Chapter 3 — BUILDING PLANNING

Section R313

California Residential Code (Title 24, Part 2.5) · 2022 edition · updated 2026-09-12 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

R313.1 Townhouse automatic fire sprinkler systems.

An automatic sprinkler system shall be installed in townhouses.

Exception: An automatic sprinkler system shall not be required where additions or alterations are made to existing townhouses that do not have an automatic sprinkler system installed. R313.1.1 Design and installation. Automatic sprinkler systems for townhouses shall be designed and installed in accordance with Section R313 or NFPA 13D.

R313.2 One- and two-family dwellings automatic sprin-kler systems.

kler systems. An automatic sprinkler system shall be installed in one- and two-family dwellings.

Exception s :

1. An automatic residential fire sprinkler system shall not be required for additions or alterations to existing buildings that are not already provided with an automatic residential sprinkler system. 2. Accessory Dwelling Unit, provided that all of the following are met:

2.1. The unit meets the definition of an Accessory Dwelling Unit as defined in the Government Code Section 65852.2. 2.2. The existing primary residence does not have automatic fire sprinklers. 2.3. The accessory detached dwelling unit does not exceed 1,200 square feet in size. 2.4. The unit is on the same lot as the primary residence.

R313.2.1 Design and installation. Automatic sprinkler systems shall be designed and installed in accordance with Section R313 or NFPA 13D.

3-56 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

HEAT SOURCE RANGE OF DISTANCE FROM HEAT
SOURCE WITHIN WHICH
INTERMEDIATE TEMPERATURE
SPRINKLERS ARE REQUIREDa, b
(inches)
Coal and wood burning stove
12 to 42
Fireplace, front of recessed
fireplace
36 to 60
Fireplace, side of open or
recessed fireplace
12 to 36
Front of wall-mounted warm-air
register
18 to 36
Heating duct, not insulated 9 to 18
Hot water pipe, not insulated
6 to 12
Kitchen range top
9 to 18
Luminaire up to 250 watts 3 to 6
Luminaire 250 watts up to 499
watts
6 to 12
Oven 9 to 18
Side of ceiling or wall warm-air
register
12 to 24
Vent connector or chimney
connector
9 to 18
Water heater, furnace or boiler 3 to 6

For SI: 1 inch = 25.4 mm. a. Sprinklers shall not be located at distances less than the minimum table

distance unless the sprinkler listing allows a lesser distance. b. Distances shall be measured in a straight line from the nearest edge of the

heat source to the nearest edge of the sprinkler.

BUILDING PLANNING

sources as required by the sprinkler manufacturer’s installation instructions.

R313.3.2.2 Intermediate temperature sprinklers. Sprinklers shall have an intermediate temperature rating not less than 175°F (79°C) and not more than 225°F (107°C) where installed in the following locations:

  1. Directly under skylights, where the sprinkler is exposed to direct sunlight.

  2. In attics.

  3. In concealed spaces located directly beneath a roof.

  4. Within the distance to a heat source as specified in Table R313.3.2.2.

R313.3.2.3 Freezing areas. Piping shall be protected from freezing as required by the California Plumbing Code or by using one of the following:

  1. A dry-pipe automatic sprinkler system that is listed for residential occupancy applications.

2 Dry-sidewall or dry-pendent sprinklers extending from a nonfreezing area into a freezing area.

3. Where fire sprinkler piping cannot be adequately protected against freezing, the system shall be designed and installed in accordance with NFPA 13D.

TABLE R313.3.2.2 LOCATIONS WHERE INTERMEDIATE TEMPERATURE SPRINKLERS ARE REQUIRED

R313.3 Dwelling unit fire sprinkler systems.

R313.3.1 General. The design and installation of residential fire sprinkler systems shall be in accordance with NFPA 13D or Section R313.3, which shall be considered equivalent to NFPA 13D. Partial residential sprinkler systems shall be permitted to be installed only in buildings not required to be equipped with a residential sprinkler system. Section R313.3 shall apply to stand-alone and multipurpose wet-pipe sprinkler systems that do not include the use of antifreeze. A multipurpose fire sprinkler system shall supply domestic water to both fire sprinklers and plumbing fixtures. A stand-alone sprinkler system shall be separate and independent from the water distribution system.

R313.3.1.1 Backflow protection.

A backflow preventer shall not be required to separate a sprinkler system from the water distribution system, provided that:

1. The system complies with NFPA 13D or Section R313;

2. Piping materials are suitable for potable water in accordance with the California Plumbing Code; and

3. The system does not contain antifreeze or have a fire department connection.

R313.3.1.2 Required sprinkler locations. Sprinklers shall be installed to protect all areas of a dwelling unit.

Exceptions:

  1. Attics, crawl spaces and normally unoccupied concealed spaces that do not contain fuel-fired appliances do not require sprinklers. In attics, crawl spaces and normally unoccupied concealed spaces that contain fuel-fired equipment, a sprinkler shall be installed above the equipment; however, sprinklers shall not be required in the remainder of the space.

  2. Clothes closets, linen closets and pantries not exceeding 24 square feet (2.2 m 2 ) in area, with the smallest dimension not greater than 3 feet (915 mm) and having wall and ceiling surfaces of gypsum board.

  3. Bathrooms not more than 55 square feet (5.1 m 2 ) in area.

  4. Detached garages; carports with no habitable space above; open attached porches; unheated entry areas, such as mud rooms, that are adjacent to an exterior door; and similar areas.

R313.3.2 Sprinklers.

Sprinklers shall be new listed residential sprinklers and shall be installed in accordance with the sprinkler manufacturer’s installation instructions.

R313.3.2.1 Temperature rating and separation from heat sources. Except as provided for in Section R313.3.2.2, sprinklers shall have a temperature rating of not less than 135°F (57°C) and not more than 225°F (107°C). Sprinklers shall be separated from heat

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

R313.3.2.4 Sprinkler coverage.

Sprinkler coverage requirements and sprinkler obstruction requirements shall be in accordance with Sections R313.3.2.4.1 and R313.3.2.4.2.

R313.3.2.4.1 Coverage area limit. The area of coverage of a single sprinkler shall not exceed 400 square feet (37 m 2 ) and shall be based on the sprinkler listing and the sprinkler manufacturer’s installation instructions.

R313.3.2.4.2 Obstructions to coverage. Sprinkler discharge shall not be blocked by obstructions unless additional sprinklers are installed to protect the obstructed area. Additional sprinklers shall not be required where the sprinkler separation from obstructions complies with either the minimum distance indicated in Figure R313.3.2.4.2 or the minimum distances specified in the sprinkler manufacturer’s instructions where the manufacturer’s instructions permit a lesser distance.

R313.3.2.4.2.1 Additional requirements for pendent sprinklers.

pendent sprinklers. Pendent sprinklers within 3 feet (915 mm) of the center of a ceiling fan, surface- mounted ceiling luminaire or similar object shall be considered to be obstructed, and additional sprinklers shall be installed.

R313.3.2.4.2.2 Additional requirements for sidewall sprinklers. Sidewall sprinklers within 5 feet (1524 mm) of the center of a ceiling fan, surface-mounted ceiling luminaire or similar object shall be considered to be obstructed, and additional sprinklers shall be installed.

R313.3.2.5 Sprinkler installation on systems assem-bled with solvent cement.

bled with solvent cement. The solvent cementing of threaded adapter fittings shall be completed and threaded adapters for sprinklers shall be verified as being clear of excess cement prior to the installation of sprinklers on systems assembled with solvent cement.

R313.3.2.6 Sprinkler modifications prohibited. Painting, caulking or modifying of sprinklers shall be prohibited. Sprinklers that have been painted, caulked, modified or damaged shall be replaced with new sprinklers.

R313.3.3 Sprinkler piping system.

Sprinkler piping shall be supported in accordance with the requirements for cold water distribution piping. Sprinkler piping shall comply with all requirements for cold water distribution piping. For multipurpose piping systems, the sprinkler piping shall connect to and be a part of the cold water distribution piping system.

Exception: For plastic piping, it shall be permissible to follow the manufacturer’s installation instructions.

R313.3.3.1 Nonmetallic pipe and tubing. Nonmetallic pipe and tubing, such as CPVC, PEX, and PE-RT shall be listed for use in residential fire sprinkler systems.

R313.3.3.1.1 Nonmetallic pipe protection.

Nonmetallic pipe and tubing systems shall be protected from exposure to the living space by a layer of not

less than 3 /8 inch (9.5 mm) thick gypsum wallboard, 1/2 inch thick plywood (13 mm), or other material having a 15-minute fire rating.

Exceptions:

  1. Pipe protection shall not be required in areas that do not require protection with sprinklers as specified in Section R313.3.1.2.

  2. Pipe protection shall not be required where exposed piping is permitted by the pipe listing.

R313.3.3.2 Shutoff valves prohibited.

With the exception of shutoff valves for the entire water distribution system or a single master control valve for the automatic sprinkler system that is locked in the open position, valves shall not be installed in any location where the valve would isolate piping serving one or more sprinklers.

R313.3.3.3 Single dwelling limit. Piping beyond the service valve located at the beginning of the water distribution system shall not serve more than one dwelling.

R313.3.3.4 Drain.

A means to drain the sprinkler system shall be provided on the system side of the water distribution shutoff valve.

R313.3.4 Determining system design flow. The flow for sizing the sprinkler piping system shall be based on Sections R313.3.4.1 and R313.3.4.2 .

R313.3.4.1 Determining required flow rate for each sprinkler. The minimum required flow for each sprinkler shall be determined using the sprinkler manufacturer’s published data for the specific sprinkler model based on all of the following:

  1. The area of coverage.

  2. The ceiling configuration, in accordance with Sections R313.3.4.1.1 through R313.3.4.1.3.

  3. The temperature rating.

  4. Any additional conditions specified by the sprinkler manufacturer.

R313.3.4.1.1 Ceiling configurations.

Manufacturer's published flow rates for sprinklers tested under a ceiling 8 feet (2438 mm) in height, in accordance with the sprinkler listing, shall be used for the following ceiling configurations, provided that the ceiling surface does not have significant irregularities, lumps or indentations and is continuous in a single plane.

  1. Ceilings that are horizontal or that have a slope not exceeding 8 units vertical in 12 units horizontal (67 percent), without beams, provided that the ceiling height, measured to the highest point, does not exceed 24 feet (7315 mm) above the floor. Where the slope exceeds 2 units vertical in 12 units horizontal (17 percent), the highest sprinkler installed along the sloped portion of a ceiling shall be positioned above all communicating openings connecting the sloped ceiling compartment with an adjacent space.

3-58 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

FIGURE R313.3.2.4.2 MINIMUM ALLOWABLE DISTANCE BETWEEN SPRINKLER AND OBSTRUCTION

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

  1. Ceilings that are horizontal or that have a slope not exceeding 8 units vertical in 12 units horizontal (67 percent), with beams, provided that the ceiling height, measured to the highest point, does not exceed 24 feet (7315 mm) above the floor. Beams shall not exceed 14 inches (350 mm) in depth, and pendent sprinklers shall be installed under the beams as described at the end of this section. The compartment containing the beamed ceiling shall not exceed 600 square feet (56 m 2 ) in area. Where the slope does not exceed 2 units vertical in 12 units horizontal (17 percent), the highest sprinkler in the compartment shall be above all communicating openings connecting the compartment with an adjacent space. Where the slope exceeds 2 units vertical in 12 units horizontal (17 percent), the highest sprinkler installed along the sloped portion of a ceiling shall be positioned above all communicating openings connecting the sloped ceiling compartment with an adjacent space.

the highest sprinkler in the compartment shall be above all communicating openings connecting the compartment with an adjacent space. Where the slope exceeds 2 units vertical in 12 units horizontal (17 percent), the highest sprinkler installed along the sloped portion of a ceiling shall be positioned above all communicating openings connecting the sloped ceiling compartment with an adjacent space.

  1. Ceilings that have a slope exceeding 2 units vertical in 12 units horizontal (17 percent) but not exceeding 8 units vertical in 12 units horizontal (67 percent), with beams of any depth, provided that the ceiling height, measured to the highest point, does not exceed 24 feet (7315 mm) above the floor. Sidewall or pendent sprinklers shall be installed in each pocket formed by beams. The compartment containing the sloped, beamed ceiling shall not exceed 600 square feet (56 m 2 ) in area.

Pendent, recessed pendent and flush-type pendent sprinklers installed directly under a beam having a maximum depth of 14 inches (356 mm) shall have the sprinkler deflector located not less than 1 inch (25 mm) or more than 2 inches (51 mm) below the bottom of the beam. Pendent sprinklers installed adjacent to the bottom of a beam having a maximum depth of 14 inches (356 mm) shall be positioned such that the vertical centerline of the sprinkler is not more than 2 inches (51 mm) from the edge of the beam, with the sprinkler deflector located not less than 1 inch (25 mm) or more than 2 inches (51 mm) below the bottom of the beam. Pendent sprinklers shall also be permitted to be installed less than 1 inch (25 mm) below the bottom of a beam where in accordance with manufacturer's instructions for installation of flush sprinklers.

R313.3.4.1.2 Ceiling configurations with special sprinkler listings.

sprinkler listings. For ceiling configurations not specified in Section R313.3.4.1.1, the manufacturer's published flow rate for sprinklers that have been listed for protection of such configurations shall be used.

R313.3.4.1.3 Other ceiling configurations. For ceiling configurations not addressed by Section

R313.3.4.1.1 or R313.3.4.1.2, the flow rate shall be subject to approval by the code official.

R313.3.4.2 System design flow rate. The design flow rate for the system shall be based on the following:

  1. The design flow rate for a room having only one sprinkler shall be the flow rate required for that sprinkler, as determined by Section R313.3.4.1.

  2. The design flow rate for a room having two or more sprinklers a shall be determined by identifying the sprinkler in that room with the highest required flow rate, based on Section R313.3.4.1, and multiplying that flow rate by 2.

  3. Where the sprinkler manufacturer specifies different criteria for ceiling configurations that are not smooth, flat and horizontal, the required flow rate for that room shall comply with the sprinkler manufacturer’s instructions.

  4. The design flow rate for the sprinkler system shall be the flow required by the room with the largest flow rate, based on Items 1, 2 and 3.

  5. For the purpose of this section, it shall be permissible to reduce the design flow rate for a room by subdividing the space into two or more rooms, where each room is evaluated separately with respect to the required design flow rate. Each room shall be bounded by walls and a ceiling. Openings in walls shall have a lintel not less than 8 inches (203 mm) in depth and each lintel shall form a solid barrier between the ceiling and the top of the opening.

R313.3.5 Water supply.

The water supply shall provide not less than the required design flow rate for sprinklers in accordance with Section R313.3.4.2 at a pressure not less than that used to comply with Section R313.3.6 . Where a water supply serves both domestic and fire sprinkler systems, 5 gpm (19 L/min) shall be added to the sprinkler system demand at the point where the systems are connected, to determine the size of common piping and the size of the total water supply requirements where no provision is made to prevent flow into the domestic water system upon operation of a sprinkler. For multi- purpose piping systems, the 5 gpm (19 L/min) demand shall be added at the domestic connection nearest the design area. This demand may be split between two domestic connections at 2.5 gpm (10 L/min) each.

R313.3.5.1 Water supply from individual sources.

Where a dwelling unit water supply is from a tank system, a private well system, a pump, or a combination of these, the available water supply shall be based on the minimum pressure control setting for the pump.

R313.3.5.2 Required capacity. The water supply shall have the capacity to provide the required design flow rate for sprinklers for a period of time as follows:

  1. Seven minutes for dwelling units one story in height and less than 2,000 square feet (186 m 2 ) in area. For the purpose of determining the area of the dwelling unit, the area of attached

3-60 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

garages and attached open carports, porches, balconies and patios shall not be included.

  1. Ten minutes for dwelling units two or more stories in height or equal to or greater than 2,000 square feet (186 m 2 ) in area. For the purpose of determining the area of the dwelling unit, the area of attached garages and attached open carports, porches, balconies and patios shall not be included.

R313.3.5.2.1

Where a well system, a water supply tank system, a pump, or a combination thereof, is used, the configuration for the system shall be one of the following:

1. The water supply shall serve both domestic and fire sprinkler systems. Any combination of well capacity and tank storage shall be permitted to meet the capacity requirement.

2. A stand-alone tank is permitted if the follow- ing conditions are met:

2.1. The pump shall be connected to a 220-volt circuit breaker shared with a common household appliance (e.g., range, oven, dryer),

2.2. The pump shall be a stainless steel 240-volt pump,

2.3. A valve shall be provided to exercise the pump. The discharge of the exercise valve shall be piped to the tank, and

2.4. A sign shall be provided stating “Valve must be opened monthly for 5 minutes.”

2.5. A means for automatically refilling the tank level so that the tank capacity will meet the required water supply duration in minutes shall be provided.

R313.3.5.3 Connections to automatic fire sprinkler systems.

systems. The potable water supply to automatic fire sprinkler shall be protected against backflow by a double check backflow prevention assembly, a double check fire protection backflow prevention assembly, a reduced pressure principle backflow prevention assembly or a reduced pressure principle fire protection backflow prevention assembly.

Exception: Where permitted by Section R313.3.1.1, backflow protection for the water supply system shall not be required.

R313.3.5.3.1 Additives or nonpotable source.

Where systems contain chemical additives or antifreeze, or where systems are connected to a nonpotable secondary water supply, the potable water supply shall be protected against backflow by a reduced pressure principle backflow prevention assembly or a reduced pressure principle fire protection backflow prevention assembly. Where chemical additives or antifreeze is added to only a portion of an automatic fire sprinkler or standpipe

BUILDING PLANNING

system, the reduced pressure principle fire protection backflow preventer shall be permitted to be located so as to isolate that portion of the system.

R313.3.6 Pipe sizing.

The piping to sprinklers shall be sized for the flow required by Section R313.3.4.2 . The flow required to supply the plumbing fixtures shall not be required to be added to the sprinkler design flow.

R313.3.6.1 Method of sizing pipe. Piping supplying sprinklers shall be sized using the prescriptive method in Section R313.3.6.2 or by hydraulic calculation in accordance with NFPA 13D. The minimum pipe size from the water supply source to any sprinkler shall be 3/4 inch (19 mm) nominal. Threaded adapter fittings at the point where sprinklers are attached to the piping shall be a minimum of 1 /2 inch (13 mm) nominal.

R313.3.6.2 Prescriptive pipe sizing method.

Pipe shall be sized by determining the available pressure to offset friction loss in piping and identifying a piping material, diameter and length using the equation in Section R313.3.6.2.1 and the procedure in Section R313.3.6.2.2 .

R313.3.6.2.1 Available pressure equation. The pressure available to offset friction loss in the interior piping system ( Pt ) shall be determined in accordance with the Equation 29-1.

Pt = Psup–PLsvc–PLm–PLd–PLe–Psp

(Equation 29-1)

where:

Pt = Pressure used in applying Tables R313.3.6.2(4)

through R313.3.6.2(9).

Psup = Pressure available from the water supply source.

PLsvc = Pressure loss in the water-service pipe.

PLm = Pressure loss in the water meter.

PLd = Pressure loss from devices other than the

water meter.

PLe = Pressure loss associated with changes in

elevation.

Psp = Maximum pressure required by a sprinkler.

R313.3.6.2.2 Calculation procedure.

Determination of the required size for water distribution piping shall be in accordance with the following procedure:

Step 1 – Determine Psup Obtain the static supply pressure that will be available from the water main from the water purveyor, or for an individual source, the available supply pressure shall be in accordance with Section R313.3.5.1.

Step 2 – Determine PLsvc Use Table R313.3.6.2(1) to determine the pressure loss in the water service pipe based on the selected size of the water service.

Step 3 – Determine PLm Use Table R313.3.6.2(2) to determine the pressure loss from the water meter, based on the selected water meter size.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

Step 4 – Determine PLd Determine the pressure loss from devices other than the water meter installed in the piping system supplying sprinklers, such as pressure-reducing valves, backflow preventers, water softeners or water filters. Device pressure losses shall be based on the device manufacturer’s specifications. The flow rate used to determine pressure loss shall be the rate from Section

R313.3.4.2

, except that 5 gpm (0.3 L/S) shall be added where the device is installed in a water-service pipe that supplies more than one dwelling. As alternative to deducting pressure loss for a device, an automatic bypass valve shall be installed to divert flow around the device when a sprinkler activates. Step 5 – Determine PLe Use Table R313.3.6.2(3) to determine the pressure loss associated with changes in elevation. The elevation used in applying the table shall be the difference between the elevation where the water source pressure was measured and the elevation of the highest sprinkler.

Step 6 – Determine Psp Determine the maximum pressure required by any individual sprinkler based on the flow rate from Sec

tion R313.3.4.1 . The required pressure is provided in the sprinkler manufacturer’s published data for the specific sprinkler model based on the selected flow rate.

Step 7 – Calculate Pt Using Equation 29-1, calculate the pressure available to offset friction loss in water-distribution piping between the service valve and the sprinklers.

Step 8 – Determine the maximum allowable pipe length

Use Tables R313.3.6.2(4) through R313.3.6.2(9) to select a material and size for water distribution piping. The piping material and size shall be acceptable if the developed length of pipe between the service valve and the most remote sprinkler does not exceed the maximum allowable length specified by the applicable table. Interpolation of Pt between the tabular values shall be permitted.

The maximum allowable length of piping in Tables R313.3.6.2(4) through R313.3.6.2(9) incorporates an adjustment for pipe fittings, and no additional consideration of friction losses associated with pipe fittings shall be required.

TABLE R313.3.6.2(1)

WATER SERVICE PRESSURE LOSS (PLsvc)a, b
FLOW
RATEc
(gpm)
3/4-INCH WATER SERVICE PRESSURE LOSS
(psi)
3/4-INCH WATER SERVICE PRESSURE LOSS
(psi)
3/4-INCH WATER SERVICE PRESSURE LOSS
(psi)
3/4-INCH WATER SERVICE PRESSURE LOSS
(psi)
1-INCH WATER SERVICE PRESSURE LOSS
(psi)
1-INCH WATER SERVICE PRESSURE LOSS
(psi)
1-INCH WATER SERVICE PRESSURE LOSS
(psi)
1-INCH WATER SERVICE PRESSURE LOSS
(psi)
11/4 -INCH WATER SERVICE PRESSURE LOSS
(psi)
11/4 -INCH WATER SERVICE PRESSURE LOSS
(psi)
11/4 -INCH WATER SERVICE PRESSURE LOSS
(psi)
11/4 -INCH WATER SERVICE PRESSURE LOSS
(psi)
FLOW
RATEc
(gpm)
Length of water service pipe (feet) Length of water service pipe (feet) Length of water service pipe (feet) Length of water service pipe (feet) Length of water service pipe (feet) Length of water service pipe (feet) Length of water service pipe (feet) Length of water service pipe (feet) Length of water service pipe (feet) Length of water service pipe (feet) Length of water service pipe (feet) Length of water service pipe (feet)
FLOW
RATEc
(gpm)
40 or less 41 to 75 76 to 100 101 to 150 40 or less 41 to 75 76 to 100 101 to 150 40 or less 41 to 75 76 to 100 101 to 150
8 5.1 8.7 11.8 17.4 1.5 2.5 3.4 5.1 0.6 1.0 1.3 1.9
10 7.7 13.1 17.8 26.3 2.3 3.8 5.2 7.7 0.8 1.4 2.0 2.9
12 10.8 18.4 24.9 NP 3.2 5.4 7.3 10.7 1.2 2.0 2.7 4.0
14 14.4 24.5 NP NP 4.2 7.1 9.6 14.3 1.6 2.7 3.6 5.4
16 18.4 NP NP NP 5.4 9.1 12.4 18.3 2.0 3.4 4.7 6.9
18 22.9 NP NP NP 6.7 11.4 15.4 22.7 2.5 4.3 5.8 8.6
20 27.8 NP NP NP 8.1 13.8 18.7 27.6 3.1 5.2 7.0 10.4
22 NP NP NP NP 9.7 16.5 22.3 NP 3.7 6.2 8.4 12.4
24 NP NP NP NP 11.4 19.3 26.2 NP 4.3 7.3 9.9 14.6
26 NP NP NP NP 13.2 22.4 NP NP 5.0 8.5 11.4 16.9
28 NP NP NP NP 15.1 25.7 NP NP 5.7 9.7 13.1 19.4
30 NP NP NP NP 17.2 NP NP NP 6.5 11.0 14.9 22.0
32 NP NP NP NP 19.4 NP NP NP 7.3 12.4 16.8 24.8
34 NP NP NP NP 21.7 NP NP NP 8.2 13.9 18.8 NP
36 NP NP NP NP 24.1 NP NP NP 9.1 15.4 20.9 NP

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.063 L/s, 1 pound per square inch = 6.895 kPa. NP—Not permitted. Pressure loss exceeds reasonable limits. a. Values are applicable for underground piping materials listed in the California Plumbing Code and are based on an SDR of 11 and a Hazen Williams C Factor

of 150. b. Values include the following length allowances for fittings: 25% length increase for actual lengths up to 100 feet and 15% length increase for actual lengths

over 100 feet. c. Flow rate from Section R313.3.4.2 . Add 5 gpm to the flow rate required by Section R313.3.4.2 where the water-service pipe supplies more than one dwelling.

3-62 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

TABLE R313.3.6.2(2)

MINIMUM WATER METER PRESSURE LOSS ( PLm ) a

FLOW RATE
(gallons per minute, gpm)b
5/-INCH METER PRESSURE LOSS
8
(pounds per square inch, psi)
3/-INCH METER PRESSURE LESS
4
(pounds per square inch, psi)
1-INCH METER PRESSURE LOSS
(pounds per square inch, psi)
8 3 3 1
10
3
3
1
12
4
3
1
14 6 5 1
16
7
6
1
18
9
7
2
20 11 9 2
23
14
11
3
26
18
14
3
31 26 22 4
39
38
35
6
52 NP NP 10

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.063 L/s. NP = Not permitted unless the actual water meter pressure loss is known. a. Table P2904.6.2(2) establishes conservative values for water meter pressure loss or installations where the water meter loss is unknown. Where the actual

water meter pressure loss is published and available from the meter manufacturer, PLm shall be the published pressure loss for the selected meter. b. Flow rate from Section P2904.4.2. Add 5 gpm to the flow rate required by Section P2904.4.2 where the water service pipe supplies more than one dwelling.

TABLE R313.3.6.2(3) ELEVATION LOSS ( PLe )

ELEVATION (feet) PRESSURE LOSS (psi)
5 2.2
10 4.4
15 6.5
20 8.7
25 10.9
30 13
35 15.2
40 17.4

For SI: 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

TABLE R313.3.6.2(4)

ALLOWABLE PIPE LENGTH FOR 3/4-INCH TYPE M COPPER WATER TUBING —
SPRINKLER
FLOW RATEa
(gpm)

WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSURE_Pt _(psi) AVAILABLE PRESSURE_Pt _(psi) AVAILABLE PRESSURE_Pt _(psi) AVAILABLE PRESSURE_Pt _(psi) AVAILABLE PRESSURE_Pt _(psi) AVAILABLE PRESSURE_Pt _(psi) AVAILABLE PRESSURE_Pt _(psi) AVAILABLE PRESSURE_Pt _(psi) AVAILABLE PRESSURE_Pt _(psi) AVAILABLE PRESSURE_Pt _(psi)
SPRINKLER
FLOW RATEa
(gpm)

WATER
DISTRIBUTION
SIZE (inch)
15 20 25 30 35 40 45 50 55 60
SPRINKLER
FLOW RATEa
(gpm)

WATER
DISTRIBUTION
SIZE (inch)
Allowable length of pipe from service valve to farthest sprinkler (feet)









Allowable length of pipe from service valve to farthest sprinkler (feet)









Allowable length of pipe from service valve to farthest sprinkler (feet)









Allowable length of pipe from service valve to farthest sprinkler (feet)









Allowable length of pipe from service valve to farthest sprinkler (feet)









Allowable length of pipe from service valve to farthest sprinkler (feet)









Allowable length of pipe from service valve to farthest sprinkler (feet)









Allowable length of pipe from service valve to farthest sprinkler (feet)









Allowable length of pipe from service valve to farthest sprinkler (feet)









Allowable length of pipe from service valve to farthest sprinkler (feet)









8
3/4
217
289
361
434
506
578
650
723
795
867
9 3/4
174 232 291 349 407 465 523 581 639 697
10
3/4
143
191
239
287
335
383
430
478
526
574
11
3/4
120
160
200
241
281
321
361
401
441
481
12 3/4
102 137 171 205 239 273 307 341 375 410
13
3/4
88
118
147
177
206
235
265
294
324
353
14
3/4
77
103
128
154
180
205
231
257
282
308
15 3/4
68 90 113 136 158 181 203 226 248 271
16
3/4
60
80
100
120
140
160
180
200
220
241
17
3/4
54
72
90
108
125
143
161
179
197
215
18 3/4
48 64 81 97 113 129 145 161 177 193
19
3/4
44
58
73
88
102
117
131
146
160
175
20
3/4
40
53
66
80
93
106
119
133
146
159
21 3/4
36 48 61 73 85 97 109 121 133 145
22
3/4
33
44
56
67
78
89
100
111
122
133
23
3/4
31
41
51
61
72
82
92
102
113
123
24 3/4
28 38 47 57 66 76 85 95 104 114
25
3/4
26
35
44
53
61
70
79
88
97
105
26
3/4
24
33
41
49
57
65
73
82
90
98
27 3/4
23 30 38 46 53 61 69 76 84 91
28
3/4
21
28
36
43
50
57
64
71
78
85
29
3/4
20
27
33
40
47
53
60
67
73
80
30 3/4
19 25 31 38 44 50 56 63 69 75
31
3/4
18
24
29
35
41
47
53
59
65
71
32
3/4
17
22
28
33
39
44
50
56
61
67
33
3/4
16
21
26
32
37
42
47
53
58
63
34 3/4
NP 20 25 30 35 40 45 50 55 60
35
3/4
NP
19
24
28
33
38
42
47
52
57
36
3/4
NP
18
22
27
31
36
40
45
49
54
37 3/4
NP 17 21 26 30 34 38 43 47 51
38
3/4
NP
16
20
24
28
32
36
40
45
49
39
3/4
NP
15
19
23
27
31
35
39
42
46
40 3/4 NP NP 18 22 26 29 33 37 40 44

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s. NP Not permitted a. Flow rate from Section R313.3.4.2.

3-64 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

TABLE R313.3.6.2(5) ALLOWABLE PIPE LENGTH FOR 1-INCH TYPE M COPPER WATER TUBING —
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSURE—****_Pt _(psi) AVAILABLE PRESSURE—****_Pt _(psi) AVAILABLE PRESSURE—****_Pt _(psi) AVAILABLE PRESSURE—****_Pt _(psi) AVAILABLE PRESSURE—****_Pt _(psi) AVAILABLE PRESSURE—****_Pt _(psi) AVAILABLE PRESSURE—****_Pt _(psi) AVAILABLE PRESSURE—****_Pt _(psi) AVAILABLE PRESSURE—****_Pt _(psi) AVAILABLE PRESSURE—****_Pt _(psi)
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
15 20 25 30 35 40 45 50 55 60
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet)
8 1 806 1075 1343 1612 1881 2149 2418 2687 2955 3224
9 1 648 864 1080 1296 1512 1728 1945 2161 2377 2593
10 1 533 711 889 1067 1245 1422 1600 1778 1956 2134
11 1 447 586 745 894 1043 1192 1341 1491 1640 1789
12 1 381 508 634 761 888 1015 1142 1269 1396 1523
13 1 328 438 547 657 766 875 985 1094 1204 1313
14 1 286 382 477 572 668 763 859 954 1049 1145
15 1 252 336 420 504 588 672 756 840 924 1008
16 1 224 298 373 447 522 596 671 745 820 894
17 1 200 266 333 400 466 533 600 666 733 799
18 1 180 240 300 360 420 479 539 599 659 719
19 1 163 217 271 325 380 434 488 542 597 651
20 1 148 197 247 296 345 395 444 493 543 592
21 1 135 180 225 270 315 360 406 451 496 541
22 1 124 165 207 248 289 331 372 413 455 496
23 1 114 152 190 228 267 305 343 381 419 457
24 1 106 141 176 211 246 282 317 352 387 422
25 1 98 131 163 196 228 261 294 326 359 392
26 1 91 121 152 182 212 243 273 304 334 364
27 1 85 113 142 170 198 226 255 283 311 340
28 1 79 106 132 159 185 212 238 265 291 318
29 1 74 99 124 149 174 198 223 248 273 298
30 1 70 93 116 140 163 186 210 233 256 280
31 1 66 88 110 132 153 175 197 219 241 263
32 1 62 83 103 124 145 165 186 207 227 248
33 1 59 78 98 117 137 156 176 195 215 234
34 1 55 74 92 111 129 148 166 185 203 222
35 1 53 70 88 105 123 140 158 175 193 210
36 1 50 66 83 100 116 133 150 166 183 199
37 1 47 63 79 95 111 126 142 158 174 190
38 1 45 60 75 90 105 120 135 150 165 181
39 1 43 57 72 86 100 115 129 143 158 172
40 1 41 55 68 82 96 109 123 137 150 164

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s. a. Flow rate from Section R313.3.4.2.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

TABLE R313.3.6.2(6)

ALLOWABLE PIPE LENGTH FOR 3/4-INCH CPVC PIPE —
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi)
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
15 20 25 30 35 40 45 50 55 60
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet)
8 3/4 348 465 581 697 813 929 1045 1161 1278 1394
9 3/4 280 374 467 560 654 747 841 934 1027 1121
10 3/4 231 307 384 461 538 615 692 769 845 922
11 3/4 193 258 322 387 451 515 580 644 709 773
12 3/4 165 219 274 329 384 439 494 549 603 658
13 3/4 142 189 237 284 331 378 426 473 520 568
14 3/4 124 165 206 247 289 330 371 412 454 495
15 3/4 109 145 182 218 254 290 327 363 399 436
16 3/4 97 129 161 193 226 258 290 322 354 387
17 3/4 86 115 144 173 202 230 259 288 317 346
18 3/4 78 104 130 155 181 207 233 259 285 311
19 3/4 70 94 117 141 164 188 211 234 258 281
20 3/4 64 85 107 128 149 171 192 213 235 256
21 3/4 58 78 97 117 136 156 175 195 214 234
22 3/4 54 71 89 107 125 143 161 179 197 214
23 3/4 49 66 82 99 115 132 148 165 181 198
24 3/4 46 61 76 91 107 122 137 152 167 183
25 3/4 42 56 71 85 99 113 127 141 155 169
26 3/4 39 52 66 79 92 105 118 131 144 157
27 3/4 37 49 61 73 86 98 110 122 135 147
28 3/4 34 46 57 69 80 92 103 114 126 137
29 3/4 32 43 54 64 75 86 96 107 118 129
30 3/4 30 40 50 60 70 81 91 101 111 121
31 3/4 28 38 47 57 66 76 85 95 104 114
32 3/4 27 36 45 54 63 71 80 89 98 107
33 3/4 25 34 42 51 59 68 76 84 93 101
34 3/4 24 32 40 48 56 64 72 80 88 96
35 3/4 23 30 38 45 53 61 68 76 83 91
36 3/4 22 29 36 43 50 57 65 72 79 86
37 3/4 20 27 34 41 48 55 61 68 75 82
38 3/4 20 26 33 39 46 52 59 65 72 78
39 3/4 19 25 31 37 43 50 56 62 68 74
40 3/4 18 24 30 35 41 47 53 59 65 71

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s. a. Flow rate from Section R313.3.4.2.

3-66 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

TABLE R313.3.6.2(7) ALLOWABLE PIPE LENGTH FOR 1-INCH CPVC PIPE —
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi)
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
15 20 25 30 35 40 45 50 55 60
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet)
8 1 1049 1398 1748 2098 2447 2797 3146 3496 3845 4195
9 1 843 1125 1406 1687 1968 2249 2530 2811 3093 3374
10 1 694 925 1157 1388 1619 1851 2082 2314 2545 2776
11 1 582 776 970 1164 1358 1552 1746 1940 2133 2327
12 1 495 660 826 991 1156 1321 1486 1651 1816 1981
13 1 427 570 712 854 997 1139 1281 1424 1566 1709
14 1 372 497 621 745 869 993 1117 1241 1366 1490
15 1 328 437 546 656 765 874 983 1093 1202 1311
16 1 291 388 485 582 679 776 873 970 1067 1164
17 1 260 347 433 520 607 693 780 867 954 1040
18 1 234 312 390 468 546 624 702 780 858 936
19 1 212 282 353 423 494 565 635 706 776 847
20 1 193 257 321 385 449 513 578 642 706 770
21 1 176 235 293 352 410 469 528 586 645 704
22 1 161 215 269 323 377 430 484 538 592 646
23 1 149 198 248 297 347 396 446 496 545 595
24 1 137 183 229 275 321 366 412 458 504 550
25 1 127 170 212 255 297 340 382 425 467 510
26 1 118 158 197 237 276 316 355 395 434 474
27 1 111 147 184 221 258 295 332 368 405 442
28 1 103 138 172 207 241 275 310 344 379 413
29 1 97 129 161 194 226 258 290 323 355 387
30 1 91 121 152 182 212 242 273 303 333 364
31 1 86 114 143 171 200 228 257 285 314 342
32 1 81 108 134 161 188 215 242 269 296 323
33 1 76 102 127 152 178 203 229 254 280 305
34 1 72 96 120 144 168 192 216 240 265 289
35 1 68 91 114 137 160 182 205 228 251 273
36 1 65 87 108 130 151 173 195 216 238 260
37 1 62 82 103 123 144 165 185 206 226 247
38 1 59 78 98 117 137 157 176 196 215 235
39 1 56 75 93 112 131 149 168 187 205 224
40 1 53 71 89 107 125 142 160 178 196 214

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s. a. Flow rate from Section R313.3.4.2.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

TABLE R313.3.6.2(8)

ALLOWABLE PIPE LENGTH FOR 3/4-INCH PEX AND PE-RT TUBING —
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi) AVAILABLE PRESSURE—****Pt (psi)
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
15 20 25 30 35 40 45 50 55 60
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet)
8 3/4 93 123 154 185 216 247 278 309 339 370
9 3/4 74 99 124 149 174 199 223 248 273 298
10 3/4 61 82 102 123 143 163 184 204 225 245
11 3/4 51 68 86 103 120 137 154 171 188 205
12 3/4 44 58 73 87 102 117 131 146 160 175
13 3/4 38 50 63 75 88 101 113 126 138 151
14 3/4 33 44 55 66 77 88 99 110 121 132
15 3/4 29 39 48 58 68 77 87 96 106 116
16 3/4 26 34 43 51 60 68 77 86 94 103
17 3/4 23 31 38 46 54 61 69 77 84 92
18 3/4 21 28 34 41 48 55 62 69 76 83
19 3/4 19 25 31 37 44 50 56 62 69 75
20 3/4 17 23 28 34 40 45 51 57 62 68
21 3/4 16 21 26 31 36 41 47 52 57 62
22 3/4 NP 19 24 28 33 38 43 47 52 57
23 3/4 NP 17 22 26 31 35 39 44 48 52
24 3/4 NP 16 20 24 28 32 36 40 44 49
25 3/4 NP NP 19 22 26 30 34 37 41 45
26 3/4 NP NP 17 21 24 28 31 35 38 42
27 3/4 NP NP 16 20 23 26 29 33 36 39
28 3/4 NP NP 15 18 21 24 27 30 33 36
29 3/4 NP NP NP 17 20 23 26 28 31 34
30 3/4 NP NP NP 16 19 21 24 27 29 32
31 3/4 NP NP NP 15 18 20 23 25 28 30
32 3/4 NP NP NP NP 17 19 21 24 26 28
33 3/4 NP NP NP NP 16 18 20 22 25 27
34 3/4 NP NP NP NP NP 17 19 21 23 25
35 3/4 NP NP NP NP NP 16 18 20 22 24
36 3/4 NP NP NP NP NP 15 17 19 21 23
37 3/4 NP NP NP NP NP NP 16 18 20 22
38 3/4 NP NP NP NP NP NP 16 17 19 21
39 3/4 NP NP NP NP NP NP NP 16 18 20
40 3/4 NP NP NP NP NP NP NP 16 17 19

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s. NP Not permitted. a. Flow rate from Section R313.3.4.2.

3-68 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

TABLE R313.3.6.2(9) ALLOWABLE PIPE LENGTH FOR 1-INCH PEX AND PE-RT TUBING —
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
AVAILABLE PRESSUREPt (psi) AVAILABLE PRESSUREPt (psi) AVAILABLE PRESSUREPt (psi) AVAILABLE PRESSUREPt (psi) AVAILABLE PRESSUREPt (psi) AVAILABLE PRESSUREPt (psi) AVAILABLE PRESSUREPt (psi) AVAILABLE PRESSUREPt (psi) AVAILABLE PRESSUREPt (psi) AVAILABLE PRESSUREPt (psi)
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
15 20 25 30 35 40 45 50 55 60
SPRINKLER
FLOW RATEa
(gpm)
WATER
DISTRIBUTION
SIZE (inch)
Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet) Allowable length of pipe from service valve to farthest sprinkler (feet)
8 1 314 418 523 628 732 837 941 1046 1151 1255
9 1 252 336 421 505 589 673 757 841 925 1009
10 1 208 277 346 415 485 554 623 692 761 831
11 1 174 232 290 348 406 464 522 580 638 696
12 1 148 198 247 296 346 395 445 494 543 593
13
1
128
170
213
256
298
341
383
426
469
511
14
1
111
149
186
223
260
297
334
371
409
446
15
1
98
131
163
196
229
262
294
327
360
392
16
1
87
116
145
174
203
232
261
290
319
348
17
1
78
104
130
156
182
208
233
259
285
311
18
1
70
93
117
140
163
187
210
233
257
280
19
1
63
84
106
127
148
169
190
211
232
253
20
1
58
77
96
115
134
154
173
192
211
230
21
1
53
70
88
105
123
140
158
175
193
211
22
1
48
64
80
97
113
129
145
161
177
193
23
1
44
59
74
89
104
119
133
148
163
178
24
1
41
55
69
82
96
110
123
137
151
164
25
1
38
51
64
76
89
102
114
127
140
152
26
1
35
47
59
71
83
95
106
118
130
142
27
1
33
44
55
66
77
88
99
110
121
132
28
1
31
41
52
62
72
82
93
103
113
124
29
1
29
39
48
58
68
77
87
97
106
116
30
1
27
36
45
54
63
73
82
91
100
109
31
1
26
34
43
51
60
68
77
85
94
102
32
1
24
32
40
48
56
64
72
80
89
97
33
1
23
30
38
46
53
61
68
76
84
91
34
1
22
29
36
43
50
58
65
72
79
86
35
1
20
27
34
41
48
55
61
68
75
82
36
1
19
26
32
39
45
52
58
65
71
78
37
1
18
25
31
37
43
49
55
62
68
74
38
1
18
23
29
35
41
47
53
59
64
70
39
1
17
22
28
33
39
45
50
56
61
67
40 1 16 21 27 32 37 43 48 53 59 64

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 0.963 L/s. a. Flow rate from Section R313.3.4.2.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

BUILDING PLANNING

R313.3.7 Instructions and signs.

An owner’s manual for the fire sprinkler system shall be provided to the owner. A sign or valve tag shall be installed at the main shutoff valve to the water distribution system stating the following: “Warning, the water system for this home supplies fire sprinklers that require certain flows and pressures to fight a fire. Devices that restrict the flow or decrease the pressure or automatically shut off the water to the fire sprinkler system, such as water softeners, filtration systems and automatic shutoff valves, shall not be added to this system without a review of the fire sprinkler system by a fire protection specialist. Do not remove this sign.”

R313.3.8 Inspections.

The water distribution system shall be inspected in accordance with Sections R313.3.8.1 and R313.3.8.2 .

R313.3.8.1 Preconcealment inspection. The following items shall be verified prior to the concealment of any sprinkler system piping:

  1. Sprinklers are installed in all areas as required by Section R313.3.1.2.

  2. Where sprinkler water spray patterns are obstructed by construction features, luminaires or ceiling fans, additional sprinklers are installed as required by Section R313.3.2.4.2 .

  3. Sprinklers are the correct temperature rating and are installed at or beyond the required separation distances from heat sources as required by Sections R313.3.2.1 and R313.3.2.2 .

  4. The pipe size equals or exceeds the size used in applying Tables R313.3.6.2(4) through R313.3.6.2(9) or, if the piping system was hydraulically calculated in accordance with Section R313.3.6.1, the size used in the hydraulic calculation.

  5. The pipe length does not exceed the length permitted by Tables R313.3.6.2(4) through

R313.3.6.2(9)

or, if the piping system was hydraulically calculated in accordance with Section R313.3.6.1, pipe lengths and fittings do not exceed those used in the hydraulic calculation.

  1. Nonmetallic piping that conveys water to sprinklers is listed for use with fire sprinklers.

  2. Piping is supported in accordance with the pipe manufacturer’s and sprinkler manufacturer’s installation instructions.

  3. The piping system is tested in accordance with the California Plumbing Code.

R313.3.8.2 Final inspection. The following items shall be verified upon completion of the system:

  1. Sprinkler are not painted, damaged or otherwise hindered from operation.

  2. Where a pump is required to provide water to the system, the pump starts automatically upon system water demand.

  3. Pressure-reducing valves, water softeners, water filters or other impairments to water flow that were not part of the original design have not been installed.

  4. The sign or valve tag required by Section R313.3.7 is installed and the owner’s manual for the system is present.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Residential Code (Title 24, Part 2.5)
California Residential Code (Title 24, Part 2.5)
  1. Chapter 2 — DEFINITIONS AND ABBREVIATIONS
  2. Appendix AF — RADON CONTROL
  3. Appendix AI — PRIVATE SEWAGE
  4. Appendix AJ — EXISTING
  5. Appendix AK — SOUND
  6. Appendix AO — AUTOMATIC
  7. Appendix AR — LIGHT STRAW-CLAY
  8. Appendix AS — STRAWBALE
  9. Appendix AU — COB CONSTRUCTION
  10. Appendix AV — BOARD
  11. Appendix AW — 3D-PRINTED BUILDING
  12. Chapter 1 — SCOPE AND APPLICATION
  13. Chapter 3 — BUILDING PLANNING
  14. Chapter 4 — FOUNDATIONS
  15. Chapter 5 — FLOORS
  16. Chapter 6 — WALL CONSTRUCTION
  17. Chapter 7 — WALL COVERING
  18. Chapter 8 — ROOF-CEILING CONSTRUCTION
  19. Chapter 9 — ROOF ASSEMBLIES
  20. Chapter 10 — CHIMNEYS AND FIREPLACES
  21. Chapter 44 — REFERENCED STANDARDS
  22. Appendix AH — PATIO COVERS
  23. Appendix AL — PERMIT FEES
  24. Appendix AQ — TINY HOUSES
  25. Appendix AT — SOLAR-READY PROVISIONS—DETACHED ONE- AND
  26. Appendix AX — SWIMMING POOL SAFETY ACT
  27. Appendix AY — AREAS PROTECTED BY THE FACILITIES
  28. Appendix AZ — EMERGENCY HOUSING

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.