Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO
Section 4806
California Fire Code (Title 24, Part 9) · 2019 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
4806.1 Fire alarm control units. Fire alarm control units¶
shall be California State Fire Marshal listed and shall be uti- lized in accordance with their listing. Control units may be temporarily supported by sets, platforms or pedestals.
4806.2 Heat detectors. Heat detection required by this article¶
shall be defined as a portable system as it is intended to be reinstalled when platforms or sets are changed.
Heat detectors may be secured to standard outlet boxes which may be temporarily supported by sets, platforms or pedestals.
Heat detectors shall be provided for solid-ceiling sets and platforms where required by Sections 4805.3 and 4811.14.