Section R337.5

California Residential Code (Title 24, Part 2.5) · 2022 edition · updated 2026-09-12 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

ROOFING R337.5.1 General. Roofs shall comply with the require- ments of Sections R337 and R902. Roofs shall have a roof- ing assembly installed in accordance with its listing and the manufacturer's installation instructions. Roof assem- blies in the Fire Hazard Severity Zones shall be Class A rating when tested in accordance with ASTM E108 or UL790.

R337.5.2 Roof coverings. Where the roofing profile has an airspace under the roof covering, installed over a combustible deck, a 72 lb. (32.7kg) cap sheet complying with ASTM D3909 Standard Specification for “Asphalt Rolled Roofing (Glass Felt) Surfaced with Mineral Gran- ules,” shall be installed over the roof deck. Bird stops shall be used at the eaves when the profile fits, to prevent debris at the eave. Hip and ridge caps shall be mudded in to prevent intrusion of fire or embers.

Exception: Cap sheet is not required when no less than 1 inch of mineral wool board or other noncombustible material is located between the roofing material and wood framing or deck. Alternately, a Class A fire rated roof underlayment, tested in accordance with ASTM E108, shall be permit- ted to be used. If the sheathing consists of exterior fire- retardant-treated wood, the underlayment shall not be required to comply with a Class A classification. Bird stops shall be used at the eaves when the profile fits, to prevent debris at the eave. Hip and ridge caps shall be mudded in to prevent intrusion of fire or embers.

R337.5.3 Roof valleys. Where valley flashing is installed, the flashing shall be not less than 0.019-inch (0.48 mm) No. 26 gage galvanized sheet corrosion- resistant metal installed over not less than one layer of minimum 72-pound (32.4 kg) mineral-surfaced nonper-

forated cap sheet complying with ASTM D3909, at least 36-inch-wide (914 mm) running the full length of the valley.

R337.5.4 Roof gutters. Roof gutters shall be provided with the means to prevent the accumulation of leaves and debris in the gutter.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Residential Code (Title 24, Part 2.5)
California Residential Code (Title 24, Part 2.5)
  1. Chapter 2 — DEFINITIONS AND ABBREVIATIONS
  2. Appendix AF — RADON CONTROL
  3. Appendix AI — PRIVATE SEWAGE
  4. Appendix AJ — EXISTING
  5. Appendix AK — SOUND
  6. Appendix AO — AUTOMATIC
  7. Appendix AR — LIGHT STRAW-CLAY
  8. Appendix AS — STRAWBALE
  9. Appendix AU — COB CONSTRUCTION
  10. Appendix AV — BOARD
  11. Appendix AW — 3D-PRINTED BUILDING
  12. Chapter 1 — SCOPE AND APPLICATION
  13. Chapter 3 — BUILDING PLANNING
  14. Chapter 4 — FOUNDATIONS
  15. Chapter 5 — FLOORS
  16. Chapter 6 — WALL CONSTRUCTION
  17. Chapter 7 — WALL COVERING
  18. Chapter 8 — ROOF-CEILING CONSTRUCTION
  19. Chapter 9 — ROOF ASSEMBLIES
  20. Chapter 10 — CHIMNEYS AND FIREPLACES
  21. Chapter 44 — REFERENCED STANDARDS
  22. Appendix AH — PATIO COVERS
  23. Appendix AL — PERMIT FEES
  24. Appendix AQ — TINY HOUSES
  25. Appendix AT — SOLAR-READY PROVISIONS—DETACHED ONE- AND
  26. Appendix AX — SWIMMING POOL SAFETY ACT
  27. Appendix AY — AREAS PROTECTED BY THE FACILITIES
  28. Appendix AZ — EMERGENCY HOUSING

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.