6005.1 Scope.

Ozone-gas generators having a maximum ozone-generating capacity of 0.5 pound (0.23 kg) or more over a 24-hour period shall be in accordance with Sections 6005.2 through 6005.6.

Exceptions:

  1. Ozone-generating equipment used in Group R-3 occupancies.
  2. Ozone-generating equipment where used in Group H-5 occupancies where in compliance with Chapters 27 and 50 and the other provisions in this chapter for highly toxic gases.

60-8 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HIGHLY TOXIC AND TOXIC MATERIALS

6005.2 Design.

Ozone-gas generators shall be designed, fabricated and tested in accordance with NEMA 250.

6005.3 Location.

Ozone generators shall be located in approved cabinets or ozone generator rooms in accordance with Section 6005.3.1 or 6005.3.2.

Exception: An ozone-gas generator within an approved pressure vessel where located outside of buildings.

6005.3.1 Cabinets. Ozone cabinets shall be constructed of approved materials and compatible with ozone. Cabinets shall display an approved sign stating: “OZONE-GAS GENERATOR—HIGHLY TOXIC—OXIDIZER.”

Cabinets shall be braced for seismic activity in accordance with the California Building Code .

Cabinets shall be mechanically ventilated in accordance with the California Mechanical Code with not less than six air changes per hour.

The average velocity of ventilation at makeup air openings with cabinet doors closed shall be not less than 200 feet per minute (1.02 m/s).

6005.3.2 Ozone-gas-generator rooms. Ozone-gas-generator rooms shall be mechanically ventilated in accordance with the Cali- fornia Mechanical Code with not less than six air changes per hour. Ozone-gas-generator rooms shall be equipped with a gas detection system complying with Section 916 that will shut off the generator and sound a local alarm when concentrations above the permissible exposure limit (PEL) occur.

Ozone-gas-generator rooms shall not be normally occupied, and such rooms shall be kept free of combustible and hazardous material storage. Room access doors shall display an approved sign stating: “OZONE-GAS GENERATOR—HIGHLY TOXIC— OXIDIZER.”

6005.4 Piping, valves and fittings.

Piping, valves, fittings and related components used to convey ozone shall be in accordance with Sections 6005.4.1 through 6005.4.3.

6005.4.1 Piping. Piping shall be welded stainless steel piping or tubing.

Exceptions:

  1. Double-walled piping.
  2. Piping, valves, fittings and related components located in exhausted enclosures.

6005.4.2 Materials. Materials shall be compatible with ozone and shall be rated for the design operating pressures.

6005.4.3 Identification. Piping shall be identified with the following: “OZONE GAS—HIGHLY TOXIC—OXIDIZER.”

6005.5 Automatic shutdown.

Ozone-gas generators shall be designed to shut down automatically under the following conditions:

  1. When the dissolved ozone concentration in the water being treated is above saturation when measured at the point where the water is exposed to the atmosphere.
  2. When the process using generated ozone is shut down.
  3. Failure of the ventilation system for the cabinet or ozone-generator room.
  4. Failure of the gas detection system in an ozone-gas-generator room.

6005.6 Manual shutdown.

Manual shutdown controls shall be provided at the generator and, where in a room, within 10 feet (3048 mm) of the main exit or exit access door.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

60-10 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

CALIFORNIA FIRE CODE – MATRIX ADOPTION TABLE

CHAPTER 61 – LIQUEFIED PETROLEUM GASES

(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

Adopting Agency BSC BSC-
CG
SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
Adopting Agency BSC BSC-
CG
T-24 T-19* 1 2 1/AC AC SS 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
Adopt Entire Chapter X
Adopt Entire Chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
[California Code of Regulations,
Title 19, Division 1]
X
Chapter / Section
[T-19 §3.22 (a)(c)] X
[T-19 §3.22 (b)] X
  • The California Code of Regulations (CCR), Title 19, Division 1 provisions that are found in the California Fire Code are a reprint from the current CCR, Title 19, Division 1 text for the code user’s convenience only. The scope, applicability and appeals procedures of CCR, Title 19, Division I remain the same. The state agency does not adopt sections identified by the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

61-2 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Fire Code (Title 24, Part 9)
2025 California Fire Code (Title 24, Part 9)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REQUIREMENTS
  4. Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
  5. Chapter 5 — FIRE SERVICE FEATURES
  6. Chapter 6 — BUILDING SERVICES AND SYSTEMS
  7. Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
  8. Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
  9. Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
  10. Chapter 10 — MEANS OF EGRESS
  11. Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
  12. Chapter 12 — ENERGY SYSTEMS
  13. Chapter 20 — AVIATION FACILITIES
  14. Chapter 21 — DRY CLEANING
  15. Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
  16. Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
  17. Chapter 24 — FLAMMABLE FINISHES
  18. Chapter 25 — FRUIT AND CROP RIPENING
  19. Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
  20. Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
  21. Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
  22. Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
  23. Chapter 30 — INDUSTRIAL OVENS
  24. Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
  25. Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
  26. Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
  27. Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
  28. Chapter 35 — WELDING AND OTHER HOT WORK
  29. Chapter 36 — MARINAS
  30. Chapter 37 — COMBUSTIBLE FIBERS
  31. Chapter 38 — RESERVED
  32. Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
  33. Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
  34. Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
  35. Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
  36. Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
  37. Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
  38. Chapter 51 — AEROSOLS
  39. Chapter 52 — RESERVED
  40. Chapter 53 — COMPRESSED GASES
  41. Chapter 54 — CORROSIVE MATERIALS
  42. Chapter 55 — CRYOGENIC FLUIDS
  43. Chapter 56 — EXPLOSIVES AND FIREWORKS
  44. Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
  45. Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
  46. Chapter 59 — FLAMMABLE SOLIDS
  47. Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
  48. Chapter 61 — LIQUEFIED PETROLEUM GASES
  49. Chapter 62 — ORGANIC PEROXIDES
  50. Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
  51. Chapter 64 — PYROPHORIC MATERIALS
  52. Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
  53. Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
  54. Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
  55. Chapter 80 — REFERENCED STANDARDS
  56. Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
  57. Appendix A — BOARD OF APPEALS
  58. Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
  59. Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
  60. Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
  61. Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
  62. Appendix D — FIRE APPARATUS ACCESS ROADS
  63. Appendix E — HAZARD CATEGORIES
  64. Appendix F — HAZARD RANKING
  65. Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
  66. Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
  67. Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
  68. Appendix J — BUILDING INFORMATION SIGN
  69. Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
  70. Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
  71. Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
  72. Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
  73. Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
  74. Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
  75. Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.