Chapter 14 — FIRESTOP PROTECTION
1406.4 Field Installations.
California Plumbing Code (Title 24, Part 5) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
The Authority Having Jurisdiction shall compare the field installations with the documentation supplied by the installer to determine the following: (1) The required F ratings (1 hour, 2 hour, 3 hour, or 4 hour)
and T ratings (0 hour, 1 hour, 2 hour, 3 hour, or 4 hour)
(1) The required F ratings (1 hour, 2 hour, 3 hour, or 4 hour)
and T ratings (0 hour, 1 hour, 2 hour, 3 hour, or 4 hour) of the penetration firestop systems are at least the same as the hourly rating of the assembly being penetrated. (2) The penetrating firestop system includes the penetrating
item as documented through testing of the systems con
(2) The penetrating firestop system includes the penetrating
item as documented through testing of the systems conducted by an independent testing agency. (3) The penetrating firestop system is installed as tested.
306 2019 CALIFORNIA PLUMBING CODE
CALIFORNIA PLUMBING CODE – MATRIX ADOPTION TABLE
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
▸Chapter 14 — FIRESTOP PROTECTION
Overview- 1404.2 Fire-Resistance Rating. Where penetrating a fireresista…
- 1404.3 Firestop Systems. Penetrations shall be protected
- 1404.4 Connections. Where piping penetrates a rated
- 1404.5 Insulation and Coverings. Insulation and coverings on o…
- 1404.6 Sleeves. Where sleeves are used, the sleeves shall
- 1405.2 Fire-Resistance Rating. Where penetrating a fireresista…
- 1405.3 Firestop Systems. Penetrations shall be protected
- 1405.4 Connections. Where piping penetrates a rated
- 1405.5 Unshielded Couplings. Unshielded couplings
- 1405.6 Sleeves. Where sleeves are used, the sleeves shall
- 1405.7 Insulation and Coverings. Insulation and coverings on o…
- 1406.2 Examination. The Authority Having Jurisdiction
- 1406.3 Penetrations. The Authority Having Jurisdiction
- 1406.4 Field Installations. The Authority Having Jurisdiction …
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARD FOR PEX TUBING SYSTEMS FOR …
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR