1203.2.3 - Emergency responder communication coverage systems.¶
Standby power shall be provided for in-building, two-way emergency responder communication coverage systems as required in Section 510.4.2.3. The standby power supply shall be capable of operating the in-building, two-way emergency responder communication coverage system at 100-percent system operation capacity for a duration of not less than 24 hours.
1203.2.5 - Exhaust ventilation.¶
Standby power shall be provided for mechanical exhaust ventilation systems as required in Section 1207.6.1.3. The system shall be capable of powering the required load for a duration of not less than 6 hours.
1203.2.7 - Gas detection systems.¶
Emergency power shall be provided for gas detection systems where required by Sections 1203.2.10 and 1203.2.17. Standby power shall be provided for gas detection systems where required by Sections 916.5 and 1207.6.1.6.
1204 - PORTABLE GENERATORS