1124A.1 General.¶
Elevators provided in covered multifamily buildings shall be accessible. Elevators required to be acces- sible shall comply with this chapter, ASME A17.1 (Safety Code for Elevators and Escalators), Title 8 of the California Code of Regulations, under “Elevator Safety Orders,” and any other applicable safety regulations of other administra- tive authorities having jurisdiction.
Exception: Private elevators serving only one dwelling unit.
1124A.2 Location.¶
Passenger elevators shall be located on a major accessible route and provisions shall be made to ensure that they remain accessible and usable at all times that the building is occupied.
1124A.3 Size of cab and control locations.¶
1124A.3.1 General. Elevators serving covered multifamily buildings shall be sized to accommodate a wheelchair in accordance with this section.
Exception: When the enforcing agency determines that compliance with any requirement of this section would create an unreasonable hardship, an exception to the requirement shall be granted when equivalent facilitation is provided, and where it can be demonstrated that a per- son using a wheelchair can enter and operate the elevator. 1124A.3.2 Car inside. The elevator car shall be designed to comply with one of the following:
1. Door centered on the wall. When the door is cen- tered on the car wall, it shall provide a clear width of 42 inches (1067 mm) minimum, and the clear dis- tance between car side walls shall be 80 inches (2032 mm) minimum. The clear distance between the back wall and the return panel shall be 51 inches (1295 mm) minimum. The clear distance between the back wall and the inside face of the door shall be 54 inches (1372 mm) minimum.
2. Door not centered on the wall. When the door is not centered on the car wall, it shall provide a clear width of 36 inches (914 mm) minimum, and the clear distance between car side walls shall be 68 inches (1727 mm) minimum. The clear distance between the back wall and the return panel shall be 51 inches (1295 mm) minimum. The clear distance between the back wall and the inside face of the door shall be 54 inches (1372 mm) minimum.
3. Door at any location. An elevator door with 36 inches (914 mm) minimum clear width may be installed at any location if one of the following is met:
3.1. The car inside, with the door closed, shall provide a turning clear space at least 60 inches (1524 mm) in diameter to allow for the turning of a wheelchair.
3.2. The clear distance between car side walls shall be 54 inches (1372 mm) minimum. The clear distance between the back wall and the return panel shall be 80 inches (2032 mm)
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
HOUSING ACCESSIBILITY
minimum. The clear distance between the back wall and the inside face of the door shall be 80 inches (2032 mm) minimum.
Note: See Table 1124A.3.2 and Figure 11A-7A. 1124A.3.3 Car controls.
1124A.3.3.1 Car control location. Elevator floor but- tons shall be located within one of the reach ranges specified in Section 1138A.3. Except for photoelectric tube bypass switches, emergency controls, including the emergency stop and alarm, shall be grouped in or adjacent to the bottom of the panel and shall be no lower than 35 inches (889 mm) from the floor. For mul- tiple controls, only one set must comply with these height requirements. Floor buttons shall be provided with visual indicators to show when each call is regis- tered. The visual indicators shall be extinguished when each call is answered.
1124A.3.3.2 Car control buttons. Passenger elevator car controls shall have a minimum dimension of 3 /4 inch (19.1 mm) and shall be raised 1 /8 inch (3.2 mm) plus or minus 1 /32 inch (0.8 mm) above the surrounding surface.
Control buttons shall be illuminated, shall have square shoulders and shall be activated by a mechani- cal motion that is detectable.
All control buttons shall be designated by a 5 /8-inch- minimum (15.9 mm) raised characters and standard raised symbols that comply with Sections 1143A.6 and 1143A.7 immediately to the left of the control button. Contracted Grade 2 Braille that conforms to Section 1143A.7 shall be located immediately below the numeral, character or symbol. A minimum clear space of 3 /8 inch (9.5 mm) or other suitable means of separa- tion shall be provided between rows of control buttons. (See Figure 11A-7B.)
The raised characters and symbols shall be white on a black background. Controls and emergency equip- ment identified by raised symbols shall include, but not be limited to, “door open,” “door close,” “alarm bell,” “emergency stop” and “telephone.” The call
button for the main entry floor shall be designated by a raised star at the left of the floor designation. 1124A.3.4 Emergency telephone. When an emergency telephone system is installed, the emergency telephone handset shall be positioned no higher than 48 inches (1219 mm) above the floor, and the handset cord shall be a minimum of 29 inches (737 mm) in length. If the tele- phone system is located in a closed compartment, the com- partment door hardware shall conform to the provisions of Section 1138A.4.4. Emergency intercommunication shall not require voice communication.
1124A.4 Hall call buttons.¶
Call operation buttons and key- pads shall be located within one of the reach ranges specified in Section 1138A.3, measured to the centerline of the high- est operable part. Buttons shall have square shoulders, shall be a minimum of 3 /4 inch (19.1 mm) in size, and shall be raised 1 /8 inch (3.2 mm) plus or minus 1 /32 inch (0.8 mm) above the surrounding surface. The button designating the “Up” direction shall be on top. A clear floor or ground space complying with Section 1138A.1.4 shall be provided at call controls.
Visual indication shall be provided to show each call reg- istered and extinguished when answered. Objects adjacent to, and below, hall call buttons shall not project more than 4 inches (101.6 mm) from the wall. Hall call buttons shall be internally illuminated with a white light over the entire sur- face of the button.
1124A.5 Minimum illumination.¶
The minimum illumination at the car controls threshold and the landing when the car and landing doors are open shall not be less than 5 foot-can- dles (54 lx).
1124A.6 Hall lantern.¶
A visual and audible signal shall be provided at each hoistway entrance indicating to the pro- spective passenger the car answering the call and its direc- tion of travel as follows:
1. The visual signal for each direction shall be a minimum of 2 1 /2 inches (63.5 mm) high by 2 1 /2 inches (63.5 mm) wide, and visible from the proximity of the hall call but- ton.
| TABLE 1124A.3.2 ELEVATOR CAR DIMENSIONS | ||||
|---|---|---|---|---|
| MINIMUM DIMENSIONS | MINIMUM DIMENSIONS | MINIMUM DIMENSIONS | MINIMUM DIMENSIONS | |
| DOOR LOCATION |
DOOR CLEAR WIDTH |
INSIDE CAR, SIDE TO SIDE |
INSIDE CAR, BACK WALL TO FRONT RETURN |
INSIDE CAR, BACK WALL TO INSIDE FACE OF DOOR |
| Centered | 42 inches (1067 mm) |
80 inches (2032 mm) |
51 inches (1295 mm) |
54 inches (1372 mm) |
| Side (off-centered) |
36 inches (914 mm)1 |
68 inches (1727 mm) |
51 inches (1295 mm) |
54 inches (1372 mm) |
| Any | 36 inches (914 mm)1 |
54 inches (1372 mm) |
80 inches (2032 mm) |
80 inches (2032 mm) |
| Any | 36 inches (914 mm)2 |
60 inches (1524 mm)2 |
60 inches (1524 mm)2 |
60 inches (1524 mm)2 |
1. A tolerance of minus 5 /8 inch (15.9 mm) is permitted. 2. Other car configurations that provide a turning space complying with Section 1138A.1.3 with the door closed shall be permitted.
11A-18 2022 CALIFORNIA BUILDING CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
2. The audible signal shall sound once for the “up” direc- tion and twice for the “down” direction or of a configu- ration which distinguishes between up and down elevator travel. Audible signals shall have a frequency of 1500 Hz maximum. Verbal annunciators shall have a frequency of 300 Hz minimum and 3000 Hz maximum. The audible signal and verbal annunciator shall be 10 dB minimum above ambient, but shall not exceed 80 dB, measured at the hall call button.
3. The center line of the fixture shall be located a minimum of 6 feet (1829 mm) in height above the finish floor.
4. The use of in-car lanterns, located in or on the car
doorjambs, visible from the proximity of the hall call buttons and conforming to the above requirements of this section, shall be acceptable. Note: The use of arrow shapes are preferred for visible signals.
1124A.7 Door delay.¶
1124A.7.1 Hall call. The minimum acceptable time from notification that a car is answering a call (lantern and audible signal) until the doors of the car start to close shall be calculated by the following equations, but shall be no less than 5 seconds:
T = D / (1.5 ft/s) or T = D / (445 mm/s)
Where T is the total time in seconds and D is the dis- tance from a point in the lobby or landing area 60 inches (1524 mm) directly in front of the farthest call button con- trolling that car to the centerline of its hoistway door (see Figure 11A-7D). For cars with in-car lanterns, T begins when the lantern is visible from the vicinity of hall call buttons and an audible signal is sounded.
1124A.7.2 Door delay for car calls. The minimum accept- able time for the door to remain fully open after receiving a call shall not be less than 5 seconds.
1124A.8 Doorjamb marking.¶
The floor level at all elevator hoistway entrances shall be designated by raised characters provided on both jambs. Characters shall be 2 inches (50.8 mm) in height located 48 inches (1219 mm) minimum above the finish floor, measured from the baseline of the lowest Braille cells, and 60 inches (1524 mm) maximum above the finish floor, measured from the baseline of the highest line of raised characters.
On the main entry level, a raised five-pointed star shall be placed to the left of the raised character. The outside diameter of the star shall be 2 inches (50.8 mm) and all points shall be of equal length. The raised characters and the star shall be white on a black background. Contracted Grade 2 Braille, conforming to Section 1143A.7, shall be placed below the corresponding raised characters and the star. The Braille translation for the star shall state “MAIN”. The raised characters shall comply with Section 1143A.6. (See Figure 11A-7C.)
1124A.9 Door protective and reopening devices.¶
Doors closed by automatic means shall be provided with a door- reopening device that will function to stop and reopen a car
HOUSING ACCESSIBILITY
door and adjacent hoistway door in case the car door is obstructed while closing.
This reopening device shall also be capable of sensing an object or person in the path of a closing door without requir- ing contact for activation at a nominal 5 inches and 29 inches (127 mm and 737 mm) above the floor.
Door-reopening devices shall remain effective for a period of not less than 20 seconds. After such an interval, the doors may close in accordance with the requirements of ASME A17.1.
1124A.10 Operation and leveling.¶
The elevator shall be automatic and be provided with a self-leveling feature that will automatically bring the car to the floor landings within a tolerance of plus or minus 1 /2 inch (12.7 mm) under rated loading to zero loading conditions. This self-leveling shall, within its zone, be entirely automatic and independent of the operating device and shall correct the overtravel or under- travel. The car shall also be maintained approximately level with the landing, irrespective of load.
The clearance between the car platform sill and the edge of the hoistway landing shall be no greater than 1 1 /4 inches (31.75 mm).
1124A.11 Platform (wheelchair) lifts.¶
1124A.11.1 General. Platform (wheelchair) lifts may be provided between levels, in lieu of passenger elevators, when the vertical distance between landings, as well as the structural design and safeguards are as allowed by ASME
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Building Code (Title 24, Part 2)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix G — FLOOD-RESISTANT
- Appendix L — EARTHQUAKE RECORDING
- Appendix M — TSUNAMI-GENERATED
- Appendix N — REPLICABLE
- Appendix O — PERFORMANCE-BASED
- Chapter 1 — SCOPE AND ADMINISTRATION
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
▸Chapter 11A — HOUSING ACCESSIBILITY
Overview- Section 1101A
- Section 1102A
- Section 1103A
- Section 1104A
- Section 1105A
- Section 1106A
- Section 1107A
- Section 1108A
- Section 1109A
- Section 1110A
- Section 1111A
- Section 1112A
- Section 1113A
- Section 1114A
- Section 1115A
- Section 1116A
- Section 1117A
- Section 1118A
- Section 1119A
- Section 1120A
- Section 1121A
- Section 1122A
- Section 1123A
- Section 1124A
- Section 1125A
- Section 1126A
- Section 1127A
- Section 1128A
- Section 1129A
- Section 1130A
- Section 1131A
- Section 1132A
- Section 1133A
- Section 1134A
- Section 1135A
- Section 1136A
- Section 1137A
- Section 1138A
- Section 1139A
- Section 1140A
- Section 1141A
- Section 1142A
- Section 1143A
- Section 1144A
- Section 1145A
- Section 1146A
- Section 1147A
- Section 1148A
- Section 1149A
- Section 1150A
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 22 — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U – AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix F — RODENTPROOFING
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
- Appendix P — EMERGENCY HOUSING