Chapter 3 — BUILDING PLANNING
California Residential Code (Title 24, Part 2.5) · 2022 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Sections in this part
- Section R300
- Section R301
- Section R302
- Section R303
- Section R304
- Section R305
- Section R307
- Section R308
- Section R306
- Section R309
- Section R310
- Section R311
- Section R312
- Section R313
- Section R314
- Section R315
- Section R316
- Section R317
- Section R318
- Section R319
- Section R320
- Section R321
- Section R322
- Section R323
- Section R324
- Section R325
- Section R327
- Section R326
- Section R328
- Section R329
- Section R330
- Section R334
- Section R335
- Section R336
- Section R337
- Section R337.1
- Section R337.2
- Section R337.3
- Section R337.4
- Section R337.5
- Section R337.6
- Section R337.7
- Section R337.8
- Section R337.9
- Section R337.10
- Section R338
- Section R340
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user.
See Chapter 1 for state agency authority and building applications.)
| Adopting agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting agency | BSC | BSC- CG |
SFM | 1 | 2 | 1/AC | AC | SS | SS/ CC |
1 | 1R | 2 | 3 | 4 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
| Adopt entire chapter | |||||||||||||||||||||||
| Adopt entire chapter as amended (amended sections listed below) |
X | ||||||||||||||||||||||
| Adopt only those sections that are listed below |
X | ||||||||||||||||||||||
| Chapter / Section | |||||||||||||||||||||||
| R300 | X | ||||||||||||||||||||||
| R300.1 | X | ||||||||||||||||||||||
| R300.2 | X | ||||||||||||||||||||||
| R301.1 | X | ||||||||||||||||||||||
| R301.1.1.1 | X | ||||||||||||||||||||||
| R301.1.3.1 | X | ||||||||||||||||||||||
| R301.1.3.2 | X | ||||||||||||||||||||||
| R301.1.3.3 | X | ||||||||||||||||||||||
| R301.2.2.1.1 | |||||||||||||||||||||||
| R301.2.2.1.2 | |||||||||||||||||||||||
| R301.2.2.10 | X | ||||||||||||||||||||||
| Table 301.5 | X | ||||||||||||||||||||||
| R302.1 - R302.14 | X | ||||||||||||||||||||||
| R302.1 | X | X | |||||||||||||||||||||
| Table 302.1(2) | X | ||||||||||||||||||||||
| R302.2.2 | X | ||||||||||||||||||||||
| R302.2.6 | X | X | |||||||||||||||||||||
| R302.3 | X | X | |||||||||||||||||||||
| R302.6 | X | ||||||||||||||||||||||
| R302.13 | X | ||||||||||||||||||||||
| R303.1 | X | ||||||||||||||||||||||
| R303.3 | X | ||||||||||||||||||||||
| R303.3.1 | X | ||||||||||||||||||||||
| R303.4 | X | ||||||||||||||||||||||
| R303.5.1 | X | ||||||||||||||||||||||
| R303.7 - R308.1 | X | ||||||||||||||||||||||
| R303.9.1.1 | X | ||||||||||||||||||||||
| R303.10 | X | ||||||||||||||||||||||
| R304.2 | X | ||||||||||||||||||||||
| R307.1 | X | ||||||||||||||||||||||
| Figure R307.1 | † | ||||||||||||||||||||||
| R308.3 - R308.4 | X | ||||||||||||||||||||||
| R309.4 | X | ||||||||||||||||||||||
| R309.5 | X | ||||||||||||||||||||||
| R309.6 | X | ||||||||||||||||||||||
| R309.7 | X | ||||||||||||||||||||||
| R309.8 | X | ||||||||||||||||||||||
| R310 | X |
(continued)
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
CALIFORNIA RESIDENTIAL CODE – MATRIX ADOPTION TABLE
CHAPTER 3 – BUILDING PLANNING—continued
| Adopting agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting agency | BSC | BSC- CG |
SFM | 1 | 2 | 1/AC | AC | SS | SS/ CC |
1 | 1R | 2 | 3 | 4 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
| Adopt Entire Chapter | |||||||||||||||||||||||
| Adopt Entire Chapter as amended (amended sections listed below) |
X | ||||||||||||||||||||||
| Adopt only those sections that are listed below |
X | ||||||||||||||||||||||
| Chapter / Section | |||||||||||||||||||||||
| R311 - R311.8.3.3 | X | ||||||||||||||||||||||
| R312 - R312.2.2 | X | ||||||||||||||||||||||
| R312.1.2 | X | ||||||||||||||||||||||
| R313.1 -R313.3.8.2 | X | X | |||||||||||||||||||||
| R314 - R314.8.3 | X | ||||||||||||||||||||||
| R315.1.1 | X | ||||||||||||||||||||||
| R315.2 | X | ||||||||||||||||||||||
| R315.2.1 | X | ||||||||||||||||||||||
| R315.2.2 | X | ||||||||||||||||||||||
| R315.3 | X | ||||||||||||||||||||||
| R315.4 | X | ||||||||||||||||||||||
| R315.5 | X | ||||||||||||||||||||||
| R315.6 | X | ||||||||||||||||||||||
| R315.7.2 | X | ||||||||||||||||||||||
| R315.7.4 | X | ||||||||||||||||||||||
| R316 | X | ||||||||||||||||||||||
| R316.2.1 | X | ||||||||||||||||||||||
| R316.3_Exception 2_ | X | ||||||||||||||||||||||
| R317.1 | X | ||||||||||||||||||||||
| R317.1.6 | X | ||||||||||||||||||||||
| R319 | X | ||||||||||||||||||||||
| R320.1 | X | ||||||||||||||||||||||
| R320.1.1 | † | ||||||||||||||||||||||
| R320.2 | X | ||||||||||||||||||||||
| R321 | X | ||||||||||||||||||||||
| R321.3 | X | ||||||||||||||||||||||
| R322.1.6 | X | ||||||||||||||||||||||
| R322.1.7 | X |
||||||||||||||||||||||
| R322.1.9 | † | ||||||||||||||||||||||
| R324 | X | ||||||||||||||||||||||
| R324.2 | X | ||||||||||||||||||||||
| R324.3 | X | ||||||||||||||||||||||
| R324.6 | X | ||||||||||||||||||||||
| R324.6.2.1 | X | X | |||||||||||||||||||||
| R324.6.3 | X | ||||||||||||||||||||||
| R324.7.1 | X | ||||||||||||||||||||||
| R324.8 – R324.8.2 | X | ||||||||||||||||||||||
| R325.3 | X |
(continued)
3-2 2022 CALIFORNIA RESIDENTIAL CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
CALIFORNIA RESIDENTIAL CODE – MATRIX ADOPTION TABLE
CHAPTER 3 – BUILDING PLANNING—continued
| Adopting agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting agency | BSC | BSC- CG |
SFM | 1 | 2 | 1/AC | AC | SS | SS/ CC |
1 | 1R | 2 | 3 | 4 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
| Adopt Entire Chapter | |||||||||||||||||||||||
| Adopt Entire Chapter as amended (amended sections listed below) |
X | ||||||||||||||||||||||
| Adopt only those sections that are listed below |
X | ||||||||||||||||||||||
| Chapter / Section | |||||||||||||||||||||||
| R326 | X | ||||||||||||||||||||||
| R326.3 | X | ||||||||||||||||||||||
| R327 through R327.1.4 | X | ||||||||||||||||||||||
| 328.1 – 328.12 | X | ||||||||||||||||||||||
| R328.1 | X | ||||||||||||||||||||||
| R328.6 | X | ||||||||||||||||||||||
| R328.9 | X | ||||||||||||||||||||||
| R328.10 | X | ||||||||||||||||||||||
| R329.2 | X | ||||||||||||||||||||||
| R334 | X | ||||||||||||||||||||||
| R334.1 | X | ||||||||||||||||||||||
| R335 - R335.9 | X | ||||||||||||||||||||||
| R336 - R336.8 | X | ||||||||||||||||||||||
| R337.1.1 | X | ||||||||||||||||||||||
| R337 - R337.10.4 | X | ||||||||||||||||||||||
| R337.5.1_ -_R337.5.2 | X | ||||||||||||||||||||||
| R337.6.2_ -_R337.6.3 | X | ||||||||||||||||||||||
| R337.9.1.1 | X | ||||||||||||||||||||||
| R337.9.3 | X | ||||||||||||||||||||||
| R338 - R338.4 | X | ||||||||||||||||||||||
| R340 | X | ||||||||||||||||||||||
| R340.1 | X |
The state agency does not adopt sections identified with the following symbol: † The - designation indicates that the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures subject to HCD 1.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
3-4 2022 CALIFORNIA RESIDENTIAL CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
Part III—Building Planning and Construction
CHAPTER 3
BUILDING PLANNING
User note:
About this chapter: Chapter 3 contains a wide array of building planning requirements that are critical to designing a safe and usable build- ing. This includes, but is not limited to, requirements related to general structural design, fire-resistant construction, light, ventilation, sanitation, plumbing fixture clearances, minimum room area and ceiling height, safety glazing, means of egress, automatic fire sprinkler systems, smoke and carbon monoxide alarm systems, accessibility, solar energy systems, swimming pools, spas and hot tubs.
R306.1 Toilet facilities.¶
Every dwelling unit shall be provided with a water closet, lavatory, and a bathtub or shower.
R306.2 Kitchen.¶
Each dwelling unit shall be provided with a kitchen area and every kitchen area shall be provided with a sink.
R306.3 Sewage disposal.¶
Plumbing fixtures shall be connected to a sanitary sewer or to an approved private sewage disposal system.
R306.4 Water supply to fixtures.¶
Plumbing fixtures shall be connected to an approved water supply. Kitchen sinks, lavatories, bathtubs, showers, bidets, laundry tubs and washing machine outlets shall be provided with hot and cold water.
R308.2 Louvered windows or jalousies.¶
Regular, float, wired or patterned glass in jalousies and louvered windows shall be not less than nominal 3 /16 inch (5 mm) thick and not more than 48 inches (1219 mm) in length. Exposed glass edges shall be smooth.
R308.2.1 Wired glass prohibited. Wired glass with wire exposed on longitudinal edges shall not be used in jalousies or louvered windows.
R308.3 Human impact loads.¶
Individual glazed areas, including glass mirrors in hazardous locations such as those indicated as defined in Section R308.4, shall pass the test requirements of Section R308.3.1.
Exceptions:
Louvered windows and jalousies shall comply with Section R308.2.
Mirrors and other glass panels mounted or hung on a surface that provides a continuous backing support.
Glass unit masonry complying with Section R607.
R308.3.1 Impact test. Where required by other sections of the code, glazing shall be tested in accordance with CPSC 16 CFR 1201. Glazing shall comply with the test criteria for Category II unless otherwise indicated in Table R308.3.1(1).
Exception: Glazing not in doors or enclosures for hot tubs, whirlpools, saunas, steam rooms, bathtubs and showers shall be permitted to be tested in accordance with ANSI Z97.1. Glazing shall comply with the test criteria for Class A unless otherwise indicated in Table R308.3.1(2).
R308.4 Hazardous locations.¶
The locations specified in Sections R308.4.1 through R308.4.7 shall be considered to be specific hazardous locations for the purposes of glazing.
BUILDING PLANNING
R308.4.1 Glazing in doors. Glazing in fixed and operable panels of swinging, sliding and bifold doors shall be considered to be a hazardous location.
Exceptions:
Glazed openings of a size through which a 3inch-diameter (76 mm) sphere is unable to pass.
Decorative glazing.
R308.4.2 Glazing adjacent to doors. Glazing in an individual fixed or operable panel adjacent to a door shall be considered to be a hazardous location where the bottom exposed edge of the glazing is less than 60 inches (1524 mm) above the floor or walking surface and it meets either of the following conditions:
Where the glazing is within 24 inches (610 mm) of either side of the door in the plane of the door in a closed position.
Where the glazing is on a wall less than 180 degrees (3.14 rad) from the plane of the door in a closed position and within 24 inches (610 mm) of the hinge side of an in-swinging door.
Exceptions:
Decorative glazing.
Where there is an intervening wall or other permanent barrier between the door and the glazing.
Where access through the door is to a closet or storage area 3 feet (914 mm) or less in depth. Glazing in this application shall comply with Section R308.4.3.
Glazing that is adjacent to the fixed panel of patio doors.
TABLE R308.3.1(1) MINIMUM CATEGORY CLASSIFICATION OF GLAZING USING CPSC 16 CFR 1201
| EXPOSED SURFACE AREA OF ONE SIDE OF ONE LITE |
GLAZING IN STORM OR COMBINATION DOORS (Category Class) |
GLAZING INDOORS (Category Class) |
GLAZED PANELS REGULATED BY SECTION R308.4.3 (Category Class) |
GLAZED PANELS REGULATED BY SECTION R308.4.2 (Category Class) |
GLAZING INDOORS AND ENCLOSURES REGULATED BY SECTION 308.4.5 (Category Class) |
SLIDING GLASS DOORS PATIO TYPE (Category Class) |
|---|---|---|---|---|---|---|
| 9 square feet or less | I | I | NR | I | II | II |
| More than 9 square feet | II | II | II | II | II | II |
For SI: 1 square foot = 0.0929 m 2 . NR = No Requirement.
TABLE R308.3.1(2) MINIMUM CATEGORY CLASSIFICATION OF GLAZING USING ANSI Z97.1
| EXPOSED SURFACE AREA OF ONE SIDE OF ONE LITE |
GLAZED PANELS REGULATED BY SECTION R308.4.3 (Category Class) |
GLAZED PANELS REGULATED BY SECTION R308.4.2 (Category Class) |
DOORS AND ENCLOSURES REGULATED BY SECTION R308.4.5a (Category Class) |
|---|---|---|---|
| 9 square feet or less | No requirement | B | A |
| More than 9 square feet | A | A | A |
For SI: 1 square foot = 0.0929 m 2 . a. Use is permitted only by the exception to Section R308.3.1.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
BUILDING PLANNING
R308.4.3 Glazing in windows. Glazing in an individual fixed or operable panel that meets all of the following conditions shall be considered to be a hazardous location:
The exposed area of an individual pane is larger than 9 square feet (0.836 m 2 ).
The bottom edge of the glazing is less than 18 inches (457 mm) above the floor.
The top edge of the glazing is more than 36 inches (914 mm) above the floor.
One or more walking surfaces are within 36 inches (914 mm), measured horizontally and in a straight line, of the glazing.
Exceptions:
Decorative glazing.
Where glazing is adjacent to a walking surface and a horizontal rail is installed 34 to 38 inches (864 to 965 mm) above the walking surface. The rail shall be capable of withstanding a horizontal load of 50 pounds per linear foot (730 N/m) without contacting the glass and have a cross-sectional height of not less than 1 1 /2 inches (38 mm).
Outboard panes in insulating glass units and other multiple glazed panels where the bottom edge of the glass is 25 feet (7620 mm) or more above grade, a roof, walking surfaces or other horizontal [within 45 degrees (0.79 rad) of horizontal] surface adjacent to the glass exterior.
R308.4.4 Glazing in guards and railings. Glazing in guards and railings, including structural baluster panels and nonstructural in-fill panels, regardless of area or height above a walking surface shall be considered to be a hazardous location.
R308.4.4.1 Structural glass baluster panels. Guards with structural glass baluster panels shall be installed with an attached top rail or handrail. The top rail or handrail shall be supported by not less than three glass baluster panels, or shall be otherwise supported to remain in place should one glass baluster panel fail.
Exception: An attached top rail or handrail is not required where the glass baluster panels are laminated glass with two or more glass plies of equal thickness and of the same glass type.
R308.4.5 Glazing and wet surfaces. Glazing in walls, enclosures or fences containing or adjacent to hot tubs, spas, whirlpools, saunas, steam rooms, bathtubs, showers and indoor or outdoor swimming pools where the bottom exposed edge of the glazing is less than 60 inches (1524 mm) measured vertically above any standing or walking surface shall be considered to be a hazardous location. This shall apply to single glazing and each pane in multiple glazing.
Exception: Glazing that is more than 60 inches (1524 mm), measured horizontally, from the water’s edge of a bathtub, hot tub, spa, whirlpool or swimming pool or from the edge of a shower, sauna or steam room.
R308.4.6 Glazing adjacent to stairs and ramps. Glazing where the bottom exposed edge of the glazing is less than 36 inches (914 mm) above the plane of the adjacent walking surface of stairways, landings between flights of stairs and ramps shall be considered to be a hazardous location.
Exceptions:
Where glazing is adjacent to a walking surface and a horizontal rail is installed at 34 to 38 inches (864 to 965 mm) above the walking surface. The rail shall be capable of withstanding a horizontal load of 50 pounds per linear foot (730 N/m) without contacting the glass and have a cross-sectional height of not less than 1 1 /2 inches (38 mm).
Glazing 36 inches (914 mm) or more measured horizontally from the walking surface.
R308.4.7 Glazing adjacent to the bottom stair landing. Glazing adjacent to the landing at the bottom of a stairway where the glazing is less than 36 inches (914 mm) above the landing and within a 60-inch (1524 mm) horizontal arc less than 180 degrees (3.14 rad) from the bottom tread nosing shall be considered to be a hazardous location. (See Figure R308.4.7.)
Exception: Where the glazing is protected by a guard complying with Section R312 and the plane of the glass is more than 18 inches (457 mm) from the guard.
R308.5 Site-built windows.¶
Site-built windows shall comply with Section 2404 of the California Building Code.
R308.6 Skylights and sloped glazing.¶
Skylights and sloped glazing shall comply with the following sections.
R308.6.1 Definitions. The following terms are defined in Chapter 2:
SKYLIGHT, UNIT. SKYLIGHTS AND SLOPED GLAZING. TUBULAR DAYLIGHTING DEVICE (TDD).
R308.6.2 Materials. Glazing materials shall be limited to the following:
Laminated glass with not less than a 0.015-inch (0.38 mm) polyvinyl butyral interlayer for glass panes 16 square feet (1.5 m 2 ) or less in area located such that the highest point of the glass is not more than 12 feet (3658 mm) above a walking surface; for higher or larger sizes, the interlayer thickness shall be not less than 0.030 inch (0.76 mm).
Fully tempered glass.
Heat-strengthened glass.
Wired glass.
Approved rigid plastics.
R308.6.3 Screens, general. For fully tempered or heatstrengthened glass, a broken glass retention screen meeting the requirements of Section R308.6.7 shall be installed below the full area of the glass, except for fully tempered glass that meets Condition 1 or 2 listed in Section R308.6.5.
3-48 2022 CALIFORNIA RESIDENTIAL CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
BUILDING PLANNING
For SI: 1 inch = 25.4 mm.
FIGURE R308.4.7 HAZARDOUS GLAZING LOCATIONS AT BOTTOM STAIR LANDINGS
R308.6.4 Screens with multiple glazing. Where the inboard pane is fully tempered, heat-strengthened or wired glass, a broken glass retention screen meeting the requirements of Section R308.6.7 shall be installed below the full area of the glass, except for Condition 1 or 2 listed in Section R308.6.5. Other panes in the multiple glazing shall be of any type listed in Section R308.6.2.
R308.6.5 Screens not required. Screens shall not be required where laminated glass complying with Item 1 of Section R308.6.2 is used as single glazing or the inboard pane in multiple glazing. Screens shall not be required where fully tempered glass is used as single glazing or the inboard pane in multiple glazing and either of the following conditions is met:
The glass area is 16 square feet (1.49 m 2 ) or less; the highest point of glass is not more than 12 feet (3658 mm) above a walking surface; the nominal glass thickness is not more than 3 /16 inch (4.8 mm); and for multiple glazing only the other pane or panes are fully tempered, laminated or wired glass.
The glass area is greater than 16 square feet (1.49 m 2 ); the glass is sloped 30 degrees (0.52 rad) or less from vertical; and the highest point of glass is not more than 10 feet (3048 mm) above a walking surface.
R308.6.6 Glass in greenhouses. Any glazing material is permitted to be installed without screening in the sloped areas of greenhouses, provided that the greenhouse height at the ridge does not exceed 20 feet (6096 mm) above grade.
R308.6.7 Screen characteristics. The screen and its fastenings shall: be capable of supporting twice the weight
of the glazing; be firmly and substantially fastened to the framing members; be installed within 4 inches (102 mm) of the glass; and have a mesh opening of not greater than 1 inch by 1 inch (25 mm by 25 mm).
R308.6.8 Curbs for skylights. Unit skylights installed in a roof with a pitch of less than three units vertical in 12 units horizontal (25-percent slope) shall be mounted on a curb extending not less than 4 inches (102 mm) above the plane of the roof, unless otherwise specified in the manufacturer’s installation instructions.
R308.6.9 Testing and labeling. Unit skylights and tubular daylighting devices shall be tested by an approved independent laboratory, and bear a label identifying manufacturer, performance grade rating and approved inspection agency to indicate compliance with the requirements of AAMA/WDMA/CSA 101/I.S.2/A440.
R308.6.9.1 Comparative analysis for glass-glazed unit skylights. Structural wind load design pressures for glass-glazed unit skylights different than the size tested in accordance with Section R308.6.9 shall be permitted to be different than the design value of the tested unit where determined in accordance with one of the following comparative analysis methods:
- Structural wind load design pressures for glassglazed unit skylights smaller than the size tested in accordance with Section R308.6.9 shall be permitted to be higher than the design value of the tested unit provided that such higher pressures are determined by accepted engineering analysis. Components of the smaller unit shall be the same as those of the tested unit. Such calculated design pressures shall be validated by an additional test
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
BUILDING PLANNING
of the glass-glazed unit skylight having the highest allowable design pressure.
- In accordance with WDMA I.S.11.
R317.2 Quality mark.¶
Lumber and plywood required to be pressure-preservative treated in accordance with Section R317.1 shall bear the quality mark of an approved inspection agency that maintains continuing supervision, testing and inspection over the quality of the product and that has been approved by an accreditation body that complies with the requirements of the American Lumber Standard Committee treated wood program.
R317.2.1 Required information. The required quality mark on each piece of pressure-preservative-treated lumber or plywood shall contain the following information:
Identification of the treating plant.
Type of preservative.
The minimum preservative retention.
End use for which the product was treated.
Standard to which the product was treated.
Identity of the approved inspection agency.
The designation “Dry,” if applicable.
Exception: Quality marks on lumber less than 1 inch (25 mm) nominal thickness, or lumber less than nominal 1 inch by 5 inches (25 mm by 127 mm) or 2 inches by 4 inches (51 mm by 102 mm) or lumber 36 inches (914 mm) or less in length shall be applied by stamping the faces of exterior pieces or by end labeling not less than 25 percent of the pieces of a bundled unit.
R317.3 Fasteners and connectors in contact with preser-¶
vative-treated and fire-retardant-treated wood. Fasteners, including nuts and washers, and connectors in contact with preservative-treated wood and fire-retardanttreated wood shall be in accordance with this section. The coating weights for zinc-coated fasteners shall be in accordance with ASTM A153. Stainless steel driven fasteners shall be in accordance with the material requirements of ASTM F1667.
R317.3.1 Fasteners for preservative-treated wood. Fasteners, including nuts and washers, for preservativetreated wood shall be of hot-dipped, zinc-coated galvanized steel, stainless steel, silicon bronze or copper. Staples shall be of stainless steel. Coating types and weights for connectors in contact with preservative-treated
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
BUILDING PLANNING
Naturally durable termite-resistant wood.
Physical barriers in accordance with Section R318.3 and used in locations as specified in Section R317.1.
Cold-formed steel framing in accordance with Sections R505.2.1 and R603.2.1.
R318.1.1 Quality mark. Lumber and plywood required to be pressure-preservative treated in accordance with Section R318.1 shall bear the quality mark of an approved inspection agency that maintains continuing supervision, testing and inspection over the quality of the product and that has been approved by an accreditation body that complies with the requirements of the American Lumber Standard Committee treated wood program.
R318.1.2 Field treatment. Field-cut ends, notches and drilled holes of pressure-preservative-treated wood shall be retreated in the field in accordance with AWPA M4.
R318.2 Chemical termiticide treatment.¶
Chemical termiticide treatment shall include soil treatment or field-applied wood treatment. The concentration, rate of application and method of treatment of the chemical termiticide shall be in strict accordance with the termiticide label.
R318.3 Barriers.¶
Approved physical barriers, such as metal or plastic sheeting or collars specifically designed for termite prevention, shall be installed in a manner to prevent termites from entering the structure. Shields placed on top of an exterior foundation wall shall be used only if in combination with another method of protection.
R318.4 Foam plastic protection.¶
In areas where the probability of termite infestation is “very heavy” as indicated in Figure R318.4, extruded and expanded polystyrene, polyisocyanurate and other foam plastics shall not be installed on the exterior face or under interior or exterior foundation walls or slab foundations located below grade. The clearance between foam plastics installed above grade and exposed earth shall be not less than 6 inches (152 mm).
Exceptions:
Buildings where the structural members of walls, floors, ceilings and roofs are entirely of noncombustible materials or pressure-preservative-treated wood.
Where in addition to the requirements of Section R318.1, an approved method of protecting the foam plastic and structure from subterranean termite damage is used.
On the interior side of basement walls.
R326.4 Means of egress.¶
The means of egress for habitable attics shall comply with the applicable provisions of Section R311.
R325.4 Means of egress.¶
The means of egress for mezzanines shall comply with the applicable provisions of Section R311.
R325.5 Openness.¶
Mezzanines shall be open and unobstructed to the room in which they are located except for walls not more than 36 inches (914 mm) in height, columns and posts.
Exceptions:
Mezzanines or portions thereof are not required to be open to the room in which they are located, provided that the aggregate floor area of the enclosed space is not greater than 10 percent of the mezzanine area.
In buildings that are not more than two stories above grade plane and equipped throughout with an automatic sprinkler system in accordance with Section R313, a mezzanine shall not be required to be open to the room in which the mezzanine is located.
R336.3 Smoke alarms.¶
Large family day-care homes shall be equipped with State Fire Marshal approved and listed single station residential type smoke alarms. The number and place- ment of smoke alarms shall be determined by the enforcement authority.
R336.4 Fire extinguishers.¶
Large and small family day-care homes shall be equipped with a portable fire extinguisher having a minimum 2A10BC rating.
R336.5 Fire alarm devices.¶
Every large family day-care home shall be provided with at least one manual device at a location approved by the authority having jurisdiction. Such device shall actuate a fire alarm signal, which shall be audi- ble throughout the facility at a minimum level of 15 db above ambient noise level. These devices need not be interconnected to any other fire alarm device, have a control panel or be electrically supervised or provided with emergency power. Such device or devices shall be attached to the structure and may be of any type acceptable to the enforcing agent, pro- vided that such devices are distinctive in tone and are audible throughout the structure.
R336.6 Compliance.¶
Every large family day-care home shall comply with the provisions for Group R-3 occupancies and, if appropriate, Section R336.1. For the purposes of Section R336.1, the first story shall be designated as the floor used for residential occupancy nearest to the street level which provides primary access to the building.
R336.7 Special hazards.¶
Every unenclosed gas-fired water heater or furnace which is within the area used for child care in a large family day-care home shall be protected in such a way as to prevent children from making contact with those appliances.
Exception: This does not apply to kitchen stoves or ovens.
R336.8 Exiting.¶
Every story or basement of a large family day-care home shall be provided with two exits which are remotely located from each other. Every required exit shall be of a size to permit the installation of a door not less than 32 inches (813mm) in clear width and not less than 6 feet 8 inches (2032 mm) in height. A manually operated horizontal sliding door may be used as one of the two required exits.
Where basements are used for day-care purposes, one of the two required exits shall provide access directly to the exterior without entering the first story. The second exit from the basement may either pass through the story above or exit directly to the exterior.
Rooms used for day-care purposes shall not be located above the first story.
Exception: Buildings equipped with an automatic sprin- kler system throughout and which have at least one of the required exits providing access directly to the exterior. NFPA 13R may be used in large family day-care homes. The sprinkler omissions of NFPA 13R shall not apply unless approved by the enforcing agency.
3-96 2022 CALIFORNIA RESIDENTIAL CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
Area shall comply with all sections of this chapter, including all of the following areas:
1. All unincorporated lands designated by the State Board of Forestry and Fire Protection as State Responsibility Area (SRA) including:
1.1. Moderate Fire Hazard Severity Zones 1.2. High Fire Hazard Severity Zones 1.3. Very-High Fire Hazard Severity Zones 2. Land designated as Very-High Fire Hazard Severity Zone by cities and other local agencies. 3. Land designated as Wildland Interface Fire Area by cities and other local agencies.
Exceptions: 1. New buildings located in any Fire Hazard Severity Zone within State Responsibility Areas, for which an application for a build- ing permit is submitted on or after January 1, 2008, shall comply with all sections of this chapter. 2. New buildings located in any Fire Hazard Severity Zone within State Responsibility Areas or any Wildland Interface Fire Area designated by cities and other local agen- cies for which an application for a building permit is submitted on or after December 1, 2005 but prior to July 1, 2008, shall only comply with the following sections of this chapter:
2.1. Section R337.5 – Roofing 2.2. Section R337.6 – Vents R337.1.4 Inspection and certification. Building permit applications and final completion approvals for buildings within the scope and application of this chapter shall com- ply with the following:
1. Building permit issuance. The local building official shall, prior to construction, provide the owner or applicant a certification that the building as pro- posed to be built complies with all applicable state and local building standards, including those for materials and construction methods for wildfire exposure as described in this chapter. Issuance of a building permit by the local building official for the proposed building shall be considered as complying with this section.
2. Building permit final. The local building official shall, upon completion of construction, provide the owner or applicant with a copy of the final inspec- tion report that demonstrates the building was con- structed in compliance with all applicable state and local building standards, including those for materi- als and construction methods for wildfire exposure as described in this chapter. Issuance of a certificate of occupancy by the local building official for the proposed building shall be considered as complying with this section.
BUILDING PLANNING
R337.1.5 Vegetation management compliance. Prior to building permit final approval, the property shall be in compliance with the vegetation management requirements prescribed in California Fire Code Section 4906 and 4907, including California Public Resources Code 4291 or California Government Code Section 51182. Accept- able methods of compliance inspection and documentation shall be determined by the enforcing agency and shall be permitted to include any of the following:
1. Local, state or federal fire authority or designee authorized to enforce vegetation management requirements.
2. Enforcing agency.
3. Third party inspection and certification authorized to enforce vegetation management requirements.
4. Property owner certification authorized by the enforcing agency.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Residential Code (Title 24, Part 2.5)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix AF — RADON CONTROL
- Appendix AI — PRIVATE SEWAGE
- Appendix AJ — EXISTING
- Appendix AK — SOUND
- Appendix AO — AUTOMATIC
- Appendix AR — LIGHT STRAW-CLAY
- Appendix AS — STRAWBALE
- Appendix AU — COB CONSTRUCTION
- Appendix AV — BOARD
- Appendix AW — 3D-PRINTED BUILDING
- Chapter 1 — SCOPE AND APPLICATION
▸Chapter 3 — BUILDING PLANNING
Overview- Section R300
- Section R301
- Section R302
- Section R303
- Section R304
- Section R305
- Section R307
- Section R308
- Section R306
- Section R309
- Section R310
- Section R311
- Section R312
- Section R313
- Section R314
- Section R315
- Section R316
- Section R317
- Section R318
- Section R319
- Section R320
- Section R321
- Section R322
- Section R323
- Section R324
- Section R325
- Section R327
- Section R326
- Section R328
- Section R329
- Section R330
- Section R334
- Section R335
- Section R336
- Section R337
- Section R337.1
- Section R337.2
- Section R337.3
- Section R337.4
- Section R337.5
- Section R337.6
- Section R337.7
- Section R337.8
- Section R337.9
- Section R337.10
- Section R338
- Section R340
- Chapter 4 — FOUNDATIONS
- Chapter 5 — FLOORS
- Chapter 6 — WALL CONSTRUCTION
- Chapter 7 — WALL COVERING
- Chapter 8 — ROOF-CEILING CONSTRUCTION
- Chapter 9 — ROOF ASSEMBLIES
- Chapter 10 — CHIMNEYS AND FIREPLACES
- Chapter 44 — REFERENCED STANDARDS
- Appendix AH — PATIO COVERS
- Appendix AL — PERMIT FEES
- Appendix AQ — TINY HOUSES
- Appendix AT — SOLAR-READY PROVISIONS—DETACHED ONE- AND
- Appendix AX — SWIMMING POOL SAFETY ACT
- Appendix AY — AREAS PROTECTED BY THE FACILITIES
- Appendix AZ — EMERGENCY HOUSING