Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
1503.2 System Requirements.
California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Gray water shall be permitted to be diverted away from a sewer or private sewage disposal system, and discharge to a subsurface irrigation or subsoil irrigation system , or disposal field . The gray water shall be permitted to discharge to a mulch basin for residen- tial occupancies . Gray water shall not be used to irrigate root crops or food crops intended for human consumption that comes in contact with soil.
1503.2.1 Surge Capacity. Gray water systems shall be designed to have the capacity to accommodate peak
ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
flow rates and distribute the total amount of estimated gray water on a daily basis to a subsurface irrigation field, subsoil irrigation field , disposal field, or mulch basin without surfacing, ponding, or runoff. A surge tank is required for systems that are unable to accommodate peak flow rates and distribute the total amount of gray water by gravity drainage. The water discharge for gray water systems shall be determined in accordance with Section 1503.8.1 or Section 1503.8.2. Exception: It is not the intent of this section to require that all gray water must be handled by an irrigation field or disposal field. It is acceptable for excess gray water to be diverted to the building sewer through a diverter valve or overflow drain as permitted in this chapter. 1503.2.2 Diversion. The gray water system shall connect to the sanitary drainage system downstream of fixture traps and vent connections through an approved diverter valve. The diverter valve shall be installed in a readily accessible location and clearly indicate the direction of flow. Exception: [HCD 1] A clothes washer system in com- pliance with Section 1503.1.1. 1503.2.3 Backwater Valves. Gray water drains subject to backflow shall be provided with a backwater valve at the point of connection to the building sewer system, so located as to be accessible for inspection and maintenance. 1503.2.4 Rainwater Diversion Valves. Rainwater diversion valves ranging from 6 inches (150 mm) to 12 inches (300 mm) in diameter shall comply with IAPMO IGC 352. Valves shall be accessible and include a filter located upstream of the valve when required.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
▸Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
Overview- 1501.1 Applicability [BSC-CG, DWR & HCD 1] . The
- 1501.2 System Design. Alternate water source systems
- 1501.3 Permit [BSC-CG, HCD 1, DWR] . It shall be unlawful for …
- 1501.4 Component Identification. System components
- 1501.5 Maintenance and Inspection [BSC-CG, HCD
- 1501.6 Operation and Maintenance Manual [BSC-CG,
- 1501.7 Minimum Water Quality Requirements [BSC-
- 1501.8 Material Compatibility. Alternate water source systems …
- 1501.9 Signage [BSC-CG, HCD 1, HCD 2, HCD 1-AC].
- 1501.10 System Controls. Controls for pumps, valves, and
- 1502.1 General. Alternate water source systems shall be
- 1502.2 Supply System Inspection and Test. Alternate
- 1502.3 Cross-Connection Inspection and Testing. An
- 1502.4 Separation Requirements. Underground alternate water so…
- 1502.5 Abandonment. Alternate water source systems that
- 1502.6 Sizing. Unless otherwise provided for in this chapter, …
- 1503.1 General. The provisions of this section shall apply
- 1503.2 System Requirements. Gray water shall be permitted to b…
- 1503.3 Connections to Potable and Reclaimed (Recy-
- 1503.4 Location. No gray water system or part thereof shall
- 1503.5 Plot Plan Submission. No permit for a gray water
- 1503.6 Prohibited Location. Where there is insufficient
- 1503.7 Drawings and Specifications. The Authority
- 1503.8 Procedure for Estimating Gray Water Dis-
- 1503.9 Gray Water System Components. Gray water
- 1504.1 General. Irrigation or disposal fields shall be permitt…
- 1504.3 Determination of Maximum Absorption
- 1504.4 Groundwater Level. No excavation for an irrigation fiel…
- 1504.2 Required Area of Subsurface Irrigation
- 1504.5 Irrigation, Disposal Field and Mulch Basin Con-
- 1504.6 Reserved.
- 1504.7 Reserved .
- 1504.8 Gray Water System Color and Marking Infor-
- 1504.9 Other Collection and Distribution Systems.
- 1504.10 Testing. Building drains and vents for gray water
- 1504.11 Maintenance. Gray water systems and components shall b…
- 1505.1 General. The provisions of Section 1505.0 through
- 1505.2 Permit. It shall be unlawful for a person to construct,
- 1505.3 System Changes. No changes or connections shall
- 1505.4 Connections to Potable or Recycled Water
- 1505.5 Initial Cross-Connection Test. A cross-connection test …
- 1505.6 Recycled Water Supply System Materials.
- 1505.7 Recycled Water Supply System Color and
- 1505.8 Valves. Valves, except fixture supply control valves,
- 1505.9 Hose Bibbs. Hose bibbs shall not be allowed on
- 1505.10 Required Appurtenances. The recycled water
- 1505.11 Pipe Separation in Trenches . Reclaimed (recycled) wat…
- 1505.12 Signage . Signs in rooms and water closet tanks in
- 1505.13 Inspection and Testing. Recycled water supply
- 1505.14 Minimum Water Quality Requirements for
- 1505.15 Maintenance and Inspection. Recycled water
- 1506.1 General. The provisions of this section shall apply
- 1506.2 Plumbing Plan Submission. No permit for an
- 1506.3 System Changes. No changes or connections shall
- 1506.4 Connections to Potable or Recycled Water
- 1506.5 Initial Cross-Connection Test. A cross-connection test …
- 1506.6 On-Site Treated Nonpotable Gray Water Sys-
- 1506.7 On-Site Treated Nonpotable Gray Water
- 1506.8 On-Site Treated Nonpotable Gray Water Sys-
- 1506.9 Design and Installation. The design and installation of…
- 1506.10 Valves. Valves, except fixture supply control
- 1506.11 Signs. Signs in buildings using on-site treated nonpot…
- 1506.12 Inspection and Testing. On-site treated nonpotable gra…
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …