Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS
Section A113 — DETAILED BUILDING SYSTEM DESIGN REQUIREMENTS
2025 California Existing Building Code (Title 24, Part 10) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
[BS] A113.1 Wall anchorage.
[BS] A113.1.1 Anchor locations. Unreinforced masonry walls shall be anchored at the roof and floor levels as required in Section A110.2. Ceilings of plaster or similar materials, where not attached directly to roof or floor framing and where abutting masonry walls, shall either be anchored to the walls at a maximum spacing of 6 feet (1829 mm) or be removed.
[BS] A113.1.2 Anchor requirements. Anchors shall consist of bolts installed through the wall as specified in Table A108.1(2), or an approved equivalent at a maximum anchor spacing of 6 feet (1829 mm). Wall anchors shall be secured to the framing members parallel or perpendicular to the wall to develop the required forces.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A—GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS
[BS] A113.1.3 Minimum wall anchorage. Anchorage of masonry walls to each floor or roof shall resist a minimum force determined as 0.9 S DS times the tributary weight or 200 pounds per linear foot (2920 N/m), whichever is greater, acting normal to the wall at the level of the floor or roof. Existing wall anchors, if used, must be tested and meet the requirements of Section A107.5.1 or be upgraded.
[BS] A113.1.4 Anchors at corners. At the roof and floor levels, both shear and tension anchors shall be provided within 2 feet (610 mm) horizontally from the inside of the corners of the walls.
[BS] A113.2 Diaphragm shear transfer. Anchors transmitting shear forces shall have a maximum spacing of 6 feet (1829 mm) and shall have nuts installed over malleable iron or plate washers where bearing on wood, and heavy-cut washers where bearing on steel.
[BS] A113.3 Collectors. Collector elements shall be provided that are capable of transferring the seismic forces originating in other portions of the building to the element providing the resistance to those forces.
[BS] A113.4 Ties and continuity. Ties and continuity shall conform to the requirements of the building code.
[BS] A113.5 Wall bracing.
[BS] A113.5.1 General. Where a wall height-to-thickness ratio exceeds the specified limits, the wall may be laterally supported by vertical bracing members per Section A113.5.2 or by reducing the wall height by bracing per Section A113.5.3.
[BS] A113.5.2 Vertical bracing members. Vertical bracing members shall be attached to floor and roof construction for their design loads independently of required wall anchors. Horizontal spacing of vertical bracing members shall not exceed one-half of the unsupported height of the wall or 10 feet (3048 mm). Deflection of such bracing members at design loads shall not exceed one-tenth of the wall thickness.
2 Vertical bracing members.** Vertical bracing members shall be attached to floor and roof construction for their design loads independently of required wall anchors. Horizontal spacing of vertical bracing members shall not exceed one-half of the unsupported height of the wall or 10 feet (3048 mm). Deflection of such bracing members at design loads shall not exceed one-tenth of the wall thickness.
[BS] A113.5.3 Intermediate wall bracing. The wall height may be reduced by bracing elements connected to the floor or roof. Horizontal spacing of the bracing elements and wall anchors shall be as required by design, but shall not exceed 6 feet (1829 mm) on center. Bracing elements shall be detailed to minimize the horizontal displacement of the wall by the vertical displacement of the floor or roof.
[BS] A113.6 Parapets. Parapets and exterior wall appendages not conforming to this chapter shall be removed, or stabilized or braced to ensure that the parapets and appendages remain in their original positions.
The maximum height of an unbraced unreinforced masonry parapet above the lower of either the level of tension anchors or the roof sheathing shall not exceed the height-to-thickness ratio shown in Table A113.6. If the required parapet height exceeds this maximum height, a bracing system designed for the forces determined in accordance with the building code shall support the top of the parapet. Parapet corrective work must be performed in conjunction with the installation of tension roof anchors.
The height of a URM parapet above any wall anchor shall be not less than 12 inches (305 mm).
Exception: If a reinforced concrete beam is provided at the top of the wall, the height above the wall anchor is permitted to be not less than 6 inches (152 mm).
| [BS] TABLE A113.6—MAXIMUM ALLOWABLE HEIGHT-TO-THICKNESS RATIO FOR PARAPETS | |||
|---|---|---|---|
| _SD_1 | _SD_1 | _SD_1 | |
| 0.13g ≤****_SD_1 ≤ 0.25g | 0.25g ≤****_SD_1 < 0.4g | _SD_1 ≥ 0.4g | |
| Maximum allowable height-to-thickness ratios | 2.5 | 2.5 | 1.5 |
[BS] A113.7 Veneer.
- Veneer shall be anchored with approved anchor ties conforming to the required design capacity specified in the building code and shall be placed at a maximum spacing of 24 inches (610 mm) with a maximum supported area of 4 square feet (0.372 m [2] ).
Exception: Existing anchor ties for attaching brick veneer to brick backing shall be acceptable, provided that the ties are in good condition and conform to the following minimum size and material requirements.
Existing veneer anchor ties shall be considered adequate if they are of corrugated galvanized iron strips not less than 1 inch (25 mm) in width, 8 inches (203 mm) in length and [1] / 16 inch (1.6 mm) in thickness, or the equivalent. 2. The location and condition of existing veneer anchor ties shall be verified as follows: 2.1. An approved testing laboratory shall verify the location and spacing of the ties and shall submit a report to the code official for approval as part of the structural analysis. 2.2. The veneer in a selected area shall be removed to expose a representative sample of ties (not less than four) for inspection by the code official.
[BS] A113.8 Nonstructural masonry walls. Unreinforced masonry walls that do not carry design vertical or lateral loads and that are not required by the design to be part of the lateral force-resisting system shall be adequately anchored to new or existing supporting elements. The anchors and elements shall be designed for the out-of-plane forces specified in the building code. The height- or length-to-thickness ratio between such supporting elements for such walls shall not exceed nine.
APPENDIX A-16 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A—GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS
[BS] A113.9 Truss and beam supports. Where trusses and beams other than rafters or joists are supported on masonry, independent secondary columns shall be installed to support vertical loads of the roof or floor members.
Exception: Secondary supports are not required where S D1 is less than 0.3g.
[BS] A113.10 Adjacent buildings. Where elements of adjacent buildings do not have a separation of 5 inches (127 mm) or greater, the allowable height-to-thickness ratios for “all other buildings” per Table A110.2 shall be used in the direction of consideration.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Existing Building Code (Title 24, Part 10)
- 104.11 for consideration of alternative means of compliance.
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 3A — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 4 — REPAIRS
- Chapter 4A — REPAIRS
- Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 5A — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 6 — CLASSIFICATION OF WORK
- Chapter 7 — ALTERATIONS—LEVEL 1
- Chapter 8 — ALTERATIONS—LEVEL 2
- Chapter 9 — ALTERATIONS—LEVEL 3
- Chapter 10 — CHANGE OF OCCUPANCY
- Chapter 11 — ADDITIONS
- Chapter 12 — HISTORIC BUILDINGS
- Chapter 13 — PERFORMANCE COMPLIANCE METHODS
- Chapter 14 — RELOCATED OR MOVED BUILDINGS
- Chapter 15 — CONSTRUCTION SAFEGUARDS
- Chapter 16 — REFERENCED STANDARDS
-
▸ Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING B…
Overview- Section A100 — APPLICATION
- Section A101 — PURPOSE
- Section A102 — SCOPE
- Section A103 — DEFINITIONS
- Section A104 — SYMBOLS AND NOTATIONS
- Section A105 — GENERAL REQUIREMENTS
- Section A106 — MATERIALS REQUIREMENTS
- Section A107 — QUALITY CONTROL
- Section A108 — DESIGN STRENGTHS
- Section A109 — ANALYSIS AND DESIGN PROCEDURE
- Section A110 — GENERAL PROCEDURE
- Section A111 — SPECIAL PROCEDURE
- Section A112 — ANALYSIS AND DESIGN
- Section A113 — DETAILED BUILDING SYSTEM DESIGN REQUIREMENTS
- Section A114 — WALLS OF UNBURNED CLAY, ADOBE OR STONE MASONRY
- Section A201 — PURPOSE
- Section A202 — SCOPE
- Section A203 — DEFINITIONS
- Section A204 — SYMBOLS AND NOTATIONS
- Section A205 — GENERAL REQUIREMENTS
- Section A206 — ANALYSIS AND DESIGN
- Section A207 — MATERIALS OF CONSTRUCTION
- Section A301 — GENERAL
- Section A302 — DEFINITIONS
- Section A303 — STRUCTURAL WEAKNESSES
- Section A304 — STRENGTHENING REQUIREMENTS
- Section A401 — GENERAL
- Section A402 — DEFINITIONS
- Section A403 — ANALYSIS AND DESIGN
- Section A404 — PRESCRIPTIVE MEASURES FOR WEAK STORY
- Section A405 — MATERIALS OF CONSTRUCTION
- Section A406 — CONSTRUCTION DOCUMENTS
- Section A407 — QUALITY CONTROL
- Section A501 — REFERENCED STANDARDS
- Appendix B — SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS FOR EXIS…
- Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUIL…
- Appendix D — BOARD OF APPEALS
- Appendix E — TEMPORARY EMERGENCY USES
- Appendix A — GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS A…