Sec. 903.4.1 Electronic Supervision. Valves controlling the water supply for automatic¶
sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, and water- flow switches on all automatic sprinkler systems shall be electronically supervised by a listed fire alarm control unit.
Exceptions: 1. Automatic sprinkler systems with less than 100 fire sprinklers protecting one-family and two-family dwellings and Group U occupancies. 2. Limited area sprinkler systems in accordance with Section 903.3.8. 3. Automatic sprinkler systems installed in accordance with NFPA 13R edition referenced in Chapter 80 CFC. Where a common supply main is used to supply both domestic water
16.40(21) ( Vista 10/24/2025)
Vista Municipal Code
and the automatic sprinkler system and a separate control valve for the automatic sprinkler system is not provided. 4. Jockey pump control valves that are sealed or locked in the open position. 5. Control valves to commercial kitchen hoods, paint spray booths, or dip tanks that are sealed or locked in the open position. 6. Valves controlling the fuel supply to fire pump engines that are sealed or locked in the open position. 7. Trim valves to pressure switches in dry, preaction, and deluge sprinkler systems that are sealed or locked in the open position. 8. Underground key or hub gate valves in roadway boxes.
SECTION 1205.5 GROUND-MOUNTED PHOTOVOLTAIC ARRAYS.
Section 1205.5 of the CFC is revised to read: