Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL,
Section 2803
California Fire Code (Title 24, Part 9) · 2019 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
2803.1 Open yards. Open yards required by the California¶
Building Code shall be maintained around structures.
2803.2 Dust control. Equipment or machinery located inside¶
buildings that generates or emits combustible dust shall be provided with an approved dust collection and exhaust system installed in accordance with Chapter 22 and the Califor- nia Mechanical Code . Equipment or systems that are used to
collect, process or convey combustible dusts shall be provided with an approved explosion control system.
2803.2.1 Explosion venting. Where a dust explosion hazard exists in equipment rooms, buildings or other enclosures, such areas shall be provided with explosion (deflagration) venting or an approved explosion suppression system complying with Section 911.
2803.3 Waste removal. Sawmills, planning mills and other¶
woodworking plants shall be equipped with a waste removal system that will collect and remove sawdust and shavings. Such systems shall be installed in accordance with Chapter 22 and the California Mechanical Code .
Exception: Manual waste removal where approved.
2803.3.1 Housekeeping. Provisions shall be made for a systematic and thorough cleaning of the entire plant at sufficient intervals to prevent the accumulations of combustible dust and spilled combustible or flammable liquids.
2803.3.2 Metal scrap. Provision shall be made for separately collecting and disposing of any metal scrap so that such scrap will not enter the wood handling or processing equipment.
2803.4 Electrical equipment.¶
Electrical wiring and equipment shall comply with the California Electrical Code.
2803.5 Control of ignition sources. Protection from ignition¶
sources shall be provided in accordance with Sections 2803.5.1 through 2803.5.3.
2803.5.1 Cutting and welding. Cutting and welding shall comply with Chapter 35.
2803.5.2 Static electricity. Static electricity shall be prevented from accumulating on machines and equipment subject to static electricity buildup by permanent grounding and bonding wires or other approved means.
2803.5.3 Smoking. Where smoking constitutes a fire hazard, the fire code official is authorized to order the owner or occupant to post approved “No Smoking” signs complying with Section 310. The fire code official is authorized to designate specific locations where smoking is allowed.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS AND WOODWORKING FACILITIES
2803.6 Fire apparatus access roads. Fire apparatus access¶
roads shall be provided for buildings and facilities in accordance with Section 503.
2803.7 Access plan. Where storage pile configurations could¶
change because of changes in product operations and processing, the access plan shall be submitted for approval where required by the fire code official.