Chapter 7 — COMBUSTION AIR

701.6 Outdoor Combustion Air — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 701.6 · Effective January 1, 2026 · Official source: Building Standards Commission

Outdoor combustion air shall be provided through opening(s) to the outdoors in accor dance with the methods in Section 701.6.1 or Section 701.6.2. The minimum dimension of air openings shall not be less than

FIGURE 701.5

ALL COMBUSTION AIR FROM ADJACENT INDOOR SPACES

THROUGH INDOOR COMBUSTION AIR OPENINGS

[NFPA 54: FIGURE A.9.3.2.3(1)]

701.6.1 Two Permanent Openings Method. Two permanent openings, one commencing within 12 inches (305 mm) of the top of the enclosure and one commencing within 12 inches (305 mm) of the bottom of the enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors as follows:

(1) Where directly communicating with the outdoors or where communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/h (0.0005 m [2] /kW) of total input rating of all appliances in the enclosure.

[See Figure 701.6.1(1) and Figure 701.6.1(2)] (2) Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/h (0.001 m [2] /kW) of total input rating of all appliances in the enclosure. [See Figure 701.6.1(3)] [NFPA 54:9.3.3.1] 701.6.2 One Permanent Opening Method. One permanent opening, commencing within 12 inches (305 mm) of the top of the enclosure, shall be provided. The appliance shall have clearances of at least 1 inch (25.4 mm) from the sides and back and 6 inches (152 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors (see Figure 701.6.2) and shall have a minimum free area of the following: (1) One square inch per 3000 Btu/h (0.0007 m [2] /kW) of the total input rating of all appliances located in the enclosure.

(2) Not less than the sum of the areas of all vent connectors in the space. [NFPA 54:9.3.3.2]