions.
b. This value of height-to-thickness ratio shall be used where mortar shear tests establish a tested mortar shear strength,vt, of not less than 100 pounds per square inch. This
value shall also be used where the tested mortar shear strength is not less than 60 pounds per square inch, and where a visual examination of the collar joint indicates not
less than 50-percent mortar coverage.
c. Where a visual examination of the collar joint indicates not less than 50-percent mortar coverage, and the tested mortar shear strength,vt, is greater than 30 pounds per
square inch but less than 60 pounds per square inch, the allowable height-to-thickness ratio may be determined by linear interpolation between the larger and smaller ratios
in direct proportion to the tested mortar shear strength.

[BS] A110.3 In-plane loading of URM shear walls and frames. Vertical seismic force-resisting elements shall be analyzed in accordance with Section A112.

[BS] A110.4 Redundancy and overstrength factors. Any redundancy or overstrength factors contained in the building code may be taken as unity. The vertical component of seismic force ( E v ) may be taken as zero.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Existing Building Code (Title 24, Part 10)
2025 California Existing Building Code (Title 24, Part 10)
  1. 104.11 for consideration of alternative means of compliance.
  2. Chapter 1 — ADMINISTRATION
  3. Chapter 2 — DEFINITIONS
  4. Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
  5. Chapter 3A — PROVISIONS FOR ALL COMPLIANCE METHODS
  6. Chapter 4 — REPAIRS
  7. Chapter 4A — REPAIRS
  8. Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
  9. Chapter 5A — PRESCRIPTIVE COMPLIANCE METHOD
  10. Chapter 6 — CLASSIFICATION OF WORK
  11. Chapter 7 — ALTERATIONS—LEVEL 1
  12. Chapter 8 — ALTERATIONS—LEVEL 2
  13. Chapter 9 — ALTERATIONS—LEVEL 3
  14. Chapter 10 — CHANGE OF OCCUPANCY
  15. Chapter 11 — ADDITIONS
  16. Chapter 12 — HISTORIC BUILDINGS
  17. Chapter 13 — PERFORMANCE COMPLIANCE METHODS
  18. Chapter 14 — RELOCATED OR MOVED BUILDINGS
  19. Chapter 15 — CONSTRUCTION SAFEGUARDS
  20. Chapter 16 — REFERENCED STANDARDS
  21. Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING B…
  22. Appendix B — SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS FOR EXIS…
  23. Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUIL…
  24. Appendix D — BOARD OF APPEALS
  25. Appendix E — TEMPORARY EMERGENCY USES
  26. Appendix A — GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS A…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.