Chapter 11A — HOUSING ACCESSIBILITY
Section 1136A
California Building Code (Title 24, Part 2) · 2022 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
ELECTRICAL RECEPTACLE, SWITCH AND CONTROL HEIGHTS
1136A.1 Receptacle heights.¶
Electrical receptacle outlets on branch circuits of 30 amperes or less and communica- tion system receptacles shall be located no more than 48 inches (1219 mm) measured from the top of the receptacle outlet box nor less than 15 inches (381 mm) measured from the bottom of the receptacle outlet box to the level of the fin- ished floor or working platform. If the reach is over a phys- ical barrier or an obstruction (for example, a kitchen base cabinet), receptacles shall be located within the reach ranges specified in Section 1138A.3. Physical barriers and obstructions shall not extend more than 25 inches (635 mm) from the wall beneath the receptacle. Countertops shall be allowed to extend 25 1 /2 inches (647.7 mm) from the wall beneath the receptacle.
Receptacle outlets that do not satisfy these specifications are acceptable provided that comparable receptacle outlets, that perform the same functions, are provided within the same area and are accessible.
Exceptions:
1. Receptacle outlets installed as part of permanently installed baseboard heaters are exempt.
2. Required receptacle outlets shall be permitted in floors when adjacent to sliding panels or walls.
3. Baseboard electrical outlets used in relocatable partitions, window walls or other electrical conve- nience floor outlets are not subject to the minimum height requirements.
4. This section shall not apply to existing buildings when the enforcing agency determines that compli- ance with these standards would create an unrea- sonable hardship.
1136A.2 Switch and control heights.¶
Controls or switches intended to be used by the occupant of the room or area to control lighting and receptacle outlets, appliances, alarms or cooling, heating and ventilating equipment shall be located no more than 48 inches (1219 mm) measured from the top of the outlet box nor less than 15 inches (381 mm) measured
HOUSING ACCESSIBILITY
from the bottom of the outlet box to the level of the finished floor or working platform. If the reach is over a physical bar- rier or an obstruction (for example, a kitchen base cabinet) switches and controls shall be located within the reach ranges specified in Section 1138A.3. Physical barriers or obstructions shall not extend more than 25 inches (635 mm) from the wall beneath a control or switch. Countertops shall be allowed to extend 25 1 /2 inches (647.7 mm) from the wall beneath a control or switch.
Switches and controls that do not satisfy these specifica- tions are acceptable provided that comparable controls or outlets, that perform the same functions, are provided within the same area and are accessible.
Exception: Appliances (e.g., kitchen stoves, dishwashers, range hoods, microwave ovens and similar appliances) which have controls located on the appliance.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
HOUSING ACCESSIBILITY
Division V – FEATURES COMMON TO EXTERIOR AND INTERIOR OF BUILDINGS
Division V Table of Contents
Section 1137A Other Features and Facilities
Section 1138A Space Allowances and Reach Ranges
Section 1139A Accessible Drinking Fountains
Section 1140A Accessible Telephones
Section 1141A Accessible Swimming Pools
Section 1142A Electrical Receptacle, Switch and Con- trol Heights
Section 1143A Signage
Section 1144A through 1149A Reserved
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Building Code (Title 24, Part 2)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix G — FLOOD-RESISTANT
- Appendix L — EARTHQUAKE RECORDING
- Appendix M — TSUNAMI-GENERATED
- Appendix N — REPLICABLE
- Appendix O — PERFORMANCE-BASED
- Chapter 1 — SCOPE AND ADMINISTRATION
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
▸Chapter 11A — HOUSING ACCESSIBILITY
Overview- Section 1101A
- Section 1102A
- Section 1103A
- Section 1104A
- Section 1105A
- Section 1106A
- Section 1107A
- Section 1108A
- Section 1109A
- Section 1110A
- Section 1111A
- Section 1112A
- Section 1113A
- Section 1114A
- Section 1115A
- Section 1116A
- Section 1117A
- Section 1118A
- Section 1119A
- Section 1120A
- Section 1121A
- Section 1122A
- Section 1123A
- Section 1124A
- Section 1125A
- Section 1126A
- Section 1127A
- Section 1128A
- Section 1129A
- Section 1130A
- Section 1131A
- Section 1132A
- Section 1133A
- Section 1134A
- Section 1135A
- Section 1136A
- Section 1137A
- Section 1138A
- Section 1139A
- Section 1140A
- Section 1141A
- Section 1142A
- Section 1143A
- Section 1144A
- Section 1145A
- Section 1146A
- Section 1147A
- Section 1148A
- Section 1149A
- Section 1150A
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 22 — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U – AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix F — RODENTPROOFING
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
- Appendix P — EMERGENCY HOUSING