Chapter 11 — STORM DRAINAGE

1105.1 Application — 2025 California Plumbing Code

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Plumbing Code (Title 24, Part 5) § 1105.1 · Effective January 1, 2026 · Official source: Building Standards Commission

Instead of sizing the storm drainage system in accordance with Section 1103.0, the roof drainage shall be permitted to be sized by controlled flow and storage of the storm water on the roof, provided the following conditions are met:

(1) The water from a 25-year frequency storm shall not be stored on the roof exceeding 24 hours. (2) During the storm, the water depth on the roof shall not exceed the depths specified in Table 1105.1(1). (3) Not less than two drains shall be installed in roof areas of 10 000 square feet (929 m [2] ) or less, and not less than one additional drain shall be installed for each 10 000 square feet (929 m [2] ) of roof area exceeding 10 000 square feet (929 m [2] ). (4) Each roof drain shall have a precalibrated, fixed (nonadjustable), and proportional weir (notched) in a standing water collar inside the strainer. No mechanical devices or valves shall be permitted. (5) Pipe sizing shall be based on the pre-calibrated rate of flow (gpm) (L/s) of the pre-calibrated weir for the maximum allowable water depth, and Table 1103.1 and Table 1103.2.

(6) The height of stones or other granular material above the waterproofed surface shall not be considered in water depth measurement, and the roof surface in the vicinity of the drain shall not be recessed to create a reservoir.

(7) Roof design, where controlled-flow roof drainage is used, shall be such that the design roof live load is not less than 30 lb/ft [2] (146 kg/m [2] ) to provide a safety factor exceeding the 15 lb/ft [2] (73 kg/m [2] ) represented by the depth of water stored on the roof in accordance with Table 1105.1(1). (8) Scuppers shall be provided in parapet walls. The distance of scupper bottoms above the roof level at the drains shall not exceed the maximum distances specified in Table 1105.1(2).

(9) Scupper openings shall be not less than 4 inches (102 mm) high and have a width equal to the circumference of

208 2025 CALIFORNIA PLUMBING CODE

STORM DRAINAGE

the roof drain required for the area served, sized in accordance with Table 1103.1.

(10)Flashings shall extend above the top of the scuppers.

(11)At a wall or parapet, 45 degree (0.79 rad) cants shall be installed.

(12)Separate storm and sanitary drainage systems shall be provided within the building.

(13)Calculations for the roof drainage system shall be submitted along with the plans to the Authority Having Jurisdiction for approval.

TABLE 1105.1(1) CONTROLLED-FLOW MAXIMUM ROOF WATER DEPTH

ROOF RISE*
(inches)
MAXIMUM WATER DEPTH AT
DRAIN
(inches)

Flat
3

2
4

4
5

6
6

For SI units: 1 inch = 25.4 mm

  • Vertical measurement from the roof surface at the drain to the highest point of the roof surface served by the drain, ignoring a local depression immediately adjacent to the drain.

TABLE 1105.1(2) DISTANCE OF SCUPPER BOTTOMS ABOVE ROOF

ROOF RISE*
(inches)
ABOVE ROOF LEVEL
AT DRAIN
(inches)

Flat
3

2
4

4
5

6
6

For SI units: 1 inch = 25.4 mm

  • Vertical measurement from the roof surface at the drain to the highest point of the roof surface served by the drain, ignoring a local depression immediately adjacent to the drain.