Chapter 16 — REFERENCED STANDARDS
Section C103
California Existing Building Code (Title 24, Part 10) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
MATERIALS OF CONSTRUCTION
[BS] C103.1 Existing materials. Existing wood materials that will be part of the retrofitting work (such as trusses, rafters, ceiling joists, top plates and wall studs) shall be in sound condition and free from defects or damage that substantially reduces the load-carrying capacity of the member. Any wood materials found to be damaged or deteriorated shall be strengthened or replaced with new materials to provide a net dimension of sound wood equivalent to its undamaged original dimensions.
[BS] C103.2 New materials. All new materials shall comply with the standards for those materials as specified in the Cali- fornia Building Code or the California Residential Code .
[BS] C103.3 Material specifications for retrofits. Materials for retrofitting gable end walls shall comply with Table C103.3.
[BS] C103.4 Twists in straps. Straps shall be permitted to be twisted or bent where they transition between framing members or connection points. Straps shall be bent only once at a given location though it is permissible that they be bent or twisted at multiple locations along their length.
[BS] C103.5 Fasteners. Fasteners shall meet the requirements of Table C103.5, Sections C103.5.1 and C103.5.2, and shall be permitted to be screws or nails meeting the minimum length requirement shown in the figures and specified in the tables of this appendix. Fastener spacing shall meet the requirements of Section C103.5.3.
[BS] C103.5.1 Screws. Unless otherwise indicated in the appendix, screw sizes and lengths shall be in accordance with Table C103.5. Permissible screws include deck screws and wood screws. Screws shall have not less than 1 inch (25 mm) of thread. Fine threaded screws or drywall screws shall not be permitted. Select the largest possible diameter screw such that the shank adjacent to the head fits through the hole in the strap.
[BS] C103.5.2 Nails. Unless otherwise indicated in this appendix, nail sizes and lengths shall be in accordance with Table C103.5.
[BS] C103.5.3 General fastener spacing. Fastener spacing for shear connections of lumber-to-lumber shall meet the requirements shown in Figure C103.5.3 and the following conditions.
[BS] C103.5.3.1 General fastener spacing. Fastener spacing shall meet the following conditions except as provided for in Section C103.5.3.
The distance between fasteners and the edge of lumber that is less than 3 1 /2 inches deep (89 mm) in the direction of the fastener length shall be not less than 3 /4 inch (19.1 mm).
- The distance between fasteners and the edge of lumber that is more than 2 inches (51 mm) thick in the direction of the fastener length shall be not less than 1 /2 inch (12.7 mm).
- The distance between a fastener and the end of lumber shall be not less than 2 1 /2 inches (64 mm).
- The distance between fasteners parallel to the grain (center-to-center) shall be not less than 2 1 /2 inches (64 mm).
[BS] TABLE C103.3 MATERIAL SPECIFICATIONS FOR RETROFITS a
| COMPONENT | MINIMUM SIZE OR THICKNESS | MINIMUM MATERIAL GRADE | MINIMUM CAPACITY |
|---|---|---|---|
| Anchor blocks, compression blocks, and horizontal braces |
2 x 4 nominal lumber | #2 Spruce-Pine-Fir or better | NA |
| Nail plates | 20 gage thickness 8d minimum nail holes |
Galvanized sheet steel | NA |
| Retrofit studs | 2 x 4 nominal lumber | #2 Spruce-Pine-Fir or better | NA |
| Gusset angle | 14 gage thickness | Galvanized sheet steel | 350 pounds uplift and lateral load |
| Stud-to-plate connector | 20 gage thickness | Galvanized sheet steel | 500 pounds uplift |
| Metal plate connectors, straps, and anchors | 20 gage thickness | Galvanized sheet steel | NA |
For SI: 1 foot = 304.8mm, 1 pound = 4.4 N. NA = Not Applicable. a. Metal plate connectors, nail plates, stud-to-plate connectors, straps and anchors shall be products approved for connecting wood-to-wood or wood-to-concrete
as appropriate .
[BS] TABLE C103.5 NAIL AND SCREW REQUIREMENTS
| FASTENER TYPE | MINIMUM SHANK DIAMETER | MINIMUM HEAD DIAMETER | MINIMUM FASTENER LENGTH |
|---|---|---|---|
| #8 screws | NA | 0.28 inches | 1-1/4 inches |
| 8d common nails | 0.131 inches | 0.28 inches | 2-1/2 inches |
| 10d common nails | 0.148 inches | 0.28 inches | 3 inches |
For SI: 1 inch = 25.4 mm.
NA = Not Applicable.
200 2019 CALIFORNIA EXISTING BUILDING CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
APPENDIX C
The distance between fasteners perpendicular to the grain (center-to-center) in lumber that is less than 3 1 /2 inches (89 mm) deep in the direction of the fastener length shall be 1 inch (25 mm).
The distance between fasteners perpendicular to the grain (center-to-center) in lumber that is more than 2 inches (51 mm) thick in the direction of the fastener length shall be 1 /2 inch (12.7 mm).
[BS] C103.5.3.2 Wood-to-wood connections of two members each 2 inches or less in thickness. Woodto-wood connections fastener spacing shall meet the following conditions.
The distance between fasteners parallel to grain (center-to-center) shall be not less than 2 1 /2 inches (64 mm).
The distance between fasteners across grain (center-to-center) shall be not less than 1 inch (25 mm).
For wood-to-wood connections of lumber at right angles, fasteners shall be spaced not less than 2 1 /2 inches (64 mm) parallel to the grain and 1 inch (25 mm) perpendicular to the grain in any direction.
[BS] C103.5.3.3 Metal connectors for wood-to-wood connections. Metal connectors for wood-to-wood connections shall meet the following conditions.
- Fastener spacing to edge or ends of lumber shall be as dictated by the prefabricated holes in the connectors and the connectors shall be installed in a configuration that is similar to that shown by the connector manufacturer.
- Fasteners in 1 1 /4-inch-wide (32 mm) metal straps that are installed on the narrow face of lumber shall be a minimum 1 /4 inch (6.4 mm) from either edge of the lumber. Consistent with Section
C103.5.3.1, fasteners shall be permitted to be spaced according to the fastener holes fabricated into the strap.
- Fasteners in metal nail plates shall be spaced not less than 1 /2 inch (12.7 mm) perpendicular to grain and not less than 1 1 /2 inches (38 mm) parallel to grain.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Existing Building Code (Title 24, Part 10)
- Chapter 2 — DEFINITIONS
- Appendix A — GUIDELINES FOR
- Appendix B — SUPPLEMENTARY
- Appendix C — GUIDELINES FOR THE
- Chapter 1 — SCOPE AND ADMINISTRATION
- Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 4 — REPAIRS
- Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 6 — CLASSIFICATION OF WORK
- Chapter 7 — ALTERATIONS - LEVEL 1
- Chapter 8 — ALTERATIONS - LEVEL 2
- Chapter 9 — ALTERATIONS - LEVEL 3
- Chapter 10 — CHANGE OF OCCUPANCY
- Chapter 11 — ADDITIONS
- Chapter 12 — HISTORIC BUILDINGS
- Chapter 13 — PERFORMANCE COMPLIANCE METHODS
- Chapter 14 — RELOCATED OR MOVED BUILDINGS
- Chapter 15 — CONSTRUCTION SAFEGUARDS
▸Chapter 16 — REFERENCED STANDARDS
Overview- Section A100
- Section A101
- Section A102
- Section A103
- Section A104
- Section A105
- Section A106
- Section A107
- Section A108
- Section A109
- Section A110
- Section A111
- Section A112
- Section A113
- Section A114
- Section A201
- Section A205
- Section A202
- Section A203
- Section A204
- Section A206
- Section A207
- Section A301
- Section A302
- Section A303
- Section A304
- Section A401
- Section A402
- Section A403
- Section A404
- Section A405
- Section A406
- Section A407
- Section B101
- Section B102
- Section B103
- Section B104
- Section C101
- Section C102
- Section C103
- Section C104
- Section C201
- Section C202