Chapter 8 — ROOF-CEILING CONSTRUCTION
Section R804
California Residential Code (Title 24, Part 2.5) · 2019 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
R804.1 General.¶
Elements shall be straight and free of any defects that would significantly affect their structural performance. Cold-formed steel roof framing members shall be in accordance with the requirements of this section.
R804.1.1 Applicability limits. The provisions of this section shall control the construction of cold-formed steel roof framing for buildings not greater than 60 feet (18 288 mm) perpendicular to the joist, rafter or truss span, not greater than 40 feet (12 192 mm) in width parallel to the joist span or truss, less than or equal to three stories above grade plane and with roof slopes not less than 3:12 (25percent slope) or greater than 12:12 (100-percent slope). Cold-formed steel roof framing constructed in accordance with the provisions of this section shall be limited to sites where the ultimate design wind speed is less than 140 miles per hour (63 m/s), Exposure Category B or C, and the ground snow load is less than or equal to 70 pounds per square foot (3350 Pa).
R804.1.2 In-line framing. Cold-formed steel roof framing constructed in accordance with Section R804 shall be located in line with load-bearing studs in accordance with Figure R804.1.2 and the tolerances specified as follows:
- The maximum tolerance shall be 3 /4 inch (19.1 mm) between the centerline of the horizontal framing member and the centerline of the vertical framing member.
472 2019 CALIFORNIA RESIDENTIAL CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
- Where the centerline of the horizontal framing member and bearing stiffener are located to one side of the centerline of the vertical framing member, the maximum tolerance shall be 1 /8 inch (3.2 mm) between the web of the horizontal framing member and the edge of the vertical framing member.
R804.2 Structural framing.¶
Load-bearing, cold-formed steel roof framing members shall be in accordance with this section.
R804.2.1 Material. Load-bearing, cold-formed steel framing members shall be cold formed to shape from structural quality sheet steel complying with the requirements of ASTM A1003, Structural Grades 33 Type H and 50 Type H.
R804.2.2 Corrosion protection. Load-bearing, coldformed steel framing shall have a metallic coating complying with ASTM A1003 and one of the following:
- Not less than G 60 in accordance with ASTM A653.
ROOF-CEILING CONSTRUCTION
- Not less than AZ 50 in accordance with ASTM A792.
R804.2.3 Dimension, thickness and material grade. Load-bearing, cold-formed steel roof framing members shall comply with Figure R804.2.3(1) and with the dimensional and thickness requirements specified in Table R804.2.3. Additionally, C-shaped sections shall have a minimum flange width of 1.625 inches (41 mm) and a maximum flange width of 2 inches (51 mm). The minimum lip size for C-shaped sections shall be 1 /2 inch (12.7 mm). Tracks shall comply with Figure R804.2.3(2) and shall have a minimum flange width of 1 1 /4 inches (32 mm). Minimum Grade 33 ksi steel shall be used wherever 33 mil and 43 mil thicknesses are specified. Minimum Grade 50 ksi steel shall be used wherever 54 and 68 mil thicknesses are specified.
R804.2.4 Identification. Load-bearing, cold-formed steel framing members shall have a legible label , stencil, stamp
TABLE R804.2.3 LOAD-BEARING COLD-FORMED STEEL ROOF FRAMING MEMBER SIZES AND THICKNESSES
| MEMBER DESIGNATIONa |
WEB DEPTH (inches) |
MINIMUM BASE STEEL THICKNESS mil (inches) |
|---|---|---|
| 350S162-t | 3.5 | 33 (0.0329), 43 (0.0428), 54 (0.0538) |
| 550S162-t | 5.5 | 33 (0.0329), 43 (0.0428), 54 (0.0538), 68 (0.0677) |
| 800S162-t | 8 | 33 (0.0329), 43 (0.0428), 54 (0.0538), 68 (0.0677) |
| 1000S162-t | 10 | 43 (0.0428), 54 (0.0538), 68 (0.0677) |
| 1200S162-t | 12 | 43 (0.0428), 54 (0.0538), 68 (0.0677) |
For SI: 1 inch = 25.4 mm a. The member designation is defined by the first number representing the member depth in hundredths of an inch, the letter “s” representing a stud or joist
member, the second number representing the flange width in hundredths of an inch and the letter “t” shall be a number representing the minimum base metal thickness in mils.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ROOF-CEILING CONSTRUCTION
or embossment with the following information as a minimum:
Manufacturer’s identification.
Minimum base steel thickness in inches (mm).
Minimum coating designation.
Minimum yield strength, in kips per square inch (ksi) (MPa).
R804.2.5 Fastening requirements. Screws for steel-tosteel connections shall be installed with a minimum edge distance and center-to-center spacing of 1 /2 inch (12.7 mm), shall be self-drilling tapping and shall conform to ASTM C1513. Structural sheathing shall be attached to cold-formed steel roof rafters with minimum No. 8 selfdrilling tapping screws that conform to ASTM C1513. Screws for attaching structural sheathing to cold-formed steel roof framing shall have a minimum head diameter of 0.292 inch (7.4 mm) with countersunk heads and shall be installed with a minimum edge distance of 3 /8 inch (9.5 mm). Gypsum board ceilings shall be attached to coldformed steel joists with minimum No. 6 screws conforming to ASTM C954 or ASTM C1513 with a bugle-head style and shall be installed in accordance with Section R805. For all connections, screws shall extend through the steel not fewer than three exposed threads. Fasteners shall have rust-inhibitive coating suitable for the installation in which they are being used, or be manufactured from material not susceptible to corrosion.
R804.2.6 Web holes, web hole reinforcing and web hole patching. Web holes, web hole reinforcing and web hole patching shall be in accordance with this section.
R804.2.6.1 Web holes. Web holes in roof framing members shall comply with all of the following conditions:
Holes shall conform to Figure R804.2.6.1.
Holes shall be permitted only along the centerline of the web of the framing member.
Center-to-center spacing of holes shall be not less than 24 inches (610 mm).
The web hole width shall be not greater than onehalf the member depth, or 2 1 /2 inches (64 mm).
Holes shall have a web hole length not exceeding 4 1 /2 inches (114 mm).
The minimum distance between the edge of the bearing surface and the edge of the web hole shall be not less than 10 inches (254 mm).
Framing members with web holes not conforming to Items 1 though 6 shall be reinforced in accordance with Section R804.2.6.2, patched in accordance with Section R804.2.6.3 or designed in accordance with accepted engineering practices.
R804.2.6.2 Web hole reinforcing. Reinforcement of web holes in ceiling joists not conforming to the requirements of Section R804.2.6.1 shall be permitted if the hole is located fully within the center 40 percent of the span and the depth and length of the hole do not exceed 65 percent of the flat width of the web. The reinforcing shall be a steel plate or C-shaped section with a hole that does not exceed the web hole size limitations of Section R804.2.6.1 for the member being reinforced. The steel reinforcing shall be the same thickness as the receiving member and shall extend not less than 1 inch (25 mm) beyond all edges of the hole. The steel reinforcing shall be fastened to the web of the receiving member with No. 8 screws spaced not greater than 1 inch (25 mm) center to center along the edges of the patch with minimum edge distance of 1 /2 inch (12.7 mm).
einforced. The steel reinforcing shall be the same thickness as the receiving member and shall extend not less than 1 inch (25 mm) beyond all edges of the hole. The steel reinforcing shall be fastened to the web of the receiving member with No. 8 screws spaced not greater than 1 inch (25 mm) center to center along the edges of the patch with minimum edge distance of 1 /2 inch (12.7 mm).
R804.2.6.3 Hole patching. Patching of web holes in roof framing members not conforming to the requirements in Section R804.2.6.1 shall be permitted in accordance with either of the following methods:
- Framing members shall be replaced or designed in accordance with accepted engineering practices where web holes exceed either of the following size limits:
1.1. The depth of the hole, measured across the web, exceeds 70 percent of the flat width of the web.
1.2. The length of the hole measured along the web, exceeds 10 inches (254 mm) or the depth of the web, whichever is greater.
474 2019 CALIFORNIA RESIDENTIAL CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
- Web holes not exceeding the dimensional requirements in Section R804.2.6.3, Item 1, shall be patched with a solid steel plate, stud section or track section in accordance with Figure R804.2.6.3. The steel patch shall, as a minimum, be the same thickness as the receiving member and shall extend not less than 1 inch (25 mm) beyond all edges of the hole. The steel patch shall be fastened to the web of the receiving member with No. 8 screws spaced not greater than 1 inch (25 mm) center-to-center along the edges of the patch with minimum edge distance
ROOF-CEILING CONSTRUCTION
ceiling joist, and the individual spans shall not exceed the applicable spans in Tables R804.3.1.1(1) and R804.3.1.1(2).
Where the attic is to be used as an occupied space, the ceiling joists shall be designed in accordance with Section R505.
R804.3.1.2 Ceiling joist bottom flange bracing. The bottom flanges of ceiling joists shall be laterally braced by the application of gypsum board or continuous steel straps installed perpendicular to the joist run in accordance with one of the following:
Gypsum board shall be fastened with No. 6 screws in accordance with Section R702.
Steel straps with a minimum size of 1 1 /2 inches by 33 mils (38 mm by 0.84 mm) shall be installed at a maximum spacing of 4 feet (1219 mm). Straps shall be fastened to the bottom flange at each joist with one No. 8 screw and shall be fastened to blocking with two No. 8 screws. Blocking shall be installed between joists at a maximum spacing of 12 feet (3658 mm) measured along a line of continuous strapping (perpendicular to the joist run), and at the termination of all straps.
R804.3.1.3 Ceiling joist top flange bracing. The top flanges of ceiling joists shall be laterally braced as required by Tables R804.3.1.1(1) and R804.3.1.1(2), in accordance with one of the following:
Minimum 33-mil (0.84 mm) C-shaped member in accordance with Figure R804.3.1.3(1).
Minimum 33-mil (0.84 mm) track section in accordance with Figure R804.3.1.3(1).
Minimum 33-mil (0.84 mm) hat section in accordance with Figure R804.3.1.3(1).
Minimum 54-mil (1.37 mm) 1 1 /2-inch (38 mm) cold-rolled channel section in accordance with Figure R804.3.1.3(1).
Minimum 1 1 /2-inch by 33-mil (38 mm by 0.84 mm) continuous steel strap in accordance with Figure R804.3.1.3(2).
Lateral bracing shall be installed perpendicular to the ceiling joists and shall be fastened to the top flange of each joist with one No. 8 screw. Blocking shall be installed between joists in line with bracing at a maximum spacing of 12 feet (3658 mm) measured perpendicular to the joists. Ends of lateral bracing shall be attached to blocking or anchored to a stable building component with two No. 8 screws.
R804.3.1.4 Ceiling joist splicing. Splices in ceiling joists shall be permitted, if ceiling joist splices are supported at interior bearing points and are constructed in accordance with Figure R804.3.1.4. The number of screws on each side of the splice shall be the same as required for the heel joint connection in Table R804.3.1.1(3).
R804.3.2 Roof rafters. Cold-formed steel roof rafters shall be in accordance with this section.
R804.3 Roof construction.¶
Cold-formed steel roof systems constructed in accordance with the provisions of this section shall consist of both ceiling joists and rafters in accordance with Figure R804.3 and fastened in accordance with Table R804.3.
R804.3.1 Ceiling joists. Cold-formed steel ceiling joists shall be in accordance with this section.
R804.3.1.1 Minimum ceiling joist size. Ceiling joist size and thickness shall be determined in accordance with the limits set forth in Tables R804.3.1.1(1) and R804.3.1.1(2). When determining the size of ceiling joists, the lateral support of the top flange shall be classified as unbraced, braced at midspan or braced at third points in accordance with Section R804.3.1.3. Where sheathing material is attached to the top flange of ceiling joists or where the bracing is spaced closer than at third points of the joists, the “third point” values from Tables R804.3.1.1(1) and R804.3.1.1(2) shall be used.
Ceiling joists shall have a bearing support length of not less than 1 1 /2 inches (38 mm) and shall be connected to roof rafters (heel joint) with No. 10 screws in accordance with Figure R804.3.1.1 and Table R804.3.1.1(3).
Where continuous joists are framed across interior bearing supports, the interior bearing supports shall be located within 24 inches (610 mm) of midspan of the
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ROOF-CEILING CONSTRUCTION
TABLE R804.3 ROOF FRAMING FASTENING SCHEDULE a, b
| DESCRIPTION OF BUILDING ELEMENTS | NUMBER AND SIZE OF FASTENERSa | SPACING OF FASTENERS | |||
|---|---|---|---|---|---|
| Roof sheathing (oriented strand board or plywood) to rafter |
Roof sheathing (oriented strand board or plywood) to rafter |
No. 8 screws | No. 8 screws | No. 8 screws | 6 o.c. on edges and 12 o.c. at interior supports. 6 o.c. at gable end truss |
| Gable end truss to endwall top track | Gable end truss to endwall top track | No. 10 screws | No. 10 screws | No. 10 screws | 12 o.c. |
| Rafter to ceiling joist | Rafter to ceiling joist | Minimum No. 10 screws, in accordance with Table R804.3.1.1(3) |
Minimum No. 10 screws, in accordance with Table R804.3.1.1(3) |
Minimum No. 10 screws, in accordance with Table R804.3.1.1(3) |
Evenly spaced, not less than1/2 from all edges. |
| Ceiling joist or roof truss to top track of bearing wallb |
Ceiling Joist Spacing (in.) Roof Span (f |
t) Ultimate Design Wind Speed (mph) and Exposure Category 126 B 110 C <139 B 115 C 126 C <139 C |
t) Ultimate Design Wind Speed (mph) and Exposure Category 126 B 110 C <139 B 115 C 126 C <139 C |
t) Ultimate Design Wind Speed (mph) and Exposure Category 126 B 110 C <139 B 115 C 126 C <139 C |
Each ceiling joist or roof truss |
| Ceiling joist or roof truss to top track of bearing wallb |
Ceiling Joist Spacing (in.) Roof Span (f |
t) Ultimate Design Wind Speed (mph) and Exposure Category 126 B 110 C <139 B 115 C 126 C <139 C |
126 C | <139 C | <139 C |
| Ceiling joist or roof truss to top track of bearing wallb |
16 24 28 32 36 40 |
2 2 |
2 | 3 | 3 |
| Ceiling joist or roof truss to top track of bearing wallb |
16 24 28 32 36 40 |
2 2 |
3 | 3 | 3 |
| Ceiling joist or roof truss to top track of bearing wallb |
16 24 28 32 36 40 |
2 2 |
3 | 4 | 4 |
| Ceiling joist or roof truss to top track of bearing wallb |
16 24 28 32 36 40 |
2 2 |
3 | 4 | 4 |
| Ceiling joist or roof truss to top track of bearing wallb |
16 24 28 32 36 40 |
2 2 |
3 | 4 | 4 |
| Ceiling joist or roof truss to top track of bearing wallb |
24 24 28 32 36 40 |
2 2 |
3 | 4 | 4 |
| Ceiling joist or roof truss to top track of bearing wallb |
24 24 28 32 36 40 |
2 2 |
4 | 5 | 5 |
| Ceiling joist or roof truss to top track of bearing wallb |
24 24 28 32 36 40 |
2 3 |
4 | 5 | 5 |
| Ceiling joist or roof truss to top track of bearing wallb |
24 24 28 32 36 40 |
2 3 |
4 | 6 | 6 |
| Ceiling joist or roof truss to top track of bearing wallb |
24 24 28 32 36 40 |
2 3 |
5 | 6 | 6 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa, 1 mil = 0.0254 mm. a. Screws are a minimum No. 10 unless noted otherwise. b. Indicated number of screws shall be applied through the flanges of the truss or ceiling joist or through each leg of a 54 mil clip angle. See Section R804.3.8
for additional requirements to resist uplift forces.
476 2019 CALIFORNIA RESIDENTIAL CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ROOF-CEILING CONSTRUCTION
| TABLE R804.3.1.1(1) CEILING JOIST SPANS 10 PSF LIVE LOAD (NO ATTIC STORAGE)a, b, c, d | ||||||
|---|---|---|---|---|---|---|
| MEMBER DESIGNATION |
ALLOWABLE SPAN (feet - inches) | ALLOWABLE SPAN (feet - inches) | ALLOWABLE SPAN (feet - inches) | ALLOWABLE SPAN (feet - inches) | ALLOWABLE SPAN (feet - inches) | ALLOWABLE SPAN (feet - inches) |
| MEMBER DESIGNATION |
Lateral Support of Top (Compression) Flange | Lateral Support of Top (Compression) Flange | Lateral Support of Top (Compression) Flange | Lateral Support of Top (Compression) Flange | Lateral Support of Top (Compression) Flange | Lateral Support of Top (Compression) Flange |
| MEMBER DESIGNATION |
Unbraced | Unbraced | Midspan Bracing | Midspan Bracing | Third-point Bracing | Third-point Bracing |
| MEMBER DESIGNATION |
Ceiling Joist Spacing (inches) | Ceiling Joist Spacing (inches) | Ceiling Joist Spacing (inches) | Ceiling Joist Spacing (inches) | Ceiling Joist Spacing (inches) | Ceiling Joist Spacing (inches) |
| MEMBER DESIGNATION |
16 |
24 |
16 |
24 |
16 |
24 |
| 350S162-33 | 9-6 |
8-6 |
11-10 |
9-10 |
11-10 |
10-4 |
| 350S162-43 | 10-4 | 9-3 | 12-10 | 11-3 | 12-10 | 11-3 |
| 350S162-54 | 11-1 |
9-11 |
13-9 |
12-0 |
13-9 |
12-0 |
| 350S162-68 | 12-2 |
10-10 |
14-9 |
12-10 |
14-9 |
12-10 |
| 550S162-33 | 10-11 | 9-10 | 15-7 | 12-0 | 16-10 | 12-0 |
| 550S162-43 | 11-8 |
10-6 |
16-10 |
14-10 |
18-4 |
16-0 |
| 550S162-54 | 12-7 |
11-3 |
18-0 |
16-2 |
19-4 |
17-2 |
| 550S162-68 | 13-7 | 12-1 | 19-3 | 17-3 | 20-6 | 18-5 |
| 800S162-33 | — |
— |
— |
— |
— |
— |
| 800S162-43 | 13-1 |
11-9 |
18-9 |
16-9 |
21-2 |
18-7 |
| 800S162-54 | 13-11 | 12-6 | 20-1 | 18-1 | 21-5 | 20-5 |
| 800S162-68 | 14-11 | 13-4 | 21-4 | 19-2 | 22-9 | 21-9 |
| 1000S162-43 | — |
— |
— |
— |
— |
— |
| 1000S162-54 | 14-10 | 13-4 | 21-4 | 19-2 | 22-8 | 21-8 |
| 1000S162-68 | 15-10 | 14-3 | 22-9 | 20-5 | 24-3 | 23-3 |
| 1200S162-43 | — | — | — | — | — | — |
| 1200S162-54 | — | — | — | — | — | — |
| 1200S162-68 | 16-8 | 14-11 | 23-11 | 21-7 | 25-5 | 24-5 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 pound per square foot = 0.0479 kPa. a. Deflection criterion: L /240 for total loads. b. Ceiling dead load = 5 psf. c. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses. d. Listed allowable spans are not applicable for 350S162-33, 550S162-33, 550S162-43 and 800S162-43 continuous joist members.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ROOF-CEILING CONSTRUCTION
| TABLE R804.3.1.1(2) CEILING JOIST SPANS 20 PSF LIVE LOAD (LIMITED ATTIC STORAGE)a, b, c, d | ||||||
|---|---|---|---|---|---|---|
| MEMBER DESIGNATION |
ALLOWABLE SPAN (feet - inches) | ALLOWABLE SPAN (feet - inches) | ALLOWABLE SPAN (feet - inches) | ALLOWABLE SPAN (feet - inches) | ALLOWABLE SPAN (feet - inches) | ALLOWABLE SPAN (feet - inches) |
| MEMBER DESIGNATION |
Lateral Support of Top (Compression) Flange | Lateral Support of Top (Compression) Flange | Lateral Support of Top (Compression) Flange | Lateral Support of Top (Compression) Flange | Lateral Support of Top (Compression) Flange | Lateral Support of Top (Compression) Flange |
| MEMBER DESIGNATION |
Unbraced | Unbraced | Midspan Bracing | Midspan Bracing | Third-point Bracing | Third-point Bracing |
| MEMBER DESIGNATION |
Ceiling Joist Spacing (inches) | Ceiling Joist Spacing (inches) | Ceiling Joist Spacing (inches) | Ceiling Joist Spacing (inches) | Ceiling Joist Spacing (inches) | Ceiling Joist Spacing (inches) |
| MEMBER DESIGNATION |
16 |
24 |
16 |
24 |
16 |
24 |
| 350S162-33 | 8-0 |
6-5 |
9-2 |
7-5 |
9-11 |
7-5 |
| 350S162-43 | 8-11 |
7-8 |
10-9 |
8-9 |
10-0 |
9-6 |
| 350S162-54 | 9-7 | 8-7 | 11-7 | 10-2 | 11-7 | 10-2 |
| 350S162-68 | 10-4 |
9-3 |
12-5 |
10-10 |
12-5 |
10-10 |
| 550S162-33 | 9-5 |
6-11 |
10-5 |
6-11 |
10-5 |
6-11 |
| 550S162-43 | 10-2 |
9-2 |
14-2 |
11-8 |
15-2 |
11-8 |
| 550S162-54 | 10-10 |
9-9 |
15-7 |
14-0 |
16-7 |
14-5 |
| 550S162-68 | 11-8 | 10-5 | 16-7 | 14-10 | 17-9 | 15-6 |
| 800S162-33 | — |
— |
— |
— |
— |
— |
| 800S162-43 | 11-4 | 10-2 | 16-1 | 11-0 | 16-6 | 11-0 |
| 800S162-54 | 12-0 |
10-10 |
17-4 |
15-7 |
18-7 |
17-7 |
| 800S162-68 | 12-10 | 11-6 | 18-6 | 16-7 | 19-11 | 18-11 |
| 1000S162-43 | — | — | — | — | — | — |
| 1000S162-54 | 12-10 |
11-7 |
18-5 |
16-6 |
19-8 |
18-8 |
| 1000S162-68 | 13-8 | 12-3 | 19-8 | 17-9 | 21-1 | 20-1 |
| 1200S162-43 | — | — | — | — | — | — |
| 1200S162-54 | — | — | — | — | — | — |
| 1200S162-68 | 14-5 | 12-11 | 20-9 | 18-7 | 22-0 | 21-0 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm, 1 pound per square foot = 0.0479 kPa. a. Deflection criterion: L/240 for total loads. b. Ceiling deal load = 5 psf. c. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses. d. Listed allowable spans are not applicable for 350S162-33, 350S162-43, 550S162-33, 550S162-43 and 800S162-43 continuous joist members.
ound per square foot = 0.0479 kPa. a. Deflection criterion: L/240 for total loads. b. Ceiling deal load = 5 psf. c. Minimum Grade 33 ksi steel shall be used for 33 mil and 43 mil thicknesses. Minimum Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses. d. Listed allowable spans are not applicable for 350S162-33, 350S162-43, 550S162-33, 550S162-43 and 800S162-43 continuous joist members.
| TABLE R804.3.1.1(3) NUMBER OF SCREWS REQUIRED FOR CEILING JOIST TO ROOF RAFTER CONNECTIONa | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ROOF SLOPE | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS | NUMBER OF SCREWS |
| ROOF SLOPE | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) | Building width (feet) |
| ROOF SLOPE | 24 | 24 | 24 | 24 | 28 | 28 | 28 | 28 | 32 | 32 | 32 | 32 | 36 | 36 | 36 | 36 | 40 | 40 | 40 | 40 |
| ROOF SLOPE | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) |
| ROOF SLOPE | 20 | 30 | 50 | 70 | 20 | 30 | 50 | 70 | 20 | 30 | 50 | 70 | 20 | 30 | 50 | 70 | 20 | 30 | 50 | 70 |
| 3/12 | 5 | 6 | 9 | 11 | 5 | 7 | 10 | 13 | 6 | 8 | 11 | 15 | 7 | 8 | 13 | 17 | 8 | 9 | 14 | 19 |
| 4/12 | 4 | 5 | 7 | 9 | 4 | 5 | 8 | 10 | 5 | 6 | 9 | 12 | 5 | 7 | 10 | 13 | 6 | 7 | 11 | 14 |
| 5/12 | 3 | 4 | 6 | 7 | 4 | 4 | 6 | 8 | 4 | 5 | 7 | 10 | 5 | 5 | 8 | 11 | 5 | 6 | 9 | 12 |
| 6/12 | 3 | 3 | 5 | 6 | 3 | 4 | 6 | 7 | 4 | 4 | 6 | 8 | 4 | 5 | 7 | 9 | 4 | 5 | 8 | 10 |
| 7/12 | 3 | 3 | 4 | 6 | 3 | 3 | 5 | 7 | 3 | 4 | 6 | 7 | 4 | 4 | 6 | 8 | 4 | 5 | 7 | 9 |
| 8/12 | 2 | 3 | 4 | 5 | 3 | 3 | 5 | 6 | 3 | 4 | 5 | 7 | 3 | 4 | 6 | 8 | 4 | 4 | 6 | 8 |
| 9/12 | 2 | 3 | 4 | 5 | 3 | 3 | 4 | 6 | 3 | 3 | 5 | 6 | 3 | 4 | 5 | 7 | 3 | 4 | 6 | 8 |
| 10/12 | 2 | 2 | 4 | 5 | 2 | 3 | 4 | 5 | 3 | 3 | 5 | 6 | 3 | 3 | 5 | 7 | 3 | 4 | 6 | 7 |
| 11/12 | 2 | 2 | 3 | 4 | 2 | 3 | 4 | 5 | 3 | 3 | 4 | 6 | 3 | 3 | 5 | 6 | 3 | 4 | 5 | 7 |
| 12/12 | 2 | 2 | 3 | 4 | 2 | 3 | 4 | 5 | 2 | 3 | 4 | 5 | 3 | 3 | 5 | 6 | 3 | 4 | 5 | 7 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kPa. a. Screws shall be No. 10.
478 2019 CALIFORNIA RESIDENTIAL CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ROOF-CEILING CONSTRUCTION
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ROOF-CEILING CONSTRUCTION
480 2019 CALIFORNIA RESIDENTIAL CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
R804.3.2.1 Minimum roof rafter sizes. Roof rafter size and thickness shall be determined in accordance with the limits set forth in Table R804.3.2.1(1) based on the horizontal projection of the roof rafter span. For determination of roof rafter sizes, reduction of roof spans shall be permitted where a roof rafter support brace is installed in accordance with Section R804.3.2.2. The reduced roof rafter span shall be taken as the larger of the distances from the roof rafter support brace to the ridge or to the heel measured horizontally.
For the purpose of determining roof rafter sizes in Table R804.3.2.1(1), ultimate design wind speeds shall be converted to equivalent ground snow loads in accordance with Table R804.3.2.1(2). Roof rafter sizes shall be based on the higher of the ground snow load or the equivalent snow load converted from the ultimate design wind speed.
R804.3.2.1.1 Eave overhang. Eave overhangs shall not exceed 24 inches (610 mm) measured horizontally.
R804.3.2.1.2 Rake overhangs. Rake overhangs shall not exceed 12 inches (305 mm) measured hori
ROOF-CEILING CONSTRUCTION
zontally. Outlookers at gable endwalls shall be installed in accordance with Figure R804.3.2.1.2.
R804.3.2.2 Roof rafter support brace. Where used to reduce roof rafter spans in determining roof rafter sizes, a roof rafter support brace shall meet all of the following conditions:
Minimum 350S162-33 C-shaped brace member with maximum length of 8 feet (2438 mm).
Minimum brace member slope of 45 degrees (0.785 rad) to the horizontal.
Minimum connection of brace to a roof rafter and ceiling joist with four No.10 screws at each end.
Maximum 6 inches (152 mm) between brace/ceiling joist connection and load-bearing wall below.
Each roof rafter support brace greater than 4 feet (1219 mm) in length, shall be braced with a supplemental brace having a minimum size of 350S162-33 or 350T162-33 such that the maximum unsupported length of the roof rafter support brace is 4 feet (1219 mm). The supplemental brace shall be continuous and shall be connected to each roof rafter support brace using two No. 8 screws.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ROOF-CEILING CONSTRUCTION
TABLE R804.3.2.1(1) ROOF RAFTER SPANS a, b, c, d
| MEMBER DESIGNATION |
ALLOWABLE SPAN MEASURED HORIZONTALLY (feet - inches) | |||||||
|---|---|---|---|---|---|---|---|---|
| MEMBER DESIGNATION |
Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) |
| MEMBER DESIGNATION |
20 | 20 | 30 | 30 | 50 | 50 | 70 | 70 |
| MEMBER DESIGNATION |
Rafter spacing (inches) | Rafter spacing (inches) | Rafter spacing (inches) | Rafter spacing (inches) | Rafter spacing (inches) | Rafter spacing (inches) | Rafter spacing (inches) | Rafter spacing (inches) |
| MEMBER DESIGNATION |
16 | 24 | 16 | 24 | 16 | 24 | 16 | 24 |
| 550S162-33 | 13-11 | 11-4 | 11-9 | 9-7 | 9-5 | 7-8 | 8-1 | 6-7 |
| 550S162-43 | 15-9 | 13-8 | 14-3 | 11-8 | 11-4 | 9-3 | 9-9 | 7-11 |
| 550S162-54 | 16-11 | 14-10 | 15-3 | 13-4 | 13-3 | 11-7 | 12-0 | 10-6 |
| 550S162-68 | 18-2 | 15-10 | 16-5 | 14-4 | 14-3 | 12-5 | 12-11 | 11-3 |
| 800S162-33 | 16-4 | 13-4 | 13-11 | 11-4 | 11-1 | 9-0 | 9-6 | 6-7 |
| 800S162-43 | 19-7 | 16-0 | 16-8 | 13-7 | 13-4 | 10-10 | 11-5 | 9-4 |
| 800S162-54 | 22-9 | 19-11 | 20-7 | 17-11 | 17-10 | 4-9 | 15-6 | 12-7 |
| 800S162-68 | 24-7 | 21-6 | 22-2 | 19-5 | 19-3 | 16-10 | 17-5 | 14-8 |
| 1000S162-43 | 22-2 | 18-1 | 18-10 | 15-4 | 15-1 | 12-4 | 12-11 | 10-7 |
| 1000S162-54 | 27-1 | 23-8 | 24-6 | 20-9 | 20- | 16-8 | 17-6 | 14-3 |
| 1000S162-68 | 29-5 | 25-8 | 26-6 | 23-2 | 23-0 | 19-6 | 20-6 | 16-9 |
| 1200S162-54 | 31-3 | 27-0 | 28-1 | 22-11 | 22-6 | 18-4 | 19-4 | 15-9 |
| 1200S162-68 | 34-0 | 29-8 | 30-8 | 26-9 | 26-6 | 21-7 | 22-8 | 18-6 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. a. Table provides maximum horizontal rafter spans in feet and inches for slopes between 3:12 and 12:12. b. Deflection criteria: L/240 for live loads and L/180 for total loads. c. Roof dead load = 12 psf. d. Grade 33 ksi steel is permitted to be used for 33 mil and 43 mil thicknesses. Grade 50 ksi steel shall be used for 54 and 68 mil thicknesses.
| TABLE R804.3.2.1(2) ULTIMATE DESIGN WIND SPEED TO EQUIVALENT SNOW LOAD CONVERSION | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| ULTIMATE WIND SPEED AND EXPOSURE |
ULTIMATE WIND SPEED AND EXPOSURE |
EQUIVALENT GROUND SNOW LOAD (psf) | EQUIVALENT GROUND SNOW LOAD (psf) | EQUIVALENT GROUND SNOW LOAD (psf) | EQUIVALENT GROUND SNOW LOAD (psf) | EQUIVALENT GROUND SNOW LOAD (psf) | EQUIVALENT GROUND SNOW LOAD (psf) | EQUIVALENT GROUND SNOW LOAD (psf) | EQUIVALENT GROUND SNOW LOAD (psf) | EQUIVALENT GROUND SNOW LOAD (psf) | EQUIVALENT GROUND SNOW LOAD (psf) |
| ULTIMATE WIND SPEED AND EXPOSURE |
ULTIMATE WIND SPEED AND EXPOSURE |
Roof slope | Roof slope | Roof slope | Roof slope | Roof slope | Roof slope | Roof slope | Roof slope | Roof slope | Roof slope |
| Exposure | Wind speed (mph) |
3:12 | 4:12 | 5:12 | 6:12 | 7:12 | 8:12 | 9:12 | 10:12 | 11:12 | 12:12 |
| B | 115 | 20 | 20 | 20 | 20 | 30 | 20 | 30 | 30 | 30 | 50 |
| B | 120 | 20 | 20 | 20 | 20 | 30 | 30 | 30 | 30 | 30 | 50 |
| B | 130 | 20 | 20 | 20 | 20 | 30 | 30 | 30 | 50 | 50 | 50 |
| B | <140 | 20 | 20 | 20 | 20 | 30 | 50 | 50 | 50 | 50 | 50 |
| C | 115 | 20 | 20 | 20 | 20 | 30 | 30 | 30 | 50 | 50 | 50 |
| C | 120 | 20 | 20 | 20 | 20 | 30 | 30 | 50 | 50 | 50 | 50 |
| C | 130 | 20 | 20 | 20 | 30 | 30 | 50 | 50 | 50 | 50 | 70 |
| C | <140 | 30 | 30 | 30 | 50 | 50 | 50 | 70 | 70 | 70 | — |
For SI: 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa.
482 2019 CALIFORNIA RESIDENTIAL CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
R804.3.2.3 Roof rafter splice. Roof rafters shall not be spliced.
R804.3.2.4 Roof rafter to ceiling joist and ridge mem- ber connection. Roof rafters shall be connected to a parallel ceiling joist to form a continuous tie between exterior walls in accordance with Figure R804.3.1.1 and Table R804.3.1.1(3). Ceiling joists shall be connected to the top track of the load-bearing wall in accordance with Table R804.3, either with the required number of No. 10 screws applied through the flange of the ceiling joist or by using a 54-mil (1.37 mm) clip angle with the required number of No.10 screws in each leg. Roof rafters shall be connected to a ridge member with a minimum 2-inch by 2-inch (51 mm by 51 mm) clip angle fastened with No. 10 screws to the ridge member in accordance with Figure R804.3.2.4 and Table R804.3.2.4. The clip angle shall have a steel thickness equivalent to or greater than the roof rafter thickness and shall extend the depth of the roof rafter member to the extent possible. The ridge member shall be fabricated from a C-shaped member and a track section that shall have a minimum size and steel thickness equivalent to or greater than that of adjacent roof rafters and shall be installed in accordance with
ROOF-CEILING CONSTRUCTION
Figure R804.3.2.4. The ridge member shall extend the full depth of the sloped roof rafter cut.
R804.3.2.5 Roof rafter bottom flange bracing. The bottom flanges of roof rafters shall be continuously braced, at a maximum spacing of 8 feet (2440 mm) as measured parallel to the roof rafters, with one of the following members:
Minimum 33-mil (0.84 mm) C-shaped member.
Minimum 33-mil (0.84 mm) track section.
Minimum 1 1 /2-inch by 33-mil (38 mm by 0.84 mm) steel strap.
The bracing element shall be fastened to the bottom flange of each roof rafter with one No. 8 screw and shall be fastened to blocking with two No. 8 screws. Blocking shall be installed between roof rafters in-line with the continuous bracing at a maximum spacing of 12 feet (3658 mm) measured perpendicular to the roof rafters. The ends of continuous bracing shall be fastened to blocking or anchored to a stable building component with two No. 8 screws.
TABLE R804.3.2.4 SCREWS REQUIRED AT EACH LEG OF CLIP ANGLE FOR ROOF RAFTER TO RIDGE MEMBER CONNECTION a
| BUILDING WIDTH (feet) | NUMBER OF SCREWS | |||
|---|---|---|---|---|
| BUILDING WIDTH (feet) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) | Ground snow load (psf) |
| BUILDING WIDTH (feet) | 0 to 20 | 21 to 30 | 31 to 50 | 51 to 70 |
| 24 | 2 | 2 | 3 | 4 |
| 28 | 2 | 3 | 4 | 5 |
| 32 | 2 | 3 | 4 | 5 |
| 36 | 3 | 3 | 5 | 6 |
| 40 | 3 | 4 | 5 | 7 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479 kPa. a. Screws shall be No. 10 minimum.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ROOF-CEILING CONSTRUCTION
R804.3.3 Cutting and notching. Flanges and lips of loadbearing, cold-formed steel roof framing members shall not be cut or notched.
R804.3.4 Headers. Roof-ceiling framing above wall openings shall be supported on headers. The allowable spans for headers in load-bearing walls shall not exceed the values set forth in Section R603.6 and Tables R603.6(1) through R603.6(6).
R804.3.5 Framing of openings in roofs and ceilings. Openings in roofs and ceilings shall be framed with header and trimmer joists. Header joist spans shall not exceed 4 feet (1219 mm) in length. Header and trimmer joists shall be fabricated from joist and track members having a minimum size and thickness equivalent to the adjacent ceiling joists or roof rafters and shall be installed in accordance with Figures R804.3.5(1) and R804.3.5(2). Each header joist shall be connected to trimmer joists with not less than four 2-inch by 2-inch (51 by 51 mm) clip angles. Each clip angle shall be fastened to both the header and trimmer joists with four No. 8 screws, evenly spaced, through each leg of the clip angle. The steel thickness of the clip angles shall be not less than that of the ceiling joist or roof rafter. Each track section for a built-up header or trimmer joist shall extend the full length of the joist (continuous).
R804.3.6 Roof trusses. Cold-formed steel trusses shall be designed and installed in accordance with AISI S240. In the absence of specific bracing requirements, trusses shall be braced in accordance with accepted industry practices, such as the SBCA Cold-Formed Steel Building Compo- nent Safety Information (CFSBCSI) Guide to Good Prac- tice for Handling, Installing & Bracing of Cold-Formed Steel Trusses . Trusses shall be connected to the top track of the load-bearing wall in accordance with Table R804.3,
either with two No. 10 screws applied through the flange of the truss or by using a 54-mil (1.37 mm) clip angle with two No. 10 screws in each leg.
R804.3.7 Ceiling and roof diaphragms. Ceiling and roof diaphragms shall be in accordance with this section.
R804.3.7.1 Ceiling diaphragms. At gable endwalls a ceiling diaphragm shall be provided by attaching a minimum 1 /2-inch (12.7 mm) gypsum board or a minimum 3/8-inch (9.5 mm) wood structural panel sheathing, that complies with Section R803, to the bottom of ceiling joists or roof trusses and connected to wall framing in accordance with Figures R804.3.7.1(1) and R804.3.7.1(2), unless studs are designed as full height without bracing at the ceiling. Flat blocking shall consist of C-shaped or track section with a minimum thickness of 33 mils (0.84 mm). For a gypsum board sheathed ceiling, the diaphragm length shall be in accordance with Table R804.3.7.1. For a wood structural panel sheathed ceiling, the diaphragm length shall be not less than 12 feet (3658 mm) for building widths less than 36 feet (10 973 mm), or not less than 14 feet (4267 mm) for building widths greater than or equal to 36 feet (10 973 mm).
The ceiling diaphragm shall be secured with screws spaced at a maximum 6 inches (152 mm) o.c. at panel edges and a maximum 12 inches (305 mm) o.c. in the field. The required lengths in Table R804.3.7.1 for gypsum board sheathed ceiling diaphragms shall be permitted to be multiplied by 0.35 if all panel edges are blocked. Multiplying the required lengths in Table R804.3.7.1 for gypsum board sheathed ceiling diaphragms by 0.9 shall be permitted if all panel edges are secured with screws spaced at 4 inches (102 mm) o.c.
484 2019 CALIFORNIA RESIDENTIAL CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ROOF-CEILING CONSTRUCTION
TABLE R804.3.7.1 REQUIRED LENGTHS FOR CEILING DIAPHRAGMS AT GABLE ENDWALLS
GYPSUM BOARD SHEATHED, CEILING HEIGHT = 8 FEET a, b, c, d, e, f, g
| EXPOSURE CATEGORY | ULTIMATE DESIGN WIND SPEED (mph) | ||||||
|---|---|---|---|---|---|---|---|
| B | B | 115 | 120 | 130 | < 140 | — | — |
| C | C | — | — | 115 | 120 | 130 | < 140 |
| Roof pitch | Building endwall width (feet) | Minimum diaphragm length (feet) | Minimum diaphragm length (feet) | Minimum diaphragm length (feet) | Minimum diaphragm length (feet) | ||
| 3:12 to 6:12 |
24 - 28 | 16 | 18 | 24 | 26 | 30 | 34 |
| 3:12 to 6:12 |
> 28 - 32 | 20 | 20 | 26 | 32 | 34 | 40 |
| 3:12 to 6:12 |
> 32 - 36 | 24 | 26 | 30 | 36 | 42 | 46 |
| 3:12 to 6:12 |
> 36 - 40 | 26 | 28 | 36 | 40 | 48 | 52 |
| 6:12 to 9:12 |
> 24 - 28 | 20 | 20 | 26 | 30 | 34 | 38 |
| 6:12 to 9:12 |
> 28 - 32 | 24 | 26 | 30 | 36 | 42 | 46 |
| 6:12 to 9:12 |
> 32 - 36 | 26 | 30 | 38 | 42 | 48 | 54 |
| 6:12 to 9:12 |
> 36 - 40 | 30 | 34 | 40 | 50 | 56 | 62 |
| 9:12 to 12:12 |
> 24 - 28 | 22 | 24 | 30 | 34 | 38 | 44 |
| 9:12 to 12:12 |
> 28 - 32 | 26 | 28 | 36 | 40 | 46 | 52 |
| 9:12 to 12:12 |
> 32 - 36 | 30 | 32 | 40 | 48 | 54 | 62 |
| 9:12 to 12:12 |
> 36 - 40 | 36 | 38 | 48 | 56 | 64 | 72 |
For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa, 1 mile per hour = 0.447 m/s, 1 foot = 304.8 mm, 1 mil = 0.0254 mm. a. Ceiling diaphragm is composed of 1 /2-inch gypsum board (min. thickness) secured with screws spaced at 6 inches o.c. at panel edges and 12 inches o.c.
infield. Use No. 8 screws (min.) where framing members have a designation thickness of 54 mils or less and No. 10 screws (min.) where framing members have a designation thickness greater than 54 mils. b. Maximum aspect ratio (length/width) of diaphragms is 2:1. c. Building width is in the direction of horizontal framing members supported by the wall studs. d. Required diaphragm lengths are to be provided at each end of the structure. e. Multiplying required diaphragm lengths by 0.35 is permitted if all panel edges are blocked. f. Multiplying required diaphragm lengths by 0.9 is permitted if all panel edges are secured with screws spaced at 4 inches o.c. g. To determine the minimum diaphragm length for buildings with ceiling heights of 9 feet or 10 feet values in this table shall be multiplied by 1.15.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ROOF-CEILING CONSTRUCTION
486 2019 CALIFORNIA RESIDENTIAL CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
R804.3.7.2 Roof diaphragm. A roof diaphragm shall be provided by attaching not less than 3 /8-inch (9.5 mm) wood structural panel that complies with Section R803 to roof rafters or truss top chords in accordance with Table R804.3. Buildings with 3:1 or larger plan aspect ratio and with roof rafter slope (pitch) of 9:12 or larger shall have the roof rafters and ceiling joists blocked in accordance with Figure R804.3.7.2.
R804.3.8 Roof tie-down. Roof assemblies shall be connected to walls below in accordance with Table R804.3. A continuous load path shall be provided to transfer uplift loads to the foundation.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Residential Code (Title 24, Part 2.5)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Chapter 1 — SCOPE AND APPLICATION
- Chapter 3 — BUILDING PLANNING
- Chapter 4 — FOUNDATIONS
- Chapter 5 — FLOORS
- Chapter 6 — WALL CONSTRUCTION
- Chapter 7 — WALL COVERING
▸Chapter 8 — ROOF-CEILING CONSTRUCTION
- Chapter 9 — ROOF ASSEMBLIES
- Chapter 10 — CHIMNEYS AND FIREPLACES
- Chapter 44 — REFERENCED STANDARDS
- Appendix F — RADON CONTROL METHODS
- Appendix H — PATIO COVERS
- Appendix I — PRIVATE SEWAGE DISPOSAL
- Appendix J — EXISTING BUILDINGS AND STRUCTURES
- Appendix K — SOUND TRANSMISSION
- Appendix L — PERMIT FEES
- Appendix O — AUTOMATIC VEHICULAR GATES
- Appendix Q — TINY HOUSES
- Appendix R — LIGHT STRAW-CLAY CONSTRUCTION
- Appendix S — STRAWBALE CONSTRUCTION
- Appendix T — SOLAR-READY PROVISIONS—DETACHED ONE- AND
- Appendix V — SWIMMING POOL SAFETY ACT
- Appendix W — AREAS PROTECTED BY THE FACILITIES
- Appendix X — EMERGENCY HOUSING