CPC · California Plumbing Code

Vents

Chapter 9 of the California Plumbing Code governs the materials, sizing, installation, and termination of plumbing vents to protect trap seals, control sewer gas, and ensure proper drainage.

Last reviewed: July 6, 2026

Overview

Chapter 9 of the California Plumbing Code sets requirements for plumbing vent systems — their purpose, materials, sizing, installation and termination. Vents provide air circulation to prevent trap siphonage and backpressure, control sewer gases, and help drainage flow quietly and efficiently.

Proper venting protects trap seals (limit of 1 inch water column pressure differential is required) and is tightly linked to drain sizing and layout; vent design therefore affects fixture performance, odor control, and code compliance. See the chapter’s general requirements and trap-seal protection in §901.0 and §901.3.

Key provisions you’ll consult here include §901.0 (General), §903.0 (Materials), §904.0 (Size of Vents), §905.0 (Vent Pipe Grades and Connections), §906.0 (Vent Termination), §907.0 (Vent Stacks and Relief Vents), and the wet-, combination- and circuit-venting rules in §§908.0–911.0, plus engineered venting in §912.0. Use these sections and the associated sizing tables when laying out or reviewing vent systems.

In this section

Code references

Grounded in the retrieved California Plumbing Code — click a citation to read the verbatim passage:

  • CPC § 1.1 High relevance — show source text

    1(2)_||||X||||||||||||||||||||| |903.1.1||||X|X|||||||||||||||||||| |903.1.2||||X||||||||||||||||||||| |903.1.3||||||||||X||X|X|X|X|||||||||| |906.2.1||||||||||X|X|X|X|X|X||||||||||

    This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.

    2025 CALIFORNIA PLUMBING CODE 187

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    188 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    CHAPTER 9

    VENTS

    901.0 General.

    901.1 Applicability. This chapter shall govern the materials, design, and installation of plumbing vent systems. 901.2 Vents Required. Each plumbing fixture trap, except as otherwise provided in this code, shall be protected against siphonage and backpressure, and air circulation shall be ensured throughout all parts of the drainage system by means of vent pipes installed in accordance with the requirements of this chapter and as otherwise required by this code. 901.3 Trap Seal Protection. The vent system shall be designed to prevent a trap seal from being exposed to a pressure differential that exceeds 1 inch water column (0.24 kPa) on the outlet side of the trap.

    902.0 Vents Not Required.

    902.1 Interceptor. Vent piping shall be permitted to be omitted on an interceptor where such interceptor acts as a primary settling tank and discharges through a horizontal indirect waste pipe into a secondary interceptor. The second interceptor shall be properly trapped and vented. 902.2 Bars, Soda Fountains, and Counter. Traps serving sinks that are part of the equipment of bars, soda fountains, and counters need not be vented where the location and construction of such bars, soda fountains, and counters are such as to make it impossible to do so. Where such conditions exist, said sinks shall discharge using approved indirect waste pipes into a floor sink or other approved type of recep tor.

    903.0 Materials.

    903.1 Applicable Standards. Vent pipe and fittings shall comply with the applicable standards referenced in Table 701.2, except that:

    (1) No galvanized steel or 304 stainless steel pipe shall be installed underground and shall be not less than 6 inches (152 mm) aboveground.

  • CPC § 811.7 High relevance — show source text

    811.7 Discharge . . . . . . . . . . . . . . . . . . .183

    811.8 Diluted Chemicals . . . . . . . . . . . . .183

    812.0 Clear Water Wastes . . . . . . . . . . .183

    812.1 General . . . . . . . . . . . . . . . . . . . . .183

    813.0 Swimming Pools . . . . . . . . . . . . . .183

    813.1 General . . . . . . . . . . . . . . . . . . . . .183

    814.0 Condensate Waste and Control . . .183

    814.1 Condensate Disposal . . . . . . . . . .183

    814.2 Condensate Control . . . . . . . . . . .184

    814.3 Condensate Waste Pipe Material and Sizing . . . . . . . . . . . .184

    Table 814.3 Minimum Condensate Pipe Size . . . . . . . . . . . . . . . . . . .184

    814.4 Appliance Condensate Drains . . .184

    814.5 Point of Discharge . . . . . . . . . . . .184

    814.6 Condensate Waste from

    Air-Conditioning Coils . . . . . . . . . .185

    814.7 Plastic Fittings . . . . . . . . . . . . . . .185

    xxxvi 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    TABLE OF CONTENTS

    CHAPTER 9 VENTS . . . . . . . . . . . . . . . . . . . . .187

    901.0 General . . . . . . . . . . . . . . . . . . . . .189

    901.1 Applicability . . . . . . . . . . . . . . . . . .189

    901.2 Vents Required . . . . . . . . . . . . . . .189

    901.3 Trap Seal Protection . . . . . . . . . . .189

    902.0 Vents Not Required . . . . . . . . . . .189

    902.1 Interceptor . . . . . . . . . . . . . . . . . .189

    902.2 Bars, Soda Fountains, and Counter . . . . . . . . . . . . . . . . . . . . .189

    903.0 Materials . . . . . . . . . . . . . . . . . . . .189

    903.1 Applicable Standards . . . . . . . . . .189

    903.2 Use of Copper or Copper Alloy Tubing . . . . . . . . . . . . . . . . .189

    903.3 Changes in Direction . . . . . . . . . .189

    904.0 Size of Vents . . . . . . . . . . . . . . . .189

    904.1 Size . . . . . . . . . . . . . . . . . . . . . . . .189

    904.2 Length . . . . . . . . . . . . . . . . . . . . . .189

  • CPC § 901.0 High relevance — show source text

    TABLE OF CONTENTS

    CHAPTER 9 VENTS . . . . . . . . . . . . . . . . . . . . .187

    901.0 General . . . . . . . . . . . . . . . . . . . . .189

    901.1 Applicability . . . . . . . . . . . . . . . . . .189

    901.2 Vents Required . . . . . . . . . . . . . . .189

    901.3 Trap Seal Protection . . . . . . . . . . .189

    902.0 Vents Not Required . . . . . . . . . . .189

    902.1 Interceptor . . . . . . . . . . . . . . . . . .189

    902.2 Bars, Soda Fountains, and Counter . . . . . . . . . . . . . . . . . . . . .189

    903.0 Materials . . . . . . . . . . . . . . . . . . . .189

    903.1 Applicable Standards . . . . . . . . . .189

    903.2 Use of Copper or Copper Alloy Tubing . . . . . . . . . . . . . . . . .189

    903.3 Changes in Direction . . . . . . . . . .189

    904.0 Size of Vents . . . . . . . . . . . . . . . .189

    904.1 Size . . . . . . . . . . . . . . . . . . . . . . . .189

    904.2 Length . . . . . . . . . . . . . . . . . . . . . .189

    905.0 Vent Pipe Grades and Connections . . . . . . . . . . . . . . . . .190

    905.1 Grade . . . . . . . . . . . . . . . . . . . . . .190

    905.2 Horizontal Drainage Pipe . . . . . . .190

    905.3 Vent Pipe Rise . . . . . . . . . . . . . . .190

    905.4 Roof Termination . . . . . . . . . . . . .190

    905.5 Location of Opening . . . . . . . . . . .190

    905.6 Common Vertical Pipe . . . . . . . . .190

    906.0 Vent Termination . . . . . . . . . . . . .190

    906.1 Roof Termination . . . . . . . . . . . . .190

    906.2 Clearance . . . . . . . . . . . . . . . . . . .190

    906.3 Use of Roof . . . . . . . . . . . . . . . . .190

    906.4 Outdoor Installations . . . . . . . . . . .190

    906.5 Joints . . . . . . . . . . . . . . . . . . . . . .190

    906.6 Lead . . . . . . . . . . . . . . . . . . . . . . .190

    906.7 Frost or Snow Closure . . . . . . . . .190

    907.0 Vent Stacks and Relief Vents . . . .190

    907.1 Drainage Stack . . . . . . . . . . . . . . .190

    907.2 Yoke Vent . . . . . . . . . . . . . . . . . . .190

  • CPC § 2025 High relevance — show source text

    Chapter 7 Sanitary Drainage.

    This chapter regulates the design and installation of sanitary drainage systems to ensure they will work as intended. Drainage piping should not be oversized nor undersized, and constructed of approved materials to guard against fouling, deposit of solids, clogging, and with cleanouts so arranged that the pipes may be readily cleaned. The purpose of the sanitary drainage system is to remove effluent discharged from plumbing fixtures and other equipment to an approved point of disposal, such as a public sanitary system or private sewage disposal system.

    The basics of a sanitary drainage system include public and private sewage disposal; selection of materials; installation of the building drain and sewer; joining methods for pipe and fittings; drainage fixture units for sizing the drainage system; sumps and ejectors; vent sizing and length of vents; and testing.

    Chapter 8 Indirect Wastes.

    Chapter 8 regulates indirect waste connections that are required for plumbing fixtures and plumbing appliances dealing with food preparation, dishwashing, potable liquids, and similar equipment. An indirect connection prevents sewage from backing up into a fixture or appliance, thus providing protection against potential health hazards. The waste pipe discharges through an air gap or air break into a waste receptor or standpipe. The protection in the form of an air gap is necessary when the contamination is a potential health hazard or cross connection with the potable water system. Where there is no possibility of contaminating the potable water (nonpotable discharge), the indirect waste pipe may connect in the form of an air break. This method is often preferred to prevent splashing. In addition, health care facilities and special wastes must be protected from contamination that may result from the connection to the drainage system. The waste must be treated to prevent any damage to the piping or sewage treatment process. Waste receptors are sized and designed to prevent splashing and allow for peak discharge conditions.

    Chapter 9 Vents.

    Chapter 9 regulates the material, design, and installation of vents. A vent system is a pipe or pipes installed in a drainage system that provide a flow of air to and from the system to ventilate it, provide a circulation of air to eliminate trap siphonage, and reduce back-pressure and vacuum surge. In addition, vents provide the rapid and silent flow of waste without exposing occupants of the building to any sewer gases. Proper installation of vents is crucial, as a telltale sign that there is a problem in the drain and vent system is related to the elevation of the horizontal portion of the venting. Venting is not limited to sanitary drainage systems. Venting methods are applicable to other drainage systems such as those for chemical waste, graywater waste, and clear water waste. Sizing the venting system is directly tied to the design of the drainage system. For example, the velocities in the drainage system and its peak flow rates affect the diameters in the venting system. Where the vertical distance between a fixture outlet and trap is excessive, velocities in the entire drainage system will be greater than those in the vent sizing table. All venting methods in this chapter are categorized as either dry vents or wet vents. Vent stacks, stack vents, branch vents, island vents, relief vents, and individual vents are dry vents. Wet vents (horizontal or vertical), circuit vents, combination drain and vents are versions of “wet venting” in which the vent is wetted by drainage flow.

    2025 CALIFORNIA PLUMBING CODE xv

  • CPC § 2025 Medium relevance — show source text

    The waste must be treated to prevent any damage to the piping or sewage treatment process. Waste receptors are sized and designed to prevent splashing and allow for peak discharge conditions.

    Chapter 9 Vents.

    Chapter 9 regulates the material, design, and installation of vents. A vent system is a pipe or pipes installed in a drainage system that provide a flow of air to and from the system to ventilate it, provide a circulation of air to eliminate trap siphonage, and reduce back-pressure and vacuum surge. In addition, vents provide the rapid and silent flow of waste without exposing occupants of the building to any sewer gases. Proper installation of vents is crucial, as a telltale sign that there is a problem in the drain and vent system is related to the elevation of the horizontal portion of the venting. Venting is not limited to sanitary drainage systems. Venting methods are applicable to other drainage systems such as those for chemical waste, graywater waste, and clear water waste. Sizing the venting system is directly tied to the design of the drainage system. For example, the velocities in the drainage system and its peak flow rates affect the diameters in the venting system. Where the vertical distance between a fixture outlet and trap is excessive, velocities in the entire drainage system will be greater than those in the vent sizing table. All venting methods in this chapter are categorized as either dry vents or wet vents. Vent stacks, stack vents, branch vents, island vents, relief vents, and individual vents are dry vents. Wet vents (horizontal or vertical), circuit vents, combination drain and vents are versions of “wet venting” in which the vent is wetted by drainage flow.

    2025 CALIFORNIA PLUMBING CODE xv

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    FORMAT OF THE UNIFORM PLUMBING CODE

    Chapter 10 Traps and Interceptors.

    Chapter 10 regulates the material, design, and installation of traps, interceptors, and separators. Traps are required on drainage type plumbing fixtures and must be self-scouring without interior partitions. Interceptors, on the other hand, are designed to control what goes down a drain. Interceptors are used to keep harmful substances from entering the sanitary drainage system, such as grease, sand, oil and other materials. The retained materials need periodic removal to maintain efficiency and function of the separating device. The capacity of an interceptor is based on retention and flow rate. There are many types of interceptors that are used at beauty salons, hospitals, meat, fish or foul packaging, refineries, repair garages, gas stations, car washing facilities, various plants, factories, and processing sites. The designer of the building is responsible for locating interceptors with the expectation for the frequency of maintenance, ease of cleaning and floor space for equipment.

    Chapter 11 Storm Drainage.

    Chapter 11 regulates the removal of stormwater from roofs, yards, paved areas, and similar areas. The objective of storm drainage systems is to provide a conduit or channel through which runoff will be carried from a point of collection to a point of disposal; this protects the property and the public from the uncontrolled flow of runoff and ensures that drains and inlets are adequately sized to receive the volume of runoff that flows to the drains. For the purpose of system design, it’s necessary to specify the duration of a selected storm.

  • CPC § 904.0. Medium relevance — show source text

    VENTS

    smaller than the minimum vent pipe size required for a fixture served, or by Section 904.0. 908.2 Horizontal Wet Venting for a Bathroom Group. A bathroom group located on the same floor level shall be permitted to be vented by a horizontal wet vent where all of the conditions of Section 908.2.1 through Section 908.2.5 are met.

    908.2.1 Vent Connection. The dry vent connection to the wet vent shall be an individual vent for the bidet, shower, or bathtub. One or two vented lavatory(s) shall be permitted to serve as a wet vent for a bathroom group. Only one wet-vented fixture drain or trap arm shall discharge upstream of the dry-vented fixture drain connection. Dry vent connections to the horizontal wet vent shall be in accordance with Section 905.2 and Section

    905.3.

    908.2.2 Size. The wet vent shall be sized based on the fixture unit discharge into the wet vent. The wet vent shall be not less than 2 inches (50 mm) in diameter for 4 drainage fixture units (dfu) or less, and not less than 3 inches (80 mm) in diameter for 5 dfu or more. The dry vent shall be sized in accordance with Table 702.1 and Table 703.2 based on the total fixture units discharging into the wet vent.

    908.2.3 Trap Arm. The length of the trap arm shall not exceed the limits in Table 1002.2. The trap size shall be in accordance with Section 1003.3. The vent pipe opening from the horizontal wet vent, except for water closets and similar fixtures, shall not be below the weir of the trap.

    908.2.4 Water Closet. The water closet fixture drain or trap arm connection to the wet vent shall be downstream of fixture drain or trap arm connections to the horizontal wet vent.

    908.2.5 Additional Fixtures. Additional fixtures shall discharge downstream of the wet vent system and be conventionally vented. Only the fixtures within the bathroom group shall connect to the wet-vented horizontal branch.

    909.0 Special Venting for Island Fixtures. 909.1 General. Traps for island sinks and similar equipment shall be roughed in above the floor and shall be permitted to be vented by extending the vent as high as possible, but not less than the drainboard height and then returning it downward and connecting it to the horizontal sink drain immediately downstream from the vertical fixture drain. The return vent shall be connected to the horizontal drain through a wyebranch fitting and shall, in addition, be provided with a foot vent taken off the vertical fixture vent by means of a wye branch immediately below the floor and extending to the nearest partition and then through the roof to the open air, or shall be permitted to be connected to other vents at a point not less than 6 inches (152 mm) above the flood-level rim of the fixtures served. Drainage fittings shall be used on the vent below the floor level, and a slope of not less than [1] ⁄ 4 inch per foot (20.8 mm/m) back to the drain shall be maintained. The return bend used under the drainboard shall be a one-piece

  • CPC § 907.2 Medium relevance — show source text

    907.2 Yoke Vent. The yoke vent connection to the vent stack shall be placed not less than 42 inches (1067 mm) above the floor level, and the yoke vent connection to the drainage stack shall be using a wye-branch fitting placed below the lowest drainage branch connection serving that floor.

    908.0 Wet Venting. 908.1 Vertical Wet Venting. Wet venting is limited to vertical drainage piping receiving the discharge from the trap arm of one and two fixture unit fixtures that also serves as a vent not exceeding four fixtures. Wet-vented fixtures shall be within the same story; provided, further, that fixtures with a continuous vent discharging into a wet vent shall be within the same story as the wet-vented fixtures. No wet vent shall exceed 6 feet (1829 mm) in developed length. 908.1.1 Size. The vertical piping between two consecutive inlet levels shall be considered a wet-vented sec tion. Each wet-vented section shall be not less than one pipe size exceeding the required minimum waste pipe size of the upper fixture or shall be one pipe size exceeding the required minimum pipe size for the sum of the fixture units served by such wet-vented section, whichever is larger, but in no case less than 2 inches (50 mm) in diameter. 908.1.2 Vent Connection. Common vent sizing shall be the sum of the fixture units served but, in no case,

    190 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    VENTS

    smaller than the minimum vent pipe size required for a fixture served, or by Section 904.0. 908.2 Horizontal Wet Venting for a Bathroom Group. A bathroom group located on the same floor level shall be permitted to be vented by a horizontal wet vent where all of the conditions of Section 908.2.1 through Section 908.2.5 are met.

    908.2.1 Vent Connection. The dry vent connection to the wet vent shall be an individual vent for the bidet, shower, or bathtub. One or two vented lavatory(s) shall be permitted to serve as a wet vent for a bathroom group. Only one wet-vented fixture drain or trap arm shall discharge upstream of the dry-vented fixture drain connection. Dry vent connections to the horizontal wet vent shall be in accordance with Section 905.2 and Section

    905.3.

    908.2.2 Size. The wet vent shall be sized based on the fixture unit discharge into the wet vent. The wet vent shall be not less than 2 inches (50 mm) in diameter for 4 drainage fixture units (dfu) or less, and not less than 3 inches (80 mm) in diameter for 5 dfu or more. The dry vent shall be sized in accordance with Table 702.1 and Table 703.2 based on the total fixture units discharging into the wet vent.

    908.2.3 Trap Arm. The length of the trap arm shall not exceed the limits in Table 1002.2. The trap size shall be in accordance with Section 1003.3. The vent pipe opening from the horizontal wet vent, except for water closets and similar fixtures, shall not be below the weir of the trap.

  • CPC § 705.10 Medium relevance — show source text

    Waste,
    and Vent (DWV), Sewer, Sanitary, and Storm Plumbing Sys-
    tems for Above and Below Ground Use|Joints|705.10|

    340 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    REFERENCED STANDARDS

    TABLE 1701.1 (continued) REFERENCED STANDARDS

    STANDARD NUMBER STANDARD TITLE APPLICATION REFERENCED
    SECTION
    ASTM C1540-2020 Standard Specification for Heavy-Duty Shielded Couplings
    Joining Hubless Cast Iron Soil Pipe and Fittings
    Joints 705.2.2
    ASTM C1563-2008
    (R2021)
    Standard Test Method for Gaskets for Use in Connection with
    Hub and Spigot Cast Iron Soil Pipe and Fittings for Sanitary
    Drain, Waste, Vent, and Storm Piping Applications
    Joints 705.2.2
    ASTM C1822-2021 Standard Specification for Insulating Covers on Accessible
    Lavatory Piping
    Miscellaneous 403.3
    ASTM D1253-2014 Standard Test Method for Residual Chlorine in Water Miscellaneous 1506.10.6, 1603.4.1
    ASTM D1785-2021a Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
    Pipe, Schedules 40, 80, and 120
    Piping Table 604.1, Table
    701.2
    ASTM D2235-2021 Standard Specification for Solvent Cement for Acrylonitrile-
    Butadiene-Styrene (ABS) Plastic Pipe and Fittings
    Joints 705.1.2
    ASTM D2239-2021 Standard Specification for Polyethylene (PE) Plastic Pipe
    (SIDR-PR) Based on Controlled Inside Diameter
    Piping Table 604.1
    ASTM D2241-2020 Standard Specification for Poly (Vinyl Chloride) (PVC) Pressure-
    Rated Pipe (SDR Series)
    Piping Table 604.1
    ASTM D2464-2015 Standard Specification for Threaded Poly (Vinyl Chloride)
    (PVC) Plastic Pipe Fittings, Schedule 80
    Fittings Table 604.1
    ASTM D2466-2021 Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
    Pipe Fittings, Schedule 40
    Fittings Table 604.1
    ASTM D2467-2020 Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
    Pipe Fittings, Schedule 80
    Fittings Table 604.1
    ASTM D2513-2020 Standard Specification for Polyethylene (PE) Gas Pressure
    Pipe, Tubing, and Fittings
    Piping 1208.5.4, 1208.5.6.2,
    1208.5.10.2,
    1210.1.7.1(1)
    ASTM D2564-2020 Standard Specification for Solvent Cements for Poly (Vinyl
    Chloride) (PVC) Plastic Piping Systems
    Joints 605.12.2, 705.6.
  • CPC § 910.7 Medium relevance — show source text

    910.7 Fixtures. No water closet or urinal shall be installed on such a system. Other one, two, or three unit fixtures remotely located from the sanitary system and adjacent to a combination waste and vent system shall be permitted to be connected to such system in the conventional manner by means of waste and vent pipes of regular sizes, providing that the two pipe size increase required in Section 910.4 is based on the total fixture unit load connected to the system.

    See Appendix B of this code for explanatory notes on the design of combination waste and vent systems.

    911.0 Circuit Venting. 911.1 Circuit Vent Permitted. A maximum of eight flooroutlet water closets, showers, bathtubs, or floor drains con

    2025 CALIFORNIA PLUMBING CODE 191

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    VENTS

    nected to a horizontal branch shall be permitted to be circuit vented. Each trap arm shall connect horizontally to the horizontal branch being circuit vented in accordance with Table 1002.2. The horizontal branch shall be classified as a drain and a vent from the most downstream trap arm connection to the most upstream trap arm connection to the horizontal branch.

    Exception: Back-outlet and wall-hung water closets shall be permitted to be circuit vented provided that no floor-outlet fixtures are connected to the same horizontal branch. Backoutlet and wall-hung water closets shall connect horizontally to the horizontal circuit vented drain.

    911.2 Circuit Vent Size and Connection. The circuit vent size shall be in accordance with Table 703.2 according to the number of circuit vented fixtures connected to the horizontal branch but shall be not less than 2 inches (50 mm) in diameter. The vent shall connect to the horizontal branch on the vertical between the two most upstream trap arms. The circuit vent pipe shall not receive the discharge of soil or

    waste.

    911.2.1 Multiple Circuit Vents. When multiple circuit vents are interconnected according to Section 911.4.1, each individual circuit vent shall be sized according to Section 911.2. The vent pipe connecting each circuit vent shall be sized according to Table 703.2.

    911.3 Relief Vent. A 2 inch (50 mm) relief vent shall be provided for circuit-vented horizontal branches receiving the discharge of four or more water closets when connecting to a drainage stack that receives the discharge of soil or waste from upper horizontal branches.

    911.3.1 Connection and Installation. The relief vent

    shall connect to the horizontal branch between the stack and the most downstream trap arm of the circuit vent. The relief vent shall be installed on the vertical to the

    horizontal branch.

    911.3.2 Fixture Drain. The relief vent is permitted to serve as a fixture drain. Fixtures discharging to a relief vent shall be one or two fixture unit fixtures but shall not

    exceed a total of 4 fixture units.

    911.4 Slope and Size of Horizontal Branch. The vented section of the horizontal branch shall be uniformly sloped and not more than 1 inch per foot (83.3 mm/m). The entire length of the vented section of the horizontal branch shall be sized for the total drainage discharge to the branch according to Table 703.2.

  • CPC § 814.4. Medium relevance — show source text

    An individual condensate drain shall be trapped in accordance with the appliance manufacturer’s instructions or in accordance with Section 814.4.

    TABLE 814.3

    MINIMUM CONDENSATE PIPE SIZE

    For SI units: 1 ton of refrigerant = 3.52 kW, 1 inch = 25 mm

    For SI units: °C = (°F-32)/1.8

    184 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    INDIRECT WASTES

    814.6 Condensate Waste from Air-Conditioning Coils. Where the condensate waste from air-conditioning coils discharges by direct connection to a lavatory tailpiece or to an approved accessible inlet on a bathtub overflow, the connection shall be located in the area controlled by the same person controlling the air-conditioned space. 814.7 Plastic Fittings. Female plastic screwed fittings shall be used with male plastic fittings and plastic threads.

    2025 CALIFORNIA PLUMBING CODE 185

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    186 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    CALIFORNIA PLUMBING CODE – MATRIX ADOPTION TABLE

    CHAPTER 9 - VENTS

    (Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

    Adopting Agency BSC BSC-
    CG
    SFM HCD Col6 Col7 DSA Col9 Col10 OSHPD Col12 Col13 Col14 Col15 Col16 Col17 BSCC DPH AGR DWR CEC CA SL SLC
    Adopting Agency BSC BSC-
    CG
    SFM 1 2 1-AC AC ** SS** SS/CC 1 1R 2 3 4 5 6 6 6 6 6 6 6 6 6
    Adopt Entire Chapter X X X
    Adopt Entire Chapter as
    amended (amended
    sections listed below)
    X X X X X X X X
    Adopt only those sections
    that are listed below
    Chapter/Section
    903.1(2) X
    903.1.1 X X
    _903.1.
  • CPC § 316.0 Medium relevance — show source text

    INCREASERS AND REDUCERS . . . . . . . . . . . . . . . .316.0

    INDIRECT-FIRED WATER HEATERS . . . . . . . .211.0, 505.4,

    603.5.4, 608.7 INDIRECT WASTE . . . . . . . . . . . . . . . . . . . . . . . .Chapter 8 Air gap or break . . . . . . . . . . . . . . . . . . . . . . . . . . .801.2 Appliances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .807.0 Approval required . . . . . . . . . . . . . . . . . . . . . . . . .802.0 Aspirators . . . . . . . . . . . . . . . . . . . . . . .603.5.9, 1303.5

    Chemical wastes . . . . . . . . . . . . . . . . . . . . . . . . . .811.0

    Cleanouts . . . . . . . . . . . . . . . . . . . . . . . . .801.3.2, 803.3

    Clear water wastes . . . . . . . . . . . . . . . . . . . . . . . .812.0

    Condensate . . . . . . . . . . . . . . . . . .814.1, 814.1.1, 814.5 Food handling fixtures . . . . . . . . . . . . . . . . . . . . .801.3.3 High temperature discharge . . . . . . . . . . . . . . . . .810.1 Interceptor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .902.1 Receptors . . . . . . . . . . . . . . . . . . . . . . . . . .801.4, 804.0 Sterile equipment . . . . . . . . . . . .801.6, 806.0, 1303.4.1 Swimming pools . . . . . . . . . . . . . . . . . . . . . . . . . .813.0 Traps . . . . . . . . . . . . . . . . . . . . . . .801.3.2, 803.3, 814.5

    Vents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .803.3

    Where required . . . . . . . . . . . . . . . . . . . . . . . . . . .801.2

    INDIVIDUAL VENTS . . . . . . . . . . .211.0, Table 703.2, 904.1,

    908.2.1

    2025 CALIFORNIA PLUMBING CODE 569

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    INDEX

    INDUSTRIAL WASTES

  • CPC § 906.4 Medium relevance — show source text

    906.4 Outdoor Installations. Vent pipes for outdoor installations shall extend not less than 10 feet (3048 mm) above the surrounding ground and shall be securely supported.

    906.5 Joints. Joints at the roof around vent pipes shall be made watertight by the use of approved flashings or flashing material.

    906.6 Lead. (See Chapter 17) Sheet lead shall comply with the following:

    (1) For safe pans – not less than 4 pounds per square foot (lb/ft [2] ) (19 kg/m [2] ) or [1] ⁄ 16 of an inch (1.6 mm) thick. (2) For flashings or vent terminals – not less than 3 lb/ft [2] (15 kg/m [2] ) or 0.0472 of an inch (1.2 mm) thick. (3) Lead bends and lead traps shall be not less than [1] ⁄ 8 of an inch (3.2 mm) in wall thickness.

    906.7 Frost or Snow Closure. Where frost or snow closure is likely to occur in locations having minimum design temperature below 0°F (-17.8°C), vent terminals shall be not less than 3 inches (76 mm) in diameter, but in no event smaller than the required vent pipe. The change in diameter shall be made inside the building not less than 1 foot (305 mm) below the roof in an insulated space and terminate not less than 10 inches (254 mm) above the roof, or in accordance with the Authority Having Jurisdiction.

    907.0 Vent Stacks and Relief Vents.

    907.1 Drainage Stack. Each drainage stack that extends 10 or more stories shall be served by a parallel vent stack, which shall extend undiminished in size from its upper terminal and connect to the drainage stack at or immediately below the lowest fixture drain. Each such vent stack shall also be connected to the drainage stack at each fifth floor, counting down from the uppermost fixture drain, using a yoke vent, the size of which shall be not less in diameter than either the drainage or the vent stack, whichever is smaller.

    907.2 Yoke Vent. The yoke vent connection to the vent stack shall be placed not less than 42 inches (1067 mm) above the floor level, and the yoke vent connection to the drainage stack shall be using a wye-branch fitting placed below the lowest drainage branch connection serving that floor.

    908.0 Wet Venting. 908.1 Vertical Wet Venting. Wet venting is limited to vertical drainage piping receiving the discharge from the trap arm of one and two fixture unit fixtures that also serves as a vent not exceeding four fixtures. Wet-vented fixtures shall be within the same story; provided, further, that fixtures with a continuous vent discharging into a wet vent shall be within the same story as the wet-vented fixtures. No wet vent shall exceed 6 feet (1829 mm) in developed length. 908.1.1 Size. The vertical piping between two consecutive inlet levels shall be considered a wet-vented sec tion. Each wet-vented section shall be not less than one pipe size exceeding the required minimum waste pipe size of the upper fixture or shall be one pipe size exceeding the required minimum pipe size for the sum of the fixture units served by such wet-vented section, whichever is larger, but in no case less than 2 inches (50 mm) in diameter. **908.1.2 Vent Connection.

Frequently asked questions

What is the primary function of a vent under the CPC?

A vent supplies air to the drainage system to prevent trap siphonage and backpressure, ensure rapid silent flow, and keep sewer gases out of occupied spaces; the requirement and intent are described in §901.0–§901.3.

Where are vent sizes and minimums specified?

Vent sizing is governed by §904.0 and the vent-sizing tables referenced throughout Chapter 9 (and related tables such as Table 702.1/Table 703.2 for common-vent and circuit-vent sizing). Always verify developed length and total fixture units when selecting vent diameter.

Can vents terminate through the roof and are there clearance rules?

Yes — roof termination rules, required clearances, and special provisions (including frost/snow protection and outdoor vent height/support) are in §906.0 and its subsections (e.g., §906.1–§906.7).

More in California Plumbing Code

Ask about the CPC

Get cited, plain-English answers on the California Plumbing Code for your project — any code section, any scenario.

Start Free Trial

Related in the CPC