Section R337.6
California Residential Code (Title 24, Part 2.5) · 2022 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
VENTS R337.6.1 General. Where provided, ventilation openings for enclosed attics, gable ends, ridge ends, under eaves and cornices, enclosed eave soffit spaces, enclosed rafter spaces formed where ceilings are applied directly to the underside of roof rafters, underfloor ventilation, founda- tions and crawl spaces, or any other opening intended to permit ventilation, either in a horizontal or vertical plane, shall be in accordance with Section 1202 of the California Building Code and Sections R337.6.1 through R337.6.2 to resist building ignition from the intrusion of burning embers and flame through the ventilation open- ings.
R337.6.2 Requirements. Ventilation openings shall be fully covered with Wildfire Flame and Ember Resistant vents approved and listed by the California State Fire Marshal, or WUI vents tested to ASTM E2886 and listed, by complying with all of the following requirements:
1. There shall be no flaming ignition of the cotton material during the Ember Intrusion Test.
2. There shall be no flaming ignition during the Integ- rity Test portion of the Flame Intrusion Test.
3. The maximum temperature of the unexposed side of the vent shall not exceed 662°F (350°C).
R337.6.2.1 Off ridge and ridge vents. Vents that are installed on a sloped roof, such as dormer vents, shall comply with all the following:
1. Vents shall be covered with a mesh where the dimensions of the mesh therein shall be a mini- mum of 1 /16 inch (1.6 mm) and shall not exceed 1 /8 inch (3.2 mm) in diameter.
2. The mesh material shall be noncombustible.
3. The mesh material shall be corrosion resistant.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Residential Code (Title 24, Part 2.5)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix AF — RADON CONTROL
- Appendix AI — PRIVATE SEWAGE
- Appendix AJ — EXISTING
- Appendix AK — SOUND
- Appendix AO — AUTOMATIC
- Appendix AR — LIGHT STRAW-CLAY
- Appendix AS — STRAWBALE
- Appendix AU — COB CONSTRUCTION
- Appendix AV — BOARD
- Appendix AW — 3D-PRINTED BUILDING
- Chapter 1 — SCOPE AND APPLICATION
▸Chapter 3 — BUILDING PLANNING
Overview- Section R300
- Section R301
- Section R302
- Section R303
- Section R304
- Section R305
- Section R307
- Section R308
- Section R306
- Section R309
- Section R310
- Section R311
- Section R312
- Section R313
- Section R314
- Section R315
- Section R316
- Section R317
- Section R318
- Section R319
- Section R320
- Section R321
- Section R322
- Section R323
- Section R324
- Section R325
- Section R327
- Section R326
- Section R328
- Section R329
- Section R330
- Section R334
- Section R335
- Section R336
- Section R337
- Section R337.1
- Section R337.2
- Section R337.3
- Section R337.4
- Section R337.5
- Section R337.6
- Section R337.7
- Section R337.8
- Section R337.9
- Section R337.10
- Section R338
- Section R340
- Chapter 4 — FOUNDATIONS
- Chapter 5 — FLOORS
- Chapter 6 — WALL CONSTRUCTION
- Chapter 7 — WALL COVERING
- Chapter 8 — ROOF-CEILING CONSTRUCTION
- Chapter 9 — ROOF ASSEMBLIES
- Chapter 10 — CHIMNEYS AND FIREPLACES
- Chapter 44 — REFERENCED STANDARDS
- Appendix AH — PATIO COVERS
- Appendix AL — PERMIT FEES
- Appendix AQ — TINY HOUSES
- Appendix AT — SOLAR-READY PROVISIONS—DETACHED ONE- AND
- Appendix AX — SWIMMING POOL SAFETY ACT
- Appendix AY — AREAS PROTECTED BY THE FACILITIES
- Appendix AZ — EMERGENCY HOUSING