Chapter 8 — INDIRECT WASTES

814.2 Condensate Control.

California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

Where an equipment or appliance is installed in a space where damage is capable of resulting from condensate overflow, other than damage to replaceable lay-in ceiling tiles, a drain line shall be provided and shall be drained in accordance with Section 814.1. An additional protection method for condensate overflow shall be provided in accordance with one of the following: (1) A water level detecting device that will shut off the

equipment or appliance in the event the primary drain is

EQUIPMENT CAPACITY IN TONS
OF REFRIGERATION
MINIMUM CONDENSATE PIPE
DIAMETER
(inches)

34




14


12




The size of condensate waste pipes is for one unit or a combination of units, or as recommended by the manufacturer. The capacity of waste pipes assumes a 1 ⁄8 inch per foot (10.4 mm/m) or 1 percent slope, with the pipe running threequarters full at the following pipe conditions:



DB
WB
90°F
73°F
For SI units: °C = (°F-32)/1.8


DB
WB
75°F
62.5°F

tions shall be approved by the Authority Having Jurisdiction.

(1) A water level detecting device that will shut off the

equipment or appliance in the event the primary drain is blocked. (2) An additional watertight pan of corrosion-resistant mate rial, with a separate drain line, installed beneath the cool

Air-conditioning waste pipes shall be constructed of materials specified in Chapter 7.

(2) An additional watertight pan of corrosion-resistant mate rial, with a separate drain line, installed beneath the cooling coil, unit, or the appliance to catch the overflow condensate due to a clogged primary condensate drain. (3) An additional drain line at a level that is higher than the

primary drain line connection of the drain pan.

(3) An additional drain line at a level that is higher than the

primary drain line connection of the drain pan. (4) An additional watertight pan of corrosion-resistant mate rial with a water level detection device installed beneath

(4) An additional watertight pan of corrosion-resistant mate rial with a water level detection device installed beneath the cooling coil, unit, or the appliance to catch the overflow condensate due to a clogged primary condensate drain and to shut off the equipment. The additional pan or the additional drain line connection shall be provided with a drain pipe of not less than 3 ⁄4 of an inch (20 mm) nominal pipe size, discharging at a point that is readily observed.

814.2.1 Protection of Appurtenances. Where insulation or appurtenances are installed where damage is capable of resulting from a condensate drain pan overfill, such installations shall occur above the rim of the drain pan with supports. Where the supports are in contact with the condensate waste, the supports shall be of approved corrosion-resistant material.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
    Overview
    1. 801.2 Air Gap or Air Break Required. Indirect waste piping sha…
    2. 801.3 Food and Beverage Handling Establishments. Establishment…
    3. 801.4 Bar and Fountain Sink Traps. Where the sink in a
    4. 801.5 Connections from Water Distribution System. Indirect was…
    5. 801.6 Sterilizers. Lines, devices, or apparatus such as stills,
    6. 801.7 Drip or Drainage Outlets. Appliances, devices, or
    7. 803.2 Copper and Copper Alloys. Joints and connections in copp…
    8. 803.3 Pipe Size and Length. Except as hereinafter provided, th…
    9. 804.0 Indirect Waste Receptors.804.1 Standpipe Receptors. Plum…
    10. 805.0 Pressure Drainage Connections.805.1 General. Indirect wa…
    11. 807.2 Undiluted Condensate Waste. Where undiluted
    12. 808.0 Cooling Water.808.1 General. Where permitted by the Auth…
    13. 810.0 Steam and Hot Water Drainage Condensers
    14. 807.3 Domestic Dishwashing Machine. No domestic
    15. 810.2 Sumps, Condensers, and Intercepting Tanks. Sumps, conden…
    16. 810.3 Cleaning. Sumps and condensers shall be provided
    17. 810.4 Strainers. An indirect waste interceptor is receiving
    18. 811.0 Chemical Wastes.811.1 Pretreatment. Chemical or liquid i…
    19. 811.2 Waste and Vent Pipes. Each waste pipe receiving or
    20. 811.3 Joining Materials. Joining materials shall be of
    21. 811.4 Access. Where practicable, the piping shall be readily a…
    22. 811.5 Permanent Record. The owner shall make and keep
    23. 811.6 Chemical Vent. No chemical vent shall intersect
    24. 811.7 Discharge. Chemical wastes shall be discharged in a
    25. 811.8 Diluted Chemicals. The provisions of this section
    26. 814.0 Condensate Waste and Control.814.1 Condensate Disposal. …
    27. 814.2 Condensate Control. Where an equipment or appliance is i…
    28. 814.3 Condensate Waste Pipe Material and Sizing. Condensate wa…
    29. 814.4 Appliance Condensate Drains. Condensate drain
    30. 814.5 Point of Discharge. Air-conditioning condensate
    31. 814.6 Condensate Waste from Air-Conditioning
    32. 814.7 Plastic Fittings. Female plastic screwed fittings shall
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.