Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS

Section 6003 — HIGHLY TOXIC AND TOXIC SOLIDS AND LIQUIDS

2025 California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-07-29 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

6003.1 Indoor storage and use.

The indoor storage and use of highly toxic and toxic materials shall comply with Sections 6003.1.1 through 6003.1.5.3.

6003.1.1 Quantities not exceeding the maximum allowable quantity per control area. The indoor storage or use of highly toxic and toxic solids or liquids in amounts not exceeding the maximum allowable quantity per control area indicated in Table 5003.1.1(2) shall be in accordance with Sections 5001, 5003 and 6001.

6003.1.2 Quantities exceeding the maximum allowable quantity per control area. The indoor storage or use of highly toxic and toxic solids or liquids in amounts exceeding the maximum allowable quantity per control area set forth in Table 5003.1.1(2) shall be in accordance with Section 6001, Sections 6003.1.3 through 6003.1.5.3 and Chapter 50.

6003.1.3 Treatment system—highly toxic liquids. Exhaust scrubbers or other systems for processing vapors of highly toxic liquids shall be provided where a spill or accidental release of such liquids can be expected to release highly toxic vapors at normal temperature and pressure (NTP). Treatment systems and other processing systems shall be installed in accordance with the California Mechanical Code .

6003.1.4 Indoor storage. Indoor storage of highly toxic and toxic solids and liquids shall comply with Sections 6003.1.4.1 and 6003.1.4.2.

6003.1.4.1 Floors. In addition to the requirements set forth in Section 5004.12, floors of storage areas where highly toxic and toxic liquids are stored shall be of liquid-tight construction.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HIGHLY TOXIC AND TOXIC MATERIALS

6003.1.4.2 Separation—highly toxic solids and liquids. In addition to the requirements set forth in Section 5003.9.8, highly toxic solids and liquids in storage shall be located in approved hazardous material storage cabinets or isolated from other hazardous material storage by construction in accordance with the California Building Code .

6003.1.5 Indoor use. Indoor use of highly toxic and toxic solids and liquids shall comply with Sections 6003.1.5.1 through 6003.1.5.3.

6003.1.5.1 Liquid transfer. Highly toxic and toxic liquids shall be transferred in accordance with Section 5005.1.10.

6003.1.5.2 Exhaust ventilation for open systems. Mechanical exhaust ventilation shall be provided for highly toxic and toxic liquids used in open systems in accordance with Section 5005.2.1.1.

Exception: Liquids that do not generate highly toxic or toxic fumes, mists or vapors.

6003.1.5.3 Exhaust ventilation for closed systems. Mechanical exhaust ventilation shall be provided for highly toxic and toxic liquids used in closed systems in accordance with Section 5005.2.2.1.

Exception: Liquids that do not generate highly toxic or toxic fumes, mists or vapors.

6003.2 Outdoor storage and use.

Outdoor storage and use of highly toxic and toxic materials shall comply with Sections 6003.2.1 through 6003.2.6.

6003.2.1 Quantities not exceeding the maximum allowable quantity per control area. The outdoor storage or use of highly toxic and toxic solids or liquids in amounts not exceeding the maximum allowable quantity per control area indicated in Table 5003.1.1(4) shall be in accordance with Sections 5001, 5003 and 6001.

6003.2.2 Quantities exceeding the maximum allowable quantity per control area. The outdoor storage or use of highly toxic and toxic solids or liquids in amounts exceeding the maximum allowable quantity per control area set forth in Table 5003.1.1(4) shall be in accordance with Sections 6001 and 6003.2 and Chapter 50.

6003.2.3 General outdoor requirements. The general requirements applicable to the outdoor storage of highly toxic or toxic solids and liquids shall be in accordance with Sections 6003.2.3.1 and 6003.2.3.2.

6003.2.3.1 Location. Outdoor storage or use of highly toxic or toxic solids and liquids shall not be located within 20 feet (6096 mm) of lot lines, public streets, public alleys, public ways, exit discharges or exterior wall openings. A 2-hour fire barrier without openings or penetrations extending not less than 30 inches (762 mm) above and to the sides of the storage is allowed in lieu of such distance. The wall shall either be an independent structure, or the exterior wall of the building adjacent to the stor age area.

6003.2.3.2 Treatment system—highly toxic liquids. Exhaust scrubbers or other systems for processing vapors of highly toxic liquid shall be provided where a spill or accidental release of such liquids can be expected to release highly toxic vapors at normal temperature and pressure (NTP). Treatment systems and other processing systems shall be installed in accordance with the California Mechanical Code .

6003.2.4 Outdoor storage piles. Outdoor storage piles of highly toxic and toxic solids and liquids shall be separated into piles not larger than 2,500 cubic feet (71 m [3] ). Aisle widths between piles shall be not less than one-half the height of the pile or 10 feet (3048 mm), whichever is greater.

6003.2.5 Weather protection for highly toxic liquids and solids—outdoor storage or use. Where overhead weather protection is provided for outdoor storage or use of highly toxic liquids or solids, and the weather protection is attached to a building, the storage or use area shall either be equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1, or storage or use vessels shall be fire resistive. Weather protection shall be provided in accordance with Section 5004.13 for storage and Section 5005.3.9 for use.

6003.2.6 Outdoor liquid transfer. Highly toxic and toxic liquids shall be transferred in accordance with Section 5005.1.10.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Fire Code (Title 24, Part 9)
2025 California Fire Code (Title 24, Part 9)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REQUIREMENTS
  4. Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
  5. Chapter 5 — FIRE SERVICE FEATURES
  6. Chapter 6 — BUILDING SERVICES AND SYSTEMS
  7. Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
  8. Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
  9. Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
  10. Chapter 10 — MEANS OF EGRESS
  11. Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
  12. Chapter 12 — ENERGY SYSTEMS
  13. Chapter 20 — AVIATION FACILITIES
  14. Chapter 21 — DRY CLEANING
  15. Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
  16. Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
  17. Chapter 24 — FLAMMABLE FINISHES
  18. Chapter 25 — FRUIT AND CROP RIPENING
  19. Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
  20. Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
  21. Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
  22. Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
  23. Chapter 30 — INDUSTRIAL OVENS
  24. Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
  25. Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
  26. Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
  27. Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
  28. Chapter 35 — WELDING AND OTHER HOT WORK
  29. Chapter 36 — MARINAS
  30. Chapter 37 — COMBUSTIBLE FIBERS
  31. Chapter 38 — RESERVED
  32. Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
  33. Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
  34. Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
  35. Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
  36. Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
  37. Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
  38. Chapter 51 — AEROSOLS
  39. Chapter 52 — RESERVED
  40. Chapter 53 — COMPRESSED GASES
  41. Chapter 54 — CORROSIVE MATERIALS
  42. Chapter 55 — CRYOGENIC FLUIDS
  43. Chapter 56 — EXPLOSIVES AND FIREWORKS
  44. Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
  45. Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
  46. Chapter 59 — FLAMMABLE SOLIDS
  47. Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
  48. Chapter 61 — LIQUEFIED PETROLEUM GASES
  49. Chapter 62 — ORGANIC PEROXIDES
  50. Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
  51. Chapter 64 — PYROPHORIC MATERIALS
  52. Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
  53. Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
  54. Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
  55. Chapter 80 — REFERENCED STANDARDS
  56. Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
  57. Appendix A — BOARD OF APPEALS
  58. Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
  59. Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
  60. Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
  61. Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
  62. Appendix D — FIRE APPARATUS ACCESS ROADS
  63. Appendix E — HAZARD CATEGORIES
  64. Appendix F — HAZARD RANKING
  65. Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
  66. Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
  67. Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
  68. Appendix J — BUILDING INFORMATION SIGN
  69. Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
  70. Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
  71. Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
  72. Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
  73. Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
  74. Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
  75. Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.