905.2.1 - Class I standpipes—rating.

Materials and devices shall be of sufficient strength to withstand not less than 200 pounds per square inch (1379 kPa) of water pressure when ready for service. All Class I standpipes shall be tested hydrostatically to withstand not less than 200 pounds per square inch (1379 kPa) of pressure for 2 hours, but in no case shall the pressure be less than 50 pounds per square inch (344.7 kPa) above the maximum working pressure.