Section R310
California Residential Code (Title 24, Part 2.5) · 2022 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
EMERGENCY ESCAPE AND RESCUE OPENINGS
R310.1 Emergency escape and rescue opening required.¶
Basements, habitable attics and every sleeping room shall have not less than one operable emergency escape and rescue opening. Where basements contain one or more sleeping rooms, an emergency escape and rescue opening shall be required in each sleeping room. Emergency escape and rescue openings shall open directly into a public way.
Exceptions [SFM]:
1. Basements with a ceiling height of less than 80 inches (2032 mm) shall not be required to have emergency escape and rescue openings.
2. Emergency escape and rescue openings are not required from basements or sleeping rooms that have an exit door or exit access door that opens directly into a public way or to a yard, court or exte- rior egress balcony that opens to a public way.
3. Basements without habitable spaces and having not more than 200 square feet (18.6 m 2 ) in floor area shall not be required to have emergency escape and rescue openings.
4. Storm shelters are not required to comply with this section where the shelter is constructed in accor- dance with ICC 500.
5. Where the dwelling unit or townhouse unit is equipped with an automatic sprinkler system installed in accordance with Section R313, sleeping rooms in basements shall not be required to have emergency escape and rescue openings provided that the basement has one of the following:
5.1. One means of egress complying with Section R311 and one emergency escape and rescue opening. 5.2. Two means of egress complying with Section R311.
3-50 2022 CALIFORNIA RESIDENTIAL CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
BUILDING PLANNING
horizontal projection and width of not less than 36 inches (914 mm). The size of the area well shall allow the emergency escape and rescue opening to be fully opened.
Exception: The ladder or steps required by Section R310.4.2 shall be permitted to encroach not more than 6 inches (152 mm) into the required dimensions of the area well.
R310.4.2 Ladder and steps. Area wells with a vertical depth greater than 44 inches (1118 mm) shall be equipped with an approved, permanently affixed ladder or steps. The ladder or steps shall not be obstructed by the emergency escape and rescue opening where the window or door is in the open position. Ladders or steps required by this section shall not be required to comply with Section R311.7.
R310.4.2.1 Ladders. Ladders and rungs shall have an inside width of not less than 12 inches (305 mm), shall project not less than 3 inches (76 mm) from the wall and shall be spaced not more than 18 inches (457 mm) on center vertically for the full height of the area well.
R310.4.2.2 Steps. Steps shall have an inside width of not less than 12 inches (305 mm), a minimum tread depth of 5 inches (127 mm) and a maximum riser height of 18 inches (457 mm) for the full height of the area well.
R310.4.3 Drainage. Area wells shall be designed for proper drainage by connecting to the building’s foundation drainage system required by Section R405.1.
Exception: A drainage system for area wells is not required where the foundation is on well-drained soil or sand-gravel mixture soils in accordance with the United Soil Classification System, Group I Soils, as detailed in Table R405.1.
R310.4.4 Bars, grilles, covers and screens. Where bars, grilles, covers, screens or similar devices are placed over emergency escape and rescue openings, bulkhead enclosures or area wells that serve such openings, the minimum net clear opening size shall comply with Sections R310.2 through R310.2.2 and R310.4.1. Such devices shall be releasable or removable from the inside without the use of a key or tool or force greater than that required for the normal operation of the escape and rescue opening. The release mechanism shall be maintained operable at all times.
Such bars, grills, grates or any similar devices shall be equipped with an approved exterior release device for use by the fire department only when required by the authority having jurisdiction.
Where security bars (burglar bars) are installed on emergency egress and rescue windows or doors, on or after July 1, 2000, such devices shall comply with Califor- nia Building Standards Code, Part 12, Chapter 12-3 and other applicable provisions of this code.
R310.5 Replacement windows for emergency escape and rescue openings.¶
rescue openings. Replacement windows installed in buildings meeting the scope of this code shall be exempt from
R310.1.1 Operational constraints and opening control devices. Emergency escape and rescue openings shall be maintained free of any obstructions other than those allowed by this section and shall be operational from the inside of the room without the use of keys, tools or special knowledge. Window opening control devices and fall prevention devices complying with ASTM F2090 shall be permitted for use on windows serving as a required emergency escape and rescue opening and shall be not more than 70 inches (178 cm) above the finished floor. The release mechanism shall be maintained operable at all times.
Such bars, grills, grates or any similar devices shall be equipped with an approved exterior release device for use by the fire department only when required by the authority having jurisdiction.
Where security bars (burglar bars) are installed on emergency egress and rescue windows or doors, on or after July 1, 2000, such devices shall comply with Califor- nia Building Standards Code, Part 12, Chapter 12-3 and other applicable provisions of this code.
R310.2 Emergency escape and rescue openings.¶
Emergency escape and rescue openings shall have minimum dimensions in accordance with Sections R310.2.1 through R310.2.4.
R310.2.1 Minimum size. Emergency escape and rescue openings shall have a net clear opening of not less than 5.7 square feet (0.530 m 2 ).
Exception: The minimum net clear opening for gradefloor emergency escape and rescue openings shall be 5 square feet (0.465 m 2 ).
R310.2.2 Minimum dimensions. The minimum net clear opening height dimension shall be 24 inches (610 mm). The minimum net clear opening width dimension shall be 20 inches (508 mm). The net clear opening dimensions shall be the result of normal operation of the opening.
R310.2.3 Maximum height from floor. Emergency escape and rescue openings shall have the bottom of the clear opening not greater than 44 inches (1118 mm) measured from the floor.
R310.2.4 Emergency escape and rescue openings under decks, porches and cantilevers. Emergency escape and rescue openings installed under decks, porches and cantilevers shall be fully openable and provide a path not less than 36 inches (914 mm) in height and 36 inches (914 mm) in width to a yard or court.
R310.3 Emergency escape and rescue doors.¶
Where a door is provided as the required emergency escape and rescue opening, it shall be a side-hinged door or a sliding door.
R310.4 Area wells.¶
An emergency escape and rescue opening where the bottom of the clear opening is below the adjacent grade shall be provided with an area well in accordance with Sections R310.4.1 through R310.4.4.
R310.4.1 Minimum size. The horizontal area of the area well shall be not less than 9 square feet (0.9 m 2 ), with a
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
BUILDING PLANNING
Sections R310.2 and R310.4.4, provided that the replacement window meets the following conditions:
The replacement window is the manufacturer’s largest standard size window that will fit within the existing frame or existing rough opening. The replacement window is of the same operating style as the existing window or a style that provides for an equal or greater window opening area than the existing window.
The replacement window is not part of a change of occupancy.
R310.6 Dwelling additions.¶
Where dwelling additions contain sleeping rooms, an emergency escape and rescue opening shall be provided in each new sleeping room. Where dwelling additions have basements, an emergency escape and rescue opening shall be provided in the new basement.
Exceptions:
An emergency escape and rescue opening is not required in a new basement that contains a sleeping room with an emergency escape and rescue opening.
An emergency escape and rescue opening is not required in a new basement where there is an emergency escape and rescue opening in an existing basement that is accessed from the new basement.
An operable window complying with Section 310.7.1 shall be acceptable as an emergency escape and rescue opening.
R310.7 Alterations or repairs of existing basements.¶
New sleeping rooms created in an existing basement shall be provided with emergency escape and rescue openings in accordance with Section R310.1. Other than new sleeping rooms, where existing basements undergo alterations or repairs, an emergency escape and rescue opening is not required.
Exception: An operable window complying with Section 310.7.1 shall be acceptable as an emergency escape and rescue opening.
R310.7.1 Existing emergency escape and rescue openings. Where a change of occupancy would require an emergency escape and rescue opening in accordance with Section 310.1, operable windows serving as the emergency escape and rescue opening shall comply with the following:
An existing operable window shall provide a minimum net clear opening of 4 square feet (0.38 m 2 ) with a minimum net clear opening height of 22 inches (559 mm) and a minimum net clear opening width of 20 inches (508 mm).
A replacement window where such window complies with both of the following:
2.1. The replacement window meets the size requirements in Item 1.
2.2. The replacement window is the manufacturer’s largest standard-size window that will fit within the existing frame or existing rough opening. The replacement window shall be permitted to be of the same operat
ing style as the existing window or a style that provides for an equal or greater window opening area than the existing window.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Residential Code (Title 24, Part 2.5)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix AF — RADON CONTROL
- Appendix AI — PRIVATE SEWAGE
- Appendix AJ — EXISTING
- Appendix AK — SOUND
- Appendix AO — AUTOMATIC
- Appendix AR — LIGHT STRAW-CLAY
- Appendix AS — STRAWBALE
- Appendix AU — COB CONSTRUCTION
- Appendix AV — BOARD
- Appendix AW — 3D-PRINTED BUILDING
- Chapter 1 — SCOPE AND APPLICATION
▸Chapter 3 — BUILDING PLANNING
Overview- Section R300
- Section R301
- Section R302
- Section R303
- Section R304
- Section R305
- Section R307
- Section R308
- Section R306
- Section R309
- Section R310
- Section R311
- Section R312
- Section R313
- Section R314
- Section R315
- Section R316
- Section R317
- Section R318
- Section R319
- Section R320
- Section R321
- Section R322
- Section R323
- Section R324
- Section R325
- Section R327
- Section R326
- Section R328
- Section R329
- Section R330
- Section R334
- Section R335
- Section R336
- Section R337
- Section R337.1
- Section R337.2
- Section R337.3
- Section R337.4
- Section R337.5
- Section R337.6
- Section R337.7
- Section R337.8
- Section R337.9
- Section R337.10
- Section R338
- Section R340
- Chapter 4 — FOUNDATIONS
- Chapter 5 — FLOORS
- Chapter 6 — WALL CONSTRUCTION
- Chapter 7 — WALL COVERING
- Chapter 8 — ROOF-CEILING CONSTRUCTION
- Chapter 9 — ROOF ASSEMBLIES
- Chapter 10 — CHIMNEYS AND FIREPLACES
- Chapter 44 — REFERENCED STANDARDS
- Appendix AH — PATIO COVERS
- Appendix AL — PERMIT FEES
- Appendix AQ — TINY HOUSES
- Appendix AT — SOLAR-READY PROVISIONS—DETACHED ONE- AND
- Appendix AX — SWIMMING POOL SAFETY ACT
- Appendix AY — AREAS PROTECTED BY THE FACILITIES
- Appendix AZ — EMERGENCY HOUSING