Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL,
Section 2810
California Fire Code (Title 24, Part 9) · 2019 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
OUTDOOR STORAGE OF PALLETS AT PALLET MANUFACTURING AND RECYCLING FACILITIES
2810.1 General. The outside storage of wood pallets and¶
wood composite pallets on the same site as a pallet manufacturing or recycling facility shall comply with Sections 2810.2 through 2810.11.
2810.2 Site plan. Each site shall maintain a current site plan¶
that includes a general description of the property, the boundaries of the lot, the size and location of buildings, and all of the following:
Utilities.
Type of construction and presence of sprinkler protection for other buildings on the site.
Water supply sources for fire-fighting purposes.
Location of hazardous material storage areas.
Location of pallet storage.
Equipment protected with a dust collection system.
Fire apparatus access roads.
Designated smoking areas.
Location of fire alarm control panels.
2810.3 Fire prevention plan.¶
The owner or owner’s authorized representative shall prepare an approved fire prevention plan that includes all of the following:
Frequency of walk-through inspections to verify compliance with the plan.
Hot work permit program in accordance with Chapter
Preventive maintenance program for equipment associated with pallet activities.
Inspection, testing and maintenance of fire protection systems in accordance with Chapter 9.
2810.4 Fire safety and emergency evacuation plan. The¶
owner or owner’s authorized representative shall prepare and train employees in an approved fire safety and emergency evacuation plan in accordance with Chapter 4.
2810.5 Security management plan. The owner or owner’s¶
authorized representative shall prepare a security management plan based on a security risk assessment and shall make the plan and assessment available to the fire code official upon request.
2810.6 Clearance to property line. Stacks of pallets shall¶
not be stored within 0.75 times the stack height or 8 feet (2438 mm) of the property line, whichever is greater, or shall comply with Section 2810.11.
2810.7 Clearance to important buildings. Stacks of pallets¶
shall not be stored within 0.75 times the stack height of any important building on site, or shall comply with Section 2810.11.
2810.8 Height. Pallet stacks shall not exceed 20 feet (6096¶
mm) in height.
2810.9 Fire flow. Fire-flow requirements for the site shall be¶
determined by the fire code official.
2810.10 Portable fire extinguishers.¶
Portable fire extinguishers shall be provided within 75 feet (22 860 mm) of any pallet stack.
2810.11 Alternative approach. Where approved by the fire¶
code official, pallet stacks located closer to a property line or structure than as required by Sections 2810.6 and 2810.7 shall be provided with additional fire protection including, but not limited to, the following:
The storage yard areas and materials-handling equipment selection, design, and arrangement are based on an approved risk assessment.
Automatic fire detection that transmits an alarm to a supervising station in accordance with NFPA 72.
Fire apparatus access roads around all storage areas.
410 2019 CALIFORNIA FIRE CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.