Chapter 6 — BUILDING SERVICES AND SYSTEMS

Section 606

California Fire Code (Title 24, Part 9) · 2019 edition · updated 2026-09-10 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

ELEVATOR OPERATION, MAINTENANCE AND FIRE SERVICE KEYS

606.1 Emergency operation. Existing elevators with a travel

distance of 25 feet (7620 mm) or more shall comply with the requirements in Chapter 11. New elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with California Code of Regulations, Title 8, Division 1, Chapter 4, Subchapter 6, Elevator Safety Orders.

Exceptions & meaning →

606.2 Standby power. In buildings and structures where

standby power is required or furnished to operate an elevator, standby power shall be provided in accordance with Section 1203. Operation of the system shall be in accordance with Sections 606.2.1 through 606.2.4.

606.2.1 Manual transfer. Standby power shall be manually transferable to all elevators in each bank.

606.2.2 One elevator. Where only one elevator is installed, the elevator shall automatically transfer to standby power within 60 seconds after failure of normal power.

606.2.3 Two or more elevators. Where two or more elevators are controlled by a common operating system, all elevators shall automatically transfer to standby power within 60 seconds after failure of normal power where the standby power source is of sufficient capacity to operate all elevators at the same time. Where the standby power source is not of sufficient capacity to operate all elevators at the same time, all elevators shall transfer to standby power in sequence, return to the designated landing and disconnect from the standby power source. After all elevators have been returned to the designated level, not less than one elevator shall remain operable from the standby power source.

606.2.4 Machine room ventilation. Where standby power is connected to elevators, the machine room ventilation or air conditioning shall be connected to the standby power source.

[BE] 606.3 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE EXIT STAIRS.

Exceptions:

  1. The emergency sign shall not be required for elevators that are part of an accessible means of egress complying with Section 1009.4.

  2. The emergency sign shall not be required for elevators that are used for occupant self-evacuation in accordance with Section 3008 of the California Building Code .

Exceptions & meaning →

606.4 Fire service access elevator lobbies.

Where fire service access elevators are required by Section 3007 of the Cal- ifornia Building Code, fire service access elevator lobbies shall be maintained free of storage and furniture.

Exceptions & meaning →

606.5 Occupant evacuation elevator lobbies.

Where occupant evacuation elevators are provided in accordance with Section 3008 of the California Building Code, occupant evacuation elevator lobbies shall be maintained free of storage and furniture.

Exceptions & meaning →

606.6 Water protection of hoistway enclosures. Methods to

prevent water from infiltrating into a hoistway enclosure required by Section 3007.3 and Section 3008.3 of the Califor- nia Building Code shall be maintained.

Exceptions & meaning →

606.7 Elevator key location. Keys for the elevator car doors

and fire-fighter service keys shall be kept in an approved location for immediate use by the fire department.

Exceptions & meaning →

606.8 Standardized fire service elevator keys. Buildings

with elevators equipped with Phase I emergency recall, Phase

126 2019 CALIFORNIA FIRE CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

II emergency in-car operation, or a fire service access elevator shall be equipped to operate with a standardized fire service elevator key approved by the fire code official.

Exception: The owner shall be permitted to place the building’s nonstandardized fire service elevator keys in a key box installed in accordance with Section 506.1.2.

606.8.1 Requirements for standardized fire service ele- vator keys. Standardized fire service elevator keys shall comply with all of the following:

  1. All fire service elevator keys within the jurisdiction shall be uniform and specific for the jurisdiction. Keys shall be cut to a uniform key code.

  2. Fire service elevator keys shall be of a patent-protected design to prevent unauthorized duplication.

  3. Fire service elevator keys shall be factory restricted by the manufacturer to prevent the unauthorized distribution of key blanks. Uncut key blanks shall not be permitted to leave the factory.

  4. Fire service elevator keys subject to these rules shall be engraved with the words “DO NOT DUPLICATE.”

606.8.2 Access to standardized fire service keys. Access to standardized fire service elevator keys shall be restricted to the following:

  1. Elevator owners or their authorized agents.

  2. Elevator contractors.

  3. Elevator inspectors of the jurisdiction.

  4. Fire code officials of the jurisdiction.

  5. The fire department and other emergency response agencies designated by the fire code official.

606.8.3 Duplication or distribution of keys. A person shall not duplicate a standardized fire service elevator key or issue, give, or sell a duplicated key unless in accordance with this code.

606.8.4 Responsibility to provide keys. The building owner shall provide up to three standardized fire service elevator keys where required by the fire code official, upon installation of a standardized fire service key switch or switches in the building.

606.8.5 Shunt trip. Where elevator hoistways or elevator machine rooms containing elevator control equipment are protected with automatic sprinklers, a means installed in accordance with NFPA 72, Section 21.4, Elevator Shut- down, shall be provided to automatically disconnect the main line power supply to the affected elevator prior to the application of water. This means shall not be self-reset- ting. The activation of sprinklers outside the hoistway or machine room shall not disconnect the main line power supply.

Exceptions & meaning →