CPC · California Plumbing Code

Accessible plumbing facilities and protection of exposed pipes/surfaces

If your building requires accessible restrooms, the California Plumbing Code (CPC) requires that fixtures meet accessibility standards and that any exposed water supply or drain piping under accessible lavatories be insulated or enclosed to prevent contact. The CPC mandates using protectors or insulating covers that comply with ASME A112.18.9 or ASTM C1822 (see **§ 403.1 – § 403.3**).

Last reviewed: July 6, 2026

What the code requires — 2-4 sentences

The California Plumbing Code requires that where accessible plumbing facilities are required by the building regulations, those facilities be installed to meet the accessibility rules of the building code and applicable accessibility standards — see § 403.0 / § 403.1. Fixtures and fixture fittings serving persons with disabilities must comply with ICC A117.1 and the referenced standards (§ 403.2). In addition, water supply and drainpipes located under accessible lavatories and sinks must be insulated or otherwise configured to protect against contact, and any protectors/insulators used must comply with ASME A112.18.9 or ASTM C1822 (§ 403.3).

The single most important rule: protect pipes under accessible sinks so people cannot touch hot or sharp piping — use listed insulating covers or enclosures that meet the standards the CPC names.

Requirements in detail

Scope / where this applies

  • If an accessible restroom or lavatory is required by the building regulations, the plumbing fixtures serving that facility must be installed as required by those regulations and accessibility standards. See § 403.1 (installation to conform to building accessibility rules).

Fixtures and fixture fittings for persons with disabilities

  • Plumbing fixtures and fixture fittings provided for persons with disabilities must meet ICC A117.1 and applicable referenced standards listed in Chapter 4 of the CPC. See § 403.2.

Protection of exposed pipes and surfaces

  • Water supply and drainpipes under accessible lavatories and sinks must be insulated or otherwise configured to protect against contact (for example: insulation covers, sleeves, or an enclosure). See § 403.3.
  • Any protectors or insulators used for this purpose must comply with ASME A112.18.9 or ASTM C1822; ASTM C1822 is specifically listed among the CPC referenced standards for § 403.3.

Decision‑relevant dimensions/values (quick reference)

Decision item Requirement / value Code Reference
Where requirement arises When accessible facilities are required by building regulations § 403.1
Standard for fixtures/fittings Must meet ICC A117.1 and referenced Chapter 4 standards § 403.2
Exposed piping under accessible lavs Insulate or otherwise configure to protect against contact § 403.3
Acceptable protectors/insulators Must comply with ASME A112.18.9 or ASTM C1822 § 403.3; ASTM C1822 listed in referenced standards table
Related protection requirements General piping protection / installation (sleeves, sealing, expansion) § 312.1 / § 312.2

(If you need the full text of ASME A112.18.9 or ASTM C1822 to choose a product, obtain those standards — the CPC cites them but does not reproduce their detailed specifications.)

Exceptions & special cases

  • The CPC text for these sections notes cross-references to other state agency amendments or occupancy-specific requirements (the HCD/OSHPD bracketed notes). For specific accommodation details the code points you to Chapter 11A of the California Building Code for persons with disabilities; the CPC itself does not expand those technical dimensions beyond requiring conformance to ICC A117.1 (§ 403.1 — § 403.2).
  • The CPC requires the protectors/insulators to be compliant with the listed standards but does not itself specify material thickness, R‑value, or exact clearance distances — those are found in the referenced standards (ASME / ASTM). The CPC references ASTM C1822 for insulating covers specifically; see the referenced standards list.

Common mistakes

  • Installing an exposed P‑trap and supply lines under an accessible lav without any insulation or guard — failing to meet § 403.3.
  • Specifying or installing covers that are not listed to ASME A112.18.9 or ASTM C1822 even though they look protective; the CPC requires compliance with those test/selection standards (§ 403.3).
  • Assuming the building‑code accessibility requirements are satisfied by a “low” installation of fixtures alone — the CPC explicitly links plumbing to the building code accessibility requirements; you must meet ICC A117.1 or the building code chapters called out (§ 403.1–403.2).
  • Forgetting broader piping protection rules: sleeves, sealing, and protection from corrosion/mechanical damage are covered elsewhere (e.g., § 312.1 / § 312.2) and may affect how you route or protect exposed piping in accessible areas.

Worked example — lavatory under‑sink protection (concrete scenario)

Scenario: A public restroom requires an accessible lavatory. Under the sink you have a 1/2" hot water supply, 1/2" cold supply, and a 1 1/4" P‑trap (drain) exposed below a wall‑hung lavatory.

Step 1 — Confirm accessibility triggers: Because the restroom must be accessible by the building code, fixture locations and fittings must conform to ICC A117.1 and the building code accessibility chapter (per § 403.1–403.2) — that determines lav height, clearances and reach ranges.

Step 2 — Protect exposed piping: The CPC requires the water supply and drainpipes under the accessible lav to be insulated or otherwise configured to protect against contact (§ 403.3). You have two compliant pathways:

  • Option A — Install insulating/protective covers listed to ASTM C1822 (insulating covers for accessible lavatory piping); or
  • Option B — Install protectors listed to ASME A112.18.9 (when applicable) or construct a rigid enclosure that prevents access to the piping while maintaining required knee/toe clearance and servicing access.

Step 3 — Product selection and verification: Select an insulating cover product with manufacturer documentation stating compliance with ASTM C1822 (or ASME A112.18.9). Record the product listing in the job file for inspection. The CPC mandates compliance to those standards but does not provide the test details — obtain the standard or manufacturer documentation to confirm.

Step 4 — Install and maintain clearances: Install the covers or enclosure so they prevent contact but do not violate required ICC A117.1 clearances beneath the lav (knee and toe clearances). If an enclosure is used, ensure it is removable or has an access method that preserves plumbing serviceability. (General piping protection and routing should also conform to § 312.1/§ 312.2.)

Note: the CPC does not give a numeric “maximum touch temperature” or a specific insulation thickness — compliance is achieved by using listed products or enclosures that meet the standards the code references (§ 403.3).

Related provisions

  • § 403.1 — Install accessible plumbing facilities in accordance with building accessibility regulations / Chapter 11A of CBC.
  • § 403.2 — Fixtures and fittings for persons with disabilities must comply with ICC A117.1.
  • § 403.3 — Exposed pipes under accessible lavs must be insulated or otherwise protected; protectors must comply with ASME A112.18.9 or ASTM C1822.
  • Table of Referenced Standards (Table 1701.1) — lists ASTM C1822 as the referenced standard for § 403.3.
  • § 402.10 — fixtures with concealed slip joints require access panels — relevant when covering piping for serviceability.
  • § 312.1 / § 312.2 — general protection, corrosion control, sleeves, and expansion provisions for piping.

Code references

Grounded in the retrieved California Plumbing Code — click a citation to read the verbatim passage:

  • CPC § 312.2. High relevance — show source text

    (1) Be designed by a licensed plumbing contractor or a registered design professional in accordance with this code and the building code.

    (2) Be designed to accommodate expansion, contraction, and differential movement between parts of a tall wood (mass timber) building in accordance with Section 312.2. 301.7 One- and Two-Family Dwellings. [HCD 1] The provisions contained in this code shall not apply to one- and two-family dwelling private sewage disposal systems and minimum plumbing facilities when alternate facilities or installations have been approved by the local health author- ity, provided that such alternative facilities or installations provide substantially equivalent or greater protection to health and safety. 301.8 OSHPD 1R. [OSHPD 1R] For OSHPD 1R, refer to Section 309 of the California Existing Building Code for gen- eral requirements.

    302.0 Iron Pipe Size (IPS) Pipe. 302.1 General. Iron, steel, copper, and copper alloy pipe shall be standard-weight iron pipe size (IPS) pipe.

    303.0 Disposal of Liquid Waste. 303.1 General. It shall be unlawful for a person to cause, suffer, or permit the disposal of sewage, human excrement, or other liquid wastes, in a place or manner, except through and by means of an approved drainage system, installed and maintained in accordance with the provisions of this code. Exception: [HCD 1] Limited-density owner-built rural dwellings. A water closet shall not be required when an alter- nate system is provided and has been approved by the local health official. Where an alternative to the water closet is installed, a system for the disposal or treatment of graywater shall be provided to the dwelling. Graywater systems shall be designed according to water availability, use and discharge. The design, use and maintenance standards of such systems shall be the prerogative of the local health official.

    304.0 Connections to Plumbing System Required. 304.1 General. Plumbing fixtures, drains, appurtenances, and appliances, used to receive or discharge liquid wastes or sewage, shall be connected properly to the drainage system of the building or premises, in accordance with the requirements of this code.

    Exception: [HCD 1] Limited-density owner-built rural dwellings. Where conventional plumbing, in all or in part, is

    50 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    GENERAL REGULATIONS

    installed within the structure, it shall be installed in accordance with the provisions of this code. Alternative materials and methods shall be permitted provided that the design complies with the intent of the code, and that such alternatives shall per- form to protect health and safety for the intended purpose.

    305.0 Damage to Drainage System or Public Sewer.

  • California Plumbing Code Medium relevance — show source text

    IN THOUSANDS OF BTU PER HOUR**|APPLIANCE INPUT RATING LIMITS IN THOUSANDS OF BTU PER HOUR| |VENT
    HEIGHT
    H
    (feet)
    |CONNECTOR
    RISE
    R
    (feet)
    |FAN|FAN|NAT|FAN|FAN|NAT|FAN|FAN|NAT| |VENT
    HEIGHT
    H
    (feet)
    |CONNECTOR
    RISE
    R
    (feet)
    |Min|Max|Max|Min|Max|Max|Min|Max|Max| |6|1
    2
    3|262
    271
    279|293
    331
    361|183
    219
    247|325
    334
    344|373
    422
    462|234
    281
    316|447
    458
    468|463
    524
    574|286
    344
    385| |8|1
    2
    3|285
    293
    302|316
    353
    381|191
    228
    256|352
    360
    370|403
    450
    489|244
    292
    328|481
    492
    501|502
    560
    609|299
    355
    400| |10|1
    2
    3|302
    311
    320|335
    369
    398|196
    235
    265|372
    381
    391|429
    473
    511|252
    302
    339|506
    517
    528|534
    589
    637|308
    368
    413| |15|1
    2
    3|312
    321
    331|380
    411
    438|208
    248
    281|397
    407
    418|482
    522
    557|266
    317
    360|556
    568
    579|596
    646
    690|324
    387
    437| |20|1
    2
    3|306
    317
    326|425
    453
    476|217
    259
    294|390
    400
    412|538
    574
    607|276
    331
    375|546
    558
    570|664
    709
    750|336
    403
    457| |30|1
    2
    3|296
    307
    316|497
    521
    542|230
    274
    309|378
    389
    400|630
    662
    690|294
    349
    394|528
    541
    555|779
    819
    855|358
    425
    482| |50|1
    2

  • California Plumbing Code Medium relevance — show source text

    ; 2′ C.R.S. with 1″ cover on
    both top and bottom flanges; 13′1″ span
    restrained.|60 psf|2 hrs|||7|1, 3|2| |F/C-6-RC-34|61/4″|61/4″ thick; 43/4″ (5120 psi) concrete core;
    1″ T&G board flooring;1/2″ plaster under-
    coat; 4″ × 3″ × 10 lbs R.S.J.; 3′ C.R.S. flush
    with top surface concrete; 12′ span simply
    supported; 2″ × 1′3″ clinker concrete
    insert.|100 psf|4 hrs|||7|1, 7|4| |F/C-6-RC-35|61/4″|43/4″ (3600 psi) concrete core; 1″ T&G
    board flooring;1/2″ plaster undercoat; 4″ ×
    3″ × 10 lbs R.S.J.; 3′ C.R.S. flush with top
    surface concrete; 12′ span simply
    supported; 2″ × 1′3″ clinker concrete
    insert.|100 psf|2 hrs
    30 min|||7|1, 5|21/2| |F/C-6-RC-36|61/4″|43/4″ (2800 psi) concrete core; 1″ T&G
    board flooring;1/2″ plaster undercoat; 4″ ×
    3″ × 10 lbs R.S.J.; 3′ C.R.S. flush with top
    surface concrete; 12″ span simply
    supported; 2″ × 1′3″ clinker concrete
    insert.|80 psf|4 hrs|||7|1, 7|4| |F/C-7-RC-37|7″|(3640 psi) concrete deck;1/4″ reinforce-
    ment bars at 6″ pitch with 11/2″ cover;1/4″
    reinforcement bars at 5″ pitch perpendic-
    ular with 11/2″ cover; 13′1″ span
    restrained.|169 psf|6 hrs|||7|1, 14|6| |F/C-7-RC-38|7″|(4060 psi) concrete deck; 4″ × 3″ × 10 lbs
    R.S.J.; 2′6″ C.R.S. with 11/2″ cover on both
    top and bottom flanges; 4″ × 6″ × 13 SWG
    mesh reinforcement 11/2″ from bottom of
    slab; 13′1″ span restrained.|175 psf|6 hrs|||7|1, 14|6| |F/C-7-RC-39|71/4″|53/4″ (4010 psi) concrete core; 1″ T&G
    board flooring;1/2″ plaster undercoat;
    4″ × 3″ × 10 lbs R.S.J.; 2′6″ C.R.S.

  • CPC § 310.13 Medium relevance — show source text

    ante rooms.

    310.13 [SFM] For applications listed in Section 1.11.0 regu- lated by the Office of the State Fire Marshal, plastic piping shall not be exposed as a portion of the interior room finish in a build- ing or structure if the piping has a flame-spread rating exceed- ing 75 when tested in accordance with ASTM E84, “Test for Surface Burning Characteristics of Building Materials.” 310.14 Services/Systems and Utilities. [OSHPD 1, 2, 4 & 5] Refer to Sections 1224.4.1, 1225.2.1 and 1228.4.1.1, Cal- ifornia Building Code. 310.15 Telephone and Data Equipment Rooms.

    [OSHPD 1, 4 & 5] Where telecommunications service entrance rooms, technology equipment centers, or technology distribution rooms are provided in accordance with Section 1224.5 of the California Building Code, plumbing equipment and fixtures that are not directly related to the support of the room shall not be installed in or pass through the room.

    311.0 Independent Systems. 311.1 General. The drainage system of each new building and new work installed in an existing building shall be separate and independent from that of any other building, and, where available, every building shall have an independent connection with a public or private sewer.

    Exception: Where one building stands in the rear of another building on an interior lot, and no public or private sewer is available or can be constructed to the rear building through an adjoining court, yard, or driveway, the building drain from the front building shall be permitted to be extended to the rear building.

    Note: Accessory dwelling units are not required to have inde- pendent service utility (drainage) connections provided they meet the specific requirements in Government Code Section 65852.2.

    312.0 Protection of Piping, Tubing, Materials, and Structures.

    312.1 General. Piping passing under or through walls shall be protected from breakage. Piping passing through or under cinders or other corrosive materials shall be protected from external corrosion in an approved manner. Approved provisions shall be made for expansion of hot water piping. Voids around piping passing through concrete floors on the ground shall be sealed.

    312.2 Installation. Piping in connection with a plumbing system shall be so installed that piping or connections will not be subject to undue strains or stresses, and provisions shall be made for expansion, contraction, and structural settlement. No plumbing piping shall be directly embedded in concrete or masonry. No structural member shall be seriously weakened or impaired by cutting, notching, or otherwise, as defined in the California Building Code or California Residential Code . 312.3 Building Sewer and Drainage Piping. No building sewer or other drainage piping or part thereof, constructed of materials other than those approved for use under or within a building, shall be installed under or within 2 feet (610 mm) of a building or structure, or less than 1 foot (305 mm) below the surface of the ground. 312.4 Corrosion, Erosion, and Mechanical Damage. Piping subject to corrosion, erosion, or mechanical damage shall be protected in an approved manner. **312.5 Protectively Coated Pipe.

  • CPC § 31-2022 Medium relevance — show source text

    2025 CALIFORNIA PLUMBING CODE 453

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    454 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    "The information contained in this appendix is not part of this American National Standard (ANS) and has not been processed in accordance with ANSI's requirements for an ANS. As such, this appendix may contain material that has not been subjected to public review or a consensus process. In addition, it does not contain requirements necessary for conformance to the standard."

    The following IAPMO Installation Standard is included here for the convenience of the users of the Uniform Plumbing Code. It is not considered as a part of the Uniform Plumbing Code unless formally adopted as such. This Installation Standard is an independent, stand-alone document published by the International Association of Plumbing and Mechanical Officials and is printed herein by the expressed written permission of IAPMO.

    INSTALLATION STANDARD FOR PEX TUBING SYSTEMS

    FOR HOT- AND COLD-WATER DISTRIBUTION

    IAPMO IS 31-2022

    The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.

    1 Scope

    1.1 General

    1.1.1 This Standard specifies requirements for the installation of SDR 9 CTS crosslinked polyethylene (PEX) tubing and fittings, including cold-expansion, crimp, press, and mechanical compression fittings, intended for hot- and cold-water distribution systems within buildings.

    1.1.2 This Standards applies to

    (a) SDR 9 CTS PEX tubing complying with ASTM F876 and pressure-rated in accordance with PPI TR-3; and (b) PEX fitting systems complying with (i) ASTM F877, for mechanical compression fittings and metal or plastic insert fittings with stainless steel press sleeves; (ii) ASTM F1807 or ASTM F2159, for metal or plastic insert fittings with copper crimp rings; (iii) ASTM F1960, for cold expansion fittings with PEX reinforced rings; or (iv) ASTM F2080, for cold expansion fittings with metal compression sleeves. 1.2 Terminology

    In this Standard,

    (a) “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy to comply with the Standard; (b) “should” is used to express a recommendation, but not a requirement; (c) “may” is used to express an option or something permissible within the scope of the Standard; and (d) “can” is used to express a possibility or a capability. Notes accompanying sections of the Standard do not specify requirements or alternative requirements; their purpose is to separate explanatory or informa

    tive material from the text. Notes to tables and figures are considered part of the table or figure and can be written as requirements.

    1.3 Units of Measurement

    SI units are the primary units of record in global commerce. In this Standard, the inch/pound units are shown in parentheses. The values stated in each measurement system are equivalent in application, but each unit system is to be used independently. All references to gallons are to U.S. gallons.

    2 Reference Publications

  • CPC § 705.10 Medium relevance — show source text

    Waste,
    and Vent (DWV), Sewer, Sanitary, and Storm Plumbing Sys-
    tems for Above and Below Ground Use|Joints|705.10|

    340 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    REFERENCED STANDARDS

    TABLE 1701.1 (continued) REFERENCED STANDARDS

    STANDARD NUMBER STANDARD TITLE APPLICATION REFERENCED
    SECTION
    ASTM C1540-2020 Standard Specification for Heavy-Duty Shielded Couplings
    Joining Hubless Cast Iron Soil Pipe and Fittings
    Joints 705.2.2
    ASTM C1563-2008
    (R2021)
    Standard Test Method for Gaskets for Use in Connection with
    Hub and Spigot Cast Iron Soil Pipe and Fittings for Sanitary
    Drain, Waste, Vent, and Storm Piping Applications
    Joints 705.2.2
    ASTM C1822-2021 Standard Specification for Insulating Covers on Accessible
    Lavatory Piping
    Miscellaneous 403.3
    ASTM D1253-2014 Standard Test Method for Residual Chlorine in Water Miscellaneous 1506.10.6, 1603.4.1
    ASTM D1785-2021a Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
    Pipe, Schedules 40, 80, and 120
    Piping Table 604.1, Table
    701.2
    ASTM D2235-2021 Standard Specification for Solvent Cement for Acrylonitrile-
    Butadiene-Styrene (ABS) Plastic Pipe and Fittings
    Joints 705.1.2
    ASTM D2239-2021 Standard Specification for Polyethylene (PE) Plastic Pipe
    (SIDR-PR) Based on Controlled Inside Diameter
    Piping Table 604.1
    ASTM D2241-2020 Standard Specification for Poly (Vinyl Chloride) (PVC) Pressure-
    Rated Pipe (SDR Series)
    Piping Table 604.1
    ASTM D2464-2015 Standard Specification for Threaded Poly (Vinyl Chloride)
    (PVC) Plastic Pipe Fittings, Schedule 80
    Fittings Table 604.1
    ASTM D2466-2021 Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
    Pipe Fittings, Schedule 40
    Fittings Table 604.1
    ASTM D2467-2020 Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
    Pipe Fittings, Schedule 80
    Fittings Table 604.1
    ASTM D2513-2020 Standard Specification for Polyethylene (PE) Gas Pressure
    Pipe, Tubing, and Fittings
    Piping 1208.5.4, 1208.5.6.2,
    1208.5.10.2,
    1210.1.7.1(1)
    ASTM D2564-2020 Standard Specification for Solvent Cements for Poly (Vinyl
    Chloride) (PVC) Plastic Piping Systems
    Joints 605.12.2, 705.6.
  • CPC § 312.0 Medium relevance — show source text

    312.0 Protection of Piping, Materials, and Structures

    314.0 Trenching, Excavation, and Backfill

    701.3 Drainage Fittings

    705.5.1.1 Butt Fusion Joints

    705.5.1.2 Electro-Fusion Joints

    705.5.1.3 Socket-Fusion Joints

    723.0 Building Sewer Test

    TABLE 1

    CLEANOUTS (See Section 4.6.1)

    The following standards from Tables 1701.1 and 1701.2 of the 2024 Uniform Plumbing Code apply.

    Table 1701.1 Standards

    ASTM D2239 Polyethylene (PE) Plastic Pipe (SIDRPR) Based on Controlled Inside Diameter

    ASTM D2683 Socket-Type Polyethylene Fittings for Outside Diameter-Controlled Polyethylene Pipe and Tubing

    ASTM D3261 Butt Heat Fusion Polyethylene (PE) Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing

    ASTM F714 Polyethylene (PE) Plastic Pipe (DRPR) Based on Outside Diameter

    ASTM F894 Polyethylene (PE) Large Diameter Profile Wall Sewer and Drain Pipe

    ASTM F1055 Electrofusion Type Polyethylene Fittings for Outside Diameter Controlled Polyethylene and Crosslinked Polyethylene (PEX) Pipe and Tubing

    ASTM F2620 Heat Fusion Joining of Polyethylene Pipe and Fittings

    Table 1701.2 Standards

    ASTM D2657 Heat Fusion Joining of Polyolefin Pipe and Fittings

    IAPMO PS 25 Metallic Fittings for Joining Polyethylene Pipe for Water Service and Yard Piping

    Note: For SI units: 1 inch = 25 mm

    2025 CALIFORNIA PLUMBING CODE 453

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    454 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    "The information contained in this appendix is not part of this American National Standard (ANS) and has not been processed in accordance with ANSI's requirements for an ANS. As such, this appendix may contain material that has not been subjected to public review or a consensus process. In addition, it does not contain requirements necessary for conformance to the standard."

    The following IAPMO Installation Standard is included here for the convenience of the users of the Uniform Plumbing Code. It is not considered as a part of the Uniform Plumbing Code unless formally adopted as such. This Installation Standard is an independent, stand-alone document published by the International Association of Plumbing and Mechanical Officials and is printed herein by the expressed written permission of IAPMO.

    INSTALLATION STANDARD FOR PEX TUBING SYSTEMS

    FOR HOT- AND COLD-WATER DISTRIBUTION

    IAPMO IS 31-2022

    The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.

    1 Scope

    1.1 General

    1.1.1 This Standard specifies requirements for the installation of SDR 9 CTS crosslinked polyethylene (PEX) tubing and fittings, including cold-expansion, crimp, press, and mechanical compression fittings, intended for hot- and cold-water distribution systems within buildings.

    1.1.2 This Standards applies to

  • CPC § 505.0 Medium relevance — show source text

    Oil-burning and other . . . . . . . . . . . . . . . . . . . . . .505.0 Permits required . . . . . . . . . . . . . . . . . . . . . . . . . .502.0

    Pressure-relief valves . . . . . . . . . . .504.4, 504.6, 505.2,

    608.2 – 608.5

    Protection . . . . . . . . . . . . . . . . . . .504.3 – 504.6, 505.2,

    507.2, 507.8, 507.10,

    507.14.1, 507.24

    Relief valve discharge . . . . . . . . . . . . . . . . . . . . . .608.5 Seismic provisions . . . . . . . . . . . . . . . . . . . . . . . . .507.2 Temperature and pressure-relief valves . . . . . . . . . . . . . . .504.6, 505.2 Temperature-limiting devices . . . . . . . . . . . . . . . . .504.5

    Vents . . . . . . . . . . . . . . . . . . . . . . . . . . . . .509.0, 510.0

    Water heating system requirements . . . . . . . . . . . .501.2 WATER SOFTENERS . . . . . . . . . . . . . . . . 611.4, Table 611.4

    WATER STATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .225.0

    WATER TESTS

    Building sewers . . . . . . . . . . . . . . . . . . . . . . . . . . .723.0 Drainage and vent systems . . . . . . . . . . . . .105.3, 712.2 Storm drainage . . . . . . . . . . . . . . . . . .1107.2.1, 1107.2.3 Water supply systems . . . . . . . .105.2.1.1, 105.3, 609.4

    WATERPROOFING

    AND WATERTIGHT

    Building sewer . . . . . . . . . . . . . . . . . . . . . . . . . . . .723.1

    Cleanouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .707.3

    Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105.3

    Drain pans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .507.5

    Fixtures . . . . . . . . . . . . . . . . .402.2, 408.6, 408.8, 418.2

  • CPC § 309.0 Medium relevance — show source text

    2025 CALIFORNIA PLUMBING CODE 469

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    IS 33

    Uniform Plumbing Code References for Ductile Iron and PVC Pressure Building Supply and Exterior Cold-Water Piping

    The following sections of the 2024 Uniform Plumbing Code apply to ductile iron and PVC pressure building supply and exterior cold-water piping.

    Chapter 3 General Regulations

    309.0 Workmanship

    312.0 Protection of Piping, Materials, and Struc tures

    313.0 Hangers, Supports, and Anchors

    314.0 Trenching, Excavation, and Backfill

    Chapter 6 Water Supply and Distribution

    604.0 Materials (water piping)

    Table 604.1 Materials for Building Supply and Water Distribution Piping and Fittings

    605.4 Ductile Iron Pipe and Joints

    605.12 PVC Plastic Pipe and Joints

    605.16.2 Plastic Pipe to Other Materials

    609.0 Installation, Testing, Unions, and Location

    Abbreviations

    IAPMO International Association of Plumbing and Mechanical Officials

    UPC Uniform Plumbing Code published by IAPMO

    AWWA American Water Works Association

    CSA Canadian Standards Association

    Applicable Standards.

    ASME B16.4 Gray Iron Threaded Fittings Classes 125 and 250

    ASTM D1785 Poly (Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40, 80, and 120

    ASTM D2241 Poly (Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)

    ASTM D2466 Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40

    ASTM D2467 Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80

    ASTM F1970 Special Engineered Fittings, Appurtenances or Valves for use in Poly (Vinyl Chloride) (PVC) or Chlorinated Poly (Vinyl Chloride) (CPVC) Systems

    AWWA C110 Ductile Iron and Gray-Iron Fittings

    AWWA C111 Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings

    AWWA C151 Ductile-Iron Pipe, Centrifugally Cast

    AWWA C153 Ductile-Iron Compact Fitting

    AWWA C900 Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 4 in. through 12 in. (100 mm through 300 mm)

    AWWA C904 Crosslinked Polyethylene (PEX) Pressure Tubing, ½ in. through 3 In. (13 mm through 76 mm), for Water Service

    AWWA C907 Injection-Molded Polyvinyl Chloride (PVC) Pressure Fittings, 4 In, through 12 in (100 mm through 300 mm) for Water, Wastewater and Reclaimed Water Service

    IAPMO/

    ANSI UPC-1 Uniform Plumbing Code

    470 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

  • CPC § 714.2 Medium relevance — show source text

    714.2 Prohibited Water Discharge. No rain, surface, or subsurface water shall be connected to or discharged into a drainage system unless first approved by the Authority Having Jurisdiction.

    714.3 Prohibited Sewer Connection. No cesspool, septic tank, seepage pit, or drain field shall be connected to a public sewer or to a building sewer leading to such public

    sewer.

    714.4 Commercial Food Waste Disposer. The Authority Having Jurisdiction shall review before approval, the installation of a commercial food waste disposer connecting to a private sewage disposal system.

    714.5 Tanks. An approved type, watertight sewage or wastewater holding tank, the contents of which, due to their character, shall be periodically removed and disposed of at some approved off-site location, shall be installed where required by the Authority Having Jurisdiction or the Health Officer to prevent anticipated surface or subsurface contamination or pollution, damage to the public sewer, or other hazardous or nuisance conditions.

    715.0 Building Sewer Materials.

    715.1 Materials. The building sewer, beginning 2 feet (610 mm) from a building or structure, shall be of such materials as prescribed in this code.

    715.2 Joining Methods and Materials. Joining methods and materials shall be as prescribed in this code.

    715.3 Existing Sewers. Where permitted by the Authority Having Jurisdiction, trenchless methods of rehabilitation of existing building sewer and building storm sewers shall be installed in accordance with Section 715.3.1 or Section 715.3.2.

    715.3.1 Sewer Pipe Lining. For trenchless installation of resin-impregnated flexible tubing to line existing building sewers and building storm sewers installation shall be in accordance with ASTM F1216, ASTM F2561, ASTM F2599, or ASTM F3240.

    715.3.2 Sewer Pipe Replacement. For trenchless installation of polyethylene (PE) pipe using the pipe bursting method to replace existing building sewers and building storm sewers materials shall be in accordance with ASTM F714.

    716.0 Markings.

    716.1 General. Pipe, brick, block, prefabricated septic tanks, prefabricated septic tank or seepage pit covers, or other parts or appurtenances incidental to the installation of building sewers or private sewage disposal systems shall be in accordance with the approval requirements of Chapter 3 of this code.

    717.0 Size of Building Sewers. 717.1 General. The minimum size of a building sewer shall be determined on the basis of the total number of fixture units drained by such sewer, in accordance with Table 717.1. No building sewer shall be smaller than the building drain.

    For alternate methods of sizing building sewers, see Appendix C.

    TABLE 717.1

    MAXIMUM/MINIMUM FIXTURE UNIT LOADING

  • CPC § 2025 Medium relevance — show source text

    Gas Piping| |13|Health Care Facilities and Medical Gas and Medical Vacuum Systems| |14|Firestop Protection| |15|Alternate Water Sources for Nonpotable Applications| |16|Nonpotable Rainwater Catchment Systems| |17|Referenced Standards| |Appendix A|Recommended Rules for Sizing the Water Supply System| |Appendix B|Explanatory Notes on Combination Waste and Vent Systems| |Appendix C|Alternate Plumbing Systems| |Appendix D|Sizing Storm Water Drainage Systems| |Appendix E|Manufactured/Mobile Home Parks and Recreational Vehicle Parks| |Appendix F|Firefighter Breathing Air Replenishment Systems| |Appendix G|Sizing of Venting Systems| |Appendix H|Private Sewage Disposal Systems| |Appendix I|Installation Standards| |Appendix J|Combination of Indoor and Outdoor Combustion and Ventilation Opening Design| |Appendix K|Potable Rainwater Catchment Systems| |Appendix L|Sustainable Practices| |Appendix M|Peak Water Demand Calculator| |Appendix N|Impact of Water Temperature on the Potential for Scalding and Legionella Growth| |Appendix O|Non-Sewered Sanitation Systems| |Appendix P|Professional Qualifications| |Appendix Q|Indoor Horticultural Facilities| |Appendix R|Tiny Houses| |Appendix S|Onsite Stormwater Treatment Systems|

    2025 CALIFORNIA PLUMBING CODE xiii

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    FORMAT OF THE UNIFORM PLUMBING CODE

    The following is a summary of the scope and intent of the provisions addressed within the chapters and appendices of the Uniform Plumbing Code :

    Chapter 1 Administration.

    Chapter 1 regulates the application, enforcement, and administration of subsequent requirements of the code. As well as establishing the scope of the code, this chapter is concerned with enforcing the requirements contained in the body of the code. A plumbing code, as with any other code, is intended to be adopted as a legally enforceable document to safeguard health, safety, property, and public welfare. The code cannot be effective without satisfactory provisions for its administration and enforcement. The Authority Having Jurisdiction is to review the proposed and completed work and to decide whether a plumbing system conforms to the code requirements. As a public servant, the Authority Having Jurisdiction enforces the code in an unbiased, proper manner. The design professional is responsible for the design of a safe plumbing system. The contractor is responsible for installing the system in accordance with the plans.

    Chapter 2 Definitions.

    To maintain consistency and encourage the use of common terminology, Chapter 2 establishes definitions to provide clarity of terms and promote the use of a common language throughout the code. Understanding definitions within the context of their application enables greater collaboration, efficiency, standardization, and interpretation in applying and enforcing terms used throughout the code. Codes are technical documents, and every term can impact the meaning of the code text. Terms not defined have a normally accepted meaning.

    Chapter 3 General Regulations.

    Chapter 3 regulates the general requirements, not specific to other chapters, for installing plumbing systems. Many regulations are not specific plumbing requirements but relate to the overall plumbing system. This chapter contains safety requirements for installing plumbing and also contains nonplumbing requirements for identifying pipes, pipe fittings, traps, fixtures, materials, and devices used in plumbing systems.

  • CPC § 4.1 Medium relevance — show source text
    • 100°F
      (16°C-38°C)|1 h|6 h|2 h|12 h|6 h|24 h| |40°F-60°F
      (4°C-16°C)|2 h|12 h|4 h|24 h|12 h|48 h| |10°F- 40°F
      (-12°C+4°C)|8 h|48 h|16 h|96 h|48 h|8 days| |*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|

    2025 CALIFORNIA PLUMBING CODE 467

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    IS 33

    FIGURE 1

    LOCATION OF THRUST BLOCKS (STANDARD AND METRIC COMBINED) A COMPARISON OF THRUST-BLOCK AREAS (See Section 4.1)

    468 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    IS 33

    FIGURE 2

    THRUST BLOCK BEARING AREA (See Section 5.2.2)

    2025 CALIFORNIA PLUMBING CODE 469

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    IS 33

    Uniform Plumbing Code References for Ductile Iron and PVC Pressure Building Supply and Exterior Cold-Water Piping

    The following sections of the 2024 Uniform Plumbing Code apply to ductile iron and PVC pressure building supply and exterior cold-water piping.

    Chapter 3 General Regulations

    309.0 Workmanship

    312.0 Protection of Piping, Materials, and Struc tures

    313.0 Hangers, Supports, and Anchors

    314.0 Trenching, Excavation, and Backfill

    Chapter 6 Water Supply and Distribution

    604.0 Materials (water piping)

    Table 604.1 Materials for Building Supply and Water Distribution Piping and Fittings

    605.4 Ductile Iron Pipe and Joints

    605.12 PVC Plastic Pipe and Joints

    605.16.2 Plastic Pipe to Other Materials

    609.0 Installation, Testing, Unions, and Location

    Abbreviations

    IAPMO International Association of Plumbing and Mechanical Officials

    UPC Uniform Plumbing Code published by IAPMO

    AWWA American Water Works Association

    CSA Canadian Standards Association

    Applicable Standards.

    ASME B16.4 Gray Iron Threaded Fittings Classes 125 and 250

    ASTM D1785 Poly (Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40, 80, and 120

    ASTM D2241 Poly (Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)

  • CPC § 402.10 High relevance — show source text

    402.10 Slip Joint Connections. Fixtures having concealed slip joint connections shall be provided with an access panel or utility space not less than 12 inches (305 mm) in its least dimension and so arranged without obstructions as to make such connections accessible for inspection and repair. 402.11 Future Fixtures. Where provisions are made for the future installation of fixtures, those provided for shall be considered in determining the required sizes of the drain and water supply piping. Construction for future installations shall be terminated with a plugged fitting or fittings. Where the plugged

    fitting is at the point where the trap of a fixture is installed, the plumbing system for such fixture shall be complete and be in accordance with the plumbing requirements of this code.

    403.0 Accessible Plumbing Facilities. 403.1 General. Where accessible facilities are required in applicable building regulations, the facilities shall be installed in accordance with those regulations. [HCD 1-AC] For spe- cific requirements regarding accommodations for persons with disabilities, see Chapter 11A of the California Building Code. 403.2 Fixtures and Fixture Fittings for Persons with Disabilities. Plumbing fixtures and fixture fittings for persons with disabilities shall be in accordance with ICC A117.1 and the applicable standards referenced in Chapter 4. [HCD 1-AC] Specific requirements regarding accommodations for persons with disabilities are contained in Chapter 11A of the California Building Code. 403.3 Exposed Pipes and Surfaces. Water supply and drainpipes under accessible lavatories and sinks shall be insulated or otherwise be configured to protect against contact. Protectors, insulators, or both shall comply with ASME A112.18.9 or ASTM C1822. [HCD 1-AC] Specific requirements regard- ing accommodations for persons with disabilities are contained in Chapter 11A of the California Building Code.

    404.0 Waste Fittings and Overflows. 404.1 Waste Fittings. Waste fittings shall comply with ASME A112.18.2/CSA B125.2, ASTM F409 or Table 701.2 for aboveground drainage piping and fittings. 404.2 Overflows. Where a fixture is provided with an overflow, the overflow shall comply with Section 404.2.1 or Section 404.2.2.

    404.2.1 Sinks, Lavatories, and Bathtubs. The waste shall be so arranged that the standing water in the fixture shall not rise in the overflow where the stopper is closed or remain in the overflow where the fixture is empty. The overflow pipe from a fixture shall be connected to the house or inlet side of the fixture trap.

    404.2.2 Water Closets and Urinals. Overflows on flush tanks shall be permitted to discharge into the water closets or urinals served by them.

    405.0 Prohibited Fixtures.

    405.1 Prohibited Water Closets. Water closets having an invisible seal or an unventilated space or having walls which are not thoroughly washed at each discharge shall be prohibited. A water closet that might permit siphonage of the contents of the bowl back into the tank shall be prohibited. 405.2 Prohibited Urinals. Trough urinals and urinals with an invisible seal shall be prohibited.

  • CPC § 402.6.2 High relevance — show source text

    Closet rings (closet flanges) shall be adequately designed and secured to support fixtures connected thereto.

    402.6.2 Securing Closet Flanges. Closet screws, bolts, washers, and similar fasteners shall be of copper alloy, copper, or other listed equally corrosion-resistant materials. Screws and bolts shall be of a size and number to properly support the fixture installed. 402.6.3 Securing Floor-Mounted, Back-Outlet Water Closet Bowls. Floor-mounted, back-outlet water closet bowls shall be set level with an angle of 90 degrees (1.57 rad) between the floor and wall at the centerline of the fixture outlet. The floor and wall shall have a flat mounting surface not less than 5 inches (127 mm) to the right and left of the fixture outlet centerline. The closet flange shall be secured to the wall mounting surface. Offset, eccentric, or reducing closet flanges shall not be permitted with these fixtures.

    The fixture shall be secured to the wall outlet flange or drainage connection and the floor by corrosion-resistant screws or bolts.

    402.7 Supply Fittings. The supply lines and fittings for every plumbing fixture shall be so installed as to prevent backflow in accordance with Chapter 6.

    402.8 Installation. Fixtures shall be installed in accordance

    with the manufacturer’s installation instructions.

    402.9 Design and Installation of Plumbing Fixtures. Plumbing fixtures shall be installed in accordance with the manufacturer’s installation instructions. The means of backflow prevention shall not be compromised by the designated fixture fitting mounting surface. 402.10 Slip Joint Connections. Fixtures having concealed slip joint connections shall be provided with an access panel or utility space not less than 12 inches (305 mm) in its least dimension and so arranged without obstructions as to make such connections accessible for inspection and repair. 402.11 Future Fixtures. Where provisions are made for the future installation of fixtures, those provided for shall be considered in determining the required sizes of the drain and water supply piping. Construction for future installations shall be terminated with a plugged fitting or fittings. Where the plugged

    fitting is at the point where the trap of a fixture is installed, the plumbing system for such fixture shall be complete and be in accordance with the plumbing requirements of this code.

    403.0 Accessible Plumbing Facilities. 403.1 General. Where accessible facilities are required in applicable building regulations, the facilities shall be installed in accordance with those regulations. [HCD 1-AC] For spe- cific requirements regarding accommodations for persons with disabilities, see Chapter 11A of the California Building Code. 403.2 Fixtures and Fixture Fittings for Persons with Disabilities. Plumbing fixtures and fixture fittings for persons with disabilities shall be in accordance with ICC A117.1 and the applicable standards referenced in Chapter 4. [HCD 1-AC] Specific requirements regarding accommodations for persons with disabilities are contained in Chapter 11A of the California Building Code. 403.3 Exposed Pipes and Surfaces. Water supply and drainpipes under accessible lavatories and sinks shall be insulated or otherwise be configured to protect against contact. Protectors, insulators, or both shall comply with ASME A112.18.9 or ASTM C1822.

  • CPC § 401.2 High relevance — show source text

    401.2 Quality of Fixtures . . . . . . . . . . . . .59

    401.3 Water-Conserving Fixtures and Fittings . . . . . . . . . . . . . . . . . . .59

    402.0 Installation . . . . . . . . . . . . . . . . . . .59

    402.1 Cleaning . . . . . . . . . . . . . . . . . . . . .59

    402.2 Joints . . . . . . . . . . . . . . . . . . . . . . .59

    402.3 Securing Fixtures . . . . . . . . . . . . . .59

    402.4 Wall-Hung Fixtures . . . . . . . . . . . . .59

    402.5 Setting . . . . . . . . . . . . . . . . . . . . . .59

    402.6 Flanged Fixture Connections . . . . .59

    402.7 Supply Fittings . . . . . . . . . . . . . . . .60

    402.8 Installation . . . . . . . . . . . . . . . . . . .60

    402.9 Design and Installation of Plumbing Fixtures . . . . . . . . . . . . . .60

    402.10 Slip Joint Connections . . . . . . . . . .60

    402.11 Future Fixtures . . . . . . . . . . . . . . . .60

    403.0 Accessible Plumbing Facilities . . . .60

    403.1 General . . . . . . . . . . . . . . . . . . . . . .60

    403.2 Fixtures and Fixture Fittings for Persons with Disabilities . . . . . .60

    403.3 Exposed Pipes and Surfaces . . . . .60

    404.0 Waste Fittings and Overflows . . . . .60

    404.1 Waste Fittings . . . . . . . . . . . . . . . . .60

    404.2 Overflows . . . . . . . . . . . . . . . . . . . .60

    405.0 Prohibited Fixtures . . . . . . . . . . . . .60

    405.1 Prohibited Water Closets . . . . . . . .60

    405.2 Prohibited Urinals . . . . . . . . . . . . . .60

    405.3 Miscellaneous Fixtures . . . . . . . . . .60

    406.0 Special Fixtures and Specialties . . .61

    406.1 Water and Waste Connections . . . .61

    406.2 Special Use Sinks . . . . . . . . . . . . .61

    406.3 Special Use Fixtures . . . . . . . . . . .61

    2025 CALIFORNIA PLUMBING CODE xxix

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    TABLE OF CONTENTS

    406.4 Zinc Alloy Components . . . . . . . . .61

    407.0 Lavatories . . . . . . . . . . . . . . . . . . . .61

    407.1 Application . . . . . . . . . . . . . . . . . . .61

    407.2 Water Consumption . . . . . . . . . . . .61

    407.3 Limitation of Hot Water

  • CPC § 1.4 High relevance — show source text

    1.4, 705.3.3| |ASTM C4-2004 (R2018)|Standard Specification for Clay Drain Tile and Perforated Clay
    Drain Tile|Piping|Table 1101.4.6| |ASTM C425-2021|Standard Specification for Compression Joints for Vitrified
    Clay Pipe and Fittings|Joints|705.8.1| |ASTM C564-2020a|Standard Specification for Rubber Gaskets for Cast Iron Soil
    Pipe and Fittings|Joints|705.2.2| |ASTM C700-2018|Standard Specification for Vitrified Clay Pipe, Extra Strength,
    Standard Strength, and Perforated|Piping|Table 701.2,
    Table 1101.4.6| |ASTM C1053-2000 (R2015)|Standard Specification for Borosilicate Glass Pipe and Fittings
    for Drain, Waste, and Vent (DWV) Applications|Piping|811.2| |ASTM C1173-2018|Standard Specification for Flexible Transition Couplings for
    Underground Piping Systems|Fittings|705.10| |ASTM C1277-2020|Standard Specification for Shielded Couplings Joining Hubless
    Cast Iron Soil Pipe and Fittings|Fixtures|301.2.4, 705.2.2| |ASTM C1460-2021|Standard Specification for Shielded Transition Couplings for
    Use With Dissimilar DWV Pipe and Fittings Above Ground|Joints|705.10| |ASTM C1461-2021|Standard Specification for Mechanical Couplings Using Ther-
    moplastic Elastomeric (TPE) Gaskets for Joining Drain, Waste,
    and Vent (DWV), Sewer, Sanitary, and Storm Plumbing Sys-
    tems for Above and Below Ground Use|Joints|705.10|

    340 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    REFERENCED STANDARDS

    TABLE 1701.1 (continued) REFERENCED STANDARDS

    STANDARD NUMBER STANDARD TITLE APPLICATION REFERENCED
    SECTION
    ASTM C1540-2020 Standard Specification for Heavy-Duty Shielded Couplings
    Joining Hubless Cast Iron Soil Pipe and Fittings
    Joints 705.2.2
    ASTM C1563-2008
    (R2021)
    Standard Test Method for Gaskets for Use in Connection with
    Hub and Spigot Cast Iron Soil Pipe and Fittings for Sanitary
    Drain, Waste, Vent, and Storm Piping Applications
    Joints 705.2.2
    ASTM C1822-2021 Standard Specification for Insulating Covers on Accessible
    Lavatory Piping
    Miscellaneous 403.3
    ASTM D1253-2014 Standard Test Method for Residual Chlorine in Water Miscellaneous 1506.10.6, 1603.4.1
    ASTM D1785-2021a Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
    Pipe, Schedules 40, 80, and 120
    Piping Table 604.1, Table
    701.
  • CPC § 310.5 Medium relevance — show source text

    310.5 Obstruction of Flow. No fitting, fixture and piping connection, appliance, device, or method of installation that obstructs or retards the flow of water, wastes, sewage, or air in the drainage or venting systems, in an amount exceeding the normal frictional resistance to flow, shall be used unless it is indicated as acceptable in this code or is approved in accordance with Section 301.2 of this code. The enlargement of a 3 inch (80 mm) closet bend or stub to 4 inches (100 mm) shall not be considered an obstruction.

    310.6 Dissimilar Metals. Except for necessary valves, where intermembering or mixing of dissimilar metals occurs, the point of connection shall be confined to exposed or accessible locations.

    310.7 Direction of Flow. Valves, pipes, and fittings shall be installed in correct relationship to the direction of flow.

    310.8 Screwed Fittings. Screwed fittings shall be ABS, cast-iron, copper, copper alloy, malleable iron, PVC, steel, or other approved materials. Threads shall be tapped out of solid metal or molded in solid ABS or PVC.

    2025 CALIFORNIA PLUMBING CODE 51

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    GENERAL REGULATIONS

    310.9 Female Plastic Connections. Female plastic tapered (NPT) threaded connections shall not be allowed to be used when threaded onto a male metallic connection.

    Exception: Female plastic parallel (straight) threaded connections shall be permitted. 310.10 ABS and PVC Transition Joints. Except as provided in Section 705.9.4, PVC and ABS pipe and fittings shall not be solvent welded to dissimilar material.

    310.11 [OSHPD 1, 2, 3, 4 & 5] Drainage piping over oper- ating and delivery rooms, nurseries, food preparation cen- ters, food-serving facilities, food storage areas, compounding ante and buffer rooms and other sensitive areas shall be kept to a minimum and shall not be exposed. Special precautions shall be taken to protect these areas from possible leakage from necessary overhead drainage piping systems. Piping over switchboards, panel boards, and motor control centers are subject to restrictions of the California Electrical Code where applicable. 310.12 [OSHPD 1, 3, 4 & 5] Floor drains, waste traps, san- itary drainage cleanouts and handwashing fixtures shall not be installed in operating and delivery rooms. Floor drains with self-priming traps may be installed in cystoscopic rooms. Floor drains shall not be installed in compounding buffer or

    ante rooms.

  • CPC § 604.1 Medium relevance — show source text

    Plastic|Table 604.1| |ASTM D2846/D2846M-
    2019a|Standard Specification for Chlorinated Poly (Vinyl Chloride)
    (CPVC) Plastic Hot- and Cold-Water Distribution Systems|Piping|Table 604.1, 605.2.2,
    605.3.1| |ASTM D3034-2016|Standard Specification for Type PSM Poly (Vinyl Chloride)
    (PVC) Sewer Pipe and Fittings|Piping, Plastic|Table 701.2| |ASTM D3035-2021|Standard Specification for Polyethylene (PE) Plastic Pipe (DR-
    PR) Based on Controlled Outside Diameter|Piping|Table 604.1| |ASTM D3138-2004
    (R2016)|Standard Specification for Solvent Cement for Transition Joints
    Between Acrylonitrile-Butadiene-Styrene (ABS) and Poly
    (Vinyl Chloride) (PVC) Non-Pressure Piping Components|Joints|705.9.4| |ASTM D3139-2019|Standard Specification for Joints for Plastic Pressure Pipes
    Using Flexible Elastomeric Seals|Joints|605.12.1| |ASTM D3212-2020|Standard Specification for Joints for Drain and Sewer Plastic
    Pipes Using Flexible Elastomeric Seals|Joints|705.1.1, 705.6.1|

    2025 CALIFORNIA PLUMBING CODE 341

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    REFERENCED STANDARDS

    TABLE 1701.1 (continued) REFERENCED STANDARDS

    STANDARD NUMBER STANDARD TITLE APPLICATION REFERENCED
    SECTION
    ASTM D3261-2016 Standard Specification for Butt Heat Fusion Polyethylene (PE)
    Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing
    Fittings Table 604.1
    ASTM D4068-2017 Standard Specification for Chlorinated Polyethylene (CPE)
    Sheeting for Concealed Water-Containment Membrane
    Miscellaneous 408.8.2
    ASTM D4551-2017 Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
    Flexible Concealed Water-Containment Membrane
    Miscellaneous 408.8.1
    ASTM D6104-1997
    (R2017)e1
    Standard Practice for Determining the Performance of
    Oil/Water Separators Subjected to Surface Run-Off
    Interceptors Table 1009.1
    ASTM E84-2021a Standard Test Method for Surface Burning Characteristics of
    Building Materials
    Miscellaneous 701.2(2), 903.1(2),
    1101.4
    ASTM E119-2020 Standard Test Methods for Fire Tests of Building Construction
    and Materials
    Miscellaneous 1404.3, 1405.3
    ASTM E814-2013a (R2017) Standard Test Method for Fire Tests of Penetration Firestop
    Systems
    Miscellaneous 1404.3, 1405.3
    ASTM F409-2017 Standard Specification for Thermoplastic Accessible and
    Replaceable Plastic Tube and Tubular Fittings
    Piping, Plastic 404.
  • CPC § 11.0 Medium relevance — show source text

    11.0 - 1.11.11_|||X|||||||||||||||||||||| |1.13.0||||||||||||||||||||X||||| |Division II - Scope and
    Administration||||||||||||||||||||||||| |101.0||||||||||X|X|X||X|X|||||||||| |102.0||||||||||X|X|X||X|X|||||||||| |103.0||||||||||X|X|X||X|X|||||||||| |104.2 Items 1 & 2||||X|X|||||||||||||||||||| |104.3.1||||||||||X|X|X||X|X|||||||||| |104.4.3.1|X|||||||||||||||||||||||| |105.0||||||||||X|X|X||X|X||||||||||

    This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.

    2 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    CHAPTER 1

    ADMINISTRATION

    DIVISION I

    CALIFORNIA ADMINISTRATION

    1.1.0 General.

    1.1.1 Title. These regulations shall be known as the Califor- nia Plumbing Code, may be cited as such and will be referred to herein as “this code.” The California Plumbing Code is Part 5 of thirteen parts of the official compilation and publi- cation of the adoption, amendment, and repeal of plumbing regulations to the California Code of Regulations, Title 24, also referred to as the California Building Standards Code. This part incorporates by adoption the 2024 Uniform Plumb- ing Code of the International Association of Plumbing and Mechanical Officials with necessary California amendments.

    1.1.2 Purpose. The purpose of this code is to establish the minimum requirements to safeguard the public health, safety and general welfare through structural strength, means of egress facilities, stability, access to persons with disabilities, sanitation, adequate lighting and ventilation, and energy con- servation; safety to life and property from fire and other haz- ards attributed to the built environment; and to provide safety to fire fighters and emergency responders during emergency operations.

    1.1.3 Scope. The provisions of this code shall apply to the construction, alteration, movement, enlargement, replace- ment, repair, equipment, use and occupancy, location, main- tenance, removal, and demolition of every building or structure or any appurtenances connected or attached to such buildings or structures throughout the State of California.

  • CPC § 4.6 Medium relevance — show source text

    Considerations are soil density; clearance from obstacles, utilities, and structures; location of bends, and water service locations. Excavations and shoring shall be in accordance with jurisdictional safety requirements. (c) Set Up Fuse the proper length of polyethylene pipe in accordance with ASTM F2620, or ASTM D3261 and fuse the end to a small length that is attached to the pulling head. A rod pusher cable is pushed through the damaged host pipe and attached to the pulling cable, which is then drawn through the pipe. The clevis end of the cable is attached to the pulling head. The pulling equipment is then set up according to the manufacturer’s instructions.

    (d) Pulling Pull the pulling head through. Once the pull is done, complete the connection to the existing piping.

    4.6 Cleanouts

    4.6.1 Plug Each cleanout fitting for cast-iron pipe shall consist of a cast-iron or brass body and an approved plug. Each cleanout for galvanized wrought-iron, galvanized steel, copper, or brass pipe shall consist of a brass plug as specified in Table 1, or a standard weight brass cap, or an approved ABS or PVC plastic plug, or an approved stainless-steel cleanout or plug. Plugs shall have raised square heads or approved countersunk rectangular slots. 4.6.2 Approved Each cleanout fitting and each cleanout plug, or cap shall be of an approved type.

    452 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    IS 26

    4.6.3 Watertight and Gastight

    Cleanouts shall be designed to be watertight and gastight.

    5 Testing and Inspection Requirements

    5.1 Media

    The piping of the building sewer shall be tested with water. The Authority Having Jurisdiction shall be permitted to require the removal of cleanouts, etc., to ascertain whether the pressure has reached all parts of the system.

    5.2 Water Test

    The system shall be tested by plugging the end of the building sewer at its points of connection to the public sewer or private sewage disposal system and completely filling the building sewer with water from the lowest to the highest point thereof.

    5.3 Inspections

    The completed piping shall be internally inspected by camera unless waived by the Administrative Authority.

    TABLE 1

    CLEANOUTS (See Section 4.6.1)

    NPS SIZE OF CLEANOUT
    (inches)
    THREADS PER INCH
    1.5 1.5 11.5


    2
    1.5 11.5


    2.5
    2.5 8

    3
    2.5 8

    4 & larger
    3.5 8

    Note: For SI units: 1 inch = 25 mm

    Uniform Plumbing Code References

    The following sections of the 2024 Uniform Plumbing Code apply.

    105.2 Required Inspections

    105.2.2 Other Inspections

    105.3 Testing of Systems

    301.2 Minimum Standards

    309.0 Workmanship

    312.0 Protection of Piping, Materials, and Structures

  • CPC § 1701.1 Medium relevance — show source text

    TABLE 1701.1 (continued) REFERENCED STANDARDS

    STANDARD NUMBER STANDARD TITLE APPLICATION REFERENCED
    SECTION
    ASTM D3261-2016 Standard Specification for Butt Heat Fusion Polyethylene (PE)
    Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing
    Fittings Table 604.1
    ASTM D4068-2017 Standard Specification for Chlorinated Polyethylene (CPE)
    Sheeting for Concealed Water-Containment Membrane
    Miscellaneous 408.8.2
    ASTM D4551-2017 Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
    Flexible Concealed Water-Containment Membrane
    Miscellaneous 408.8.1
    ASTM D6104-1997
    (R2017)e1
    Standard Practice for Determining the Performance of
    Oil/Water Separators Subjected to Surface Run-Off
    Interceptors Table 1009.1
    ASTM E84-2021a Standard Test Method for Surface Burning Characteristics of
    Building Materials
    Miscellaneous 701.2(2), 903.1(2),
    1101.4
    ASTM E119-2020 Standard Test Methods for Fire Tests of Building Construction
    and Materials
    Miscellaneous 1404.3, 1405.3
    ASTM E814-2013a (R2017) Standard Test Method for Fire Tests of Penetration Firestop
    Systems
    Miscellaneous 1404.3, 1405.3
    ASTM F409-2017 Standard Specification for Thermoplastic Accessible and
    Replaceable Plastic Tube and Tubular Fittings
    Piping, Plastic 404.1
    ASTM F437-2021 Standard Specification for Threaded Chlorinated Poly (Vinyl
    Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80
    Fittings Table 604.1
    ASTM F438-2017 Standard Specification for Socket-Type Chlorinated Poly
    (Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 40
    Fittings Table 604.1
    ASTM F439-2019 Standard Specification for Chlorinated Poly (Vinyl Chloride)
    (CPVC) Plastic Pipe Fittings, Schedule 80
    Fittings Table 604.1
    ASTM F441/F441M-2020 Standard Specification for Chlorinated Poly (Vinyl Chloride)
    (CPVC) Plastic Pipe, Schedules 40 and 80
    Piping Table 604.1
    ASTM F442/F442M-2020 Standard Specification for Chlorinated Poly (Vinyl Chloride)
    (CPVC) Plastic Pipe (SDR-PR)
    Piping Table 604.1, 605.2.2
    ASTM F493-2020 Standard Specification for Solvent Cements for Chlorinated
    Poly (Vinyl Chloride) (CPVC) Plastic Pipe and Fittings
    Joints 605.2.2, 605.3.1
    ASTM F628-2012e3 Standard Specification for Acrylonitrile-Butadiene-Styrene
    (ABS) Schedule 40 Plastic Drain, Waste, and Vent Pipe with a
    Cellular Core
    Piping Table 701.2
    ASTM F656-2021 Standard Specification for Primers for Use in Solvent Cement
    Joints of Poly (Vinyl Chloride) (PVC) Plastic Pipe and Fittings
    Joints 605.2.

Frequently asked questions

Do the CPC rules specify how thick the insulating cover must be?

No. The CPC requires that protectors or insulating covers be used and that they comply with ASME A112.18.9 or ASTM C1822 (§ 403.3). The CPC itself does not set thickness or R‑value; consult the referenced standard or product listing for those technical details.

Can I simply box‑in the pipes with plywood to meet § 403.3?

You may enclose piping provided the enclosure prevents contact and does not interfere with required accessibility clearances or fixture servicing. The CPC requires use of protectors/insulators that comply with the listed standards when used; if you rely on an enclosure, be prepared to demonstrate it provides equivalent protection and service access. See § 403.3.

Which standard should I ask for on the manufacturer’s data sheet?

Ask for evidence of compliance with ASME A112.18.9 or ASTM C1822 for insulating covers/protectors; the CPC references those standards for § 403.3 and lists ASTM C1822 in the referenced standards table.

If a lav is not required to be accessible, does § 403.3 still apply?

§ 403.3 specifically addresses exposed pipes under accessible lavatories and sinks. If the facility is not an accessible fixture subject to the building accessibility requirements, the specific § 403.3 requirement for insulating covers under accessible lavs would not be triggered; however, general piping protection rules (e.g., § 312.1/§ 312.2) still apply.

Where do I find the detailed requirements for accessible fixture clearances?

The CPC points to ICC A117.1 and Chapter 11A of the California Building Code for detailed dimensions and clearances for accessible fixtures — see § 403.2 and § 403.1.

More in California Plumbing Code

Ask about the CPC

Get cited, plain-English answers on the California Plumbing Code for your project — any code section, any scenario.

Start Free Trial

Related in the CPC