Skip to content

Title 32 — FIRE CODE

Los Angeles County Municipal Code § 910.2 Where required

Los Angeles County Municipal Code · 2026-09 edition · updated 2026-10-04 · Los Angeles County

Cite as: Los Angeles County Municipal Code § 910.2 · Text as of 2026-10-04

Smoke and heat vents or a mechanical smoke removal system shall be installed as required by Sections 910.2.1 and 910.2.2.

Exception:

Frozen food warehouses used solely for storage of Class I and II commodities where protected by an approved automatic sprinkler system.

910.2.3 - Group S-2.

Group S-2 buildings, and portions thereof, containing a total basement-area enclosed parking garage exceeding 12,000 square feet (1108 m 2 ) shall require a mechanical smoke-removal system installed in accordance with Section 910.4.

Exceptions & meaning →

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — Los Angeles County Municipal Code

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.