2804.1 General.

Fire protection in timber and lumber production mills, plywood and veneer mills and agro-industrial facilities shall comply with Sections 2804.2 through 2804.4.

Exceptions & meaning →

2804.2 Fire alarms. An approved means for transmitting

alarms to the fire department shall be provided in timber and lumber production mills and plywood and veneer mills.

2804.2.1 Manual fire alarms. A manual fire alarm system complying with Section 907.2 shall be installed in areas of timber and lumber production mills and for plywood and veneer mills that contain product dryers.

Exception: Where dryers or other sources of ignition are protected by a supervised automatic sprinkler system complying with Section 903.

Exceptions & meaning →

2804.3 Portable fire extinguishers or standpipes and hose.

Portable fire extinguishers or standpipes and hose supplied from an approved water system shall be provided within a 50foot (15 240 mm) distance of travel from any machine producing shavings or sawdust. Portable fire extinguishers shall be provided in accordance with Section 906 for extra-high hazards.

Exceptions & meaning →

2804.4 Automatic sprinkler systems. Automatic sprinkler

systems shall be installed in accordance with Section 903.3.1.1.