ANALYSIS AND DESIGN PROCEDURE

[BS] A109.1 General. The elements of buildings hereby required to be analyzed are specified in Table A102.1.

[BS] A109.2 Selection of procedure. Buildings with rigid diaphragms shall be analyzed by the general procedure of Section A110. Buildings with flexible diaphragms shall be analyzed by the general procedure or, where applicable, are permitted to be analyzed by the special procedure of Section A111.

vmL

= ----------------------------------1.5

fsp + P ------ D An

[BS] A108.3 Masonry compression. Where any increase in wall dead plus live load compression stress occurs, the maximum compression stress in unreinforced masonry, QG/An, shall not exceed 300 pounds per square inch (2070 kPa).

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

APPENDIX A

[BS] TABLE A108.1(2) STRENGTH VALUES OF NEW MATERIALS USED IN CONJUNCTION WITH EXISTING CONSTRUCTION

NEW MATERIALS OR CONFIGURATION OF MATERIALS STRENGTH VALUES
Horizontal diaphragms Plywood sheathing applied directly over existing straight sheathing
with ends of plywood sheets bearing on joists or rafters and edges
of plywood located on center of individual sheathing boards.
675 lbs. per ft.
Crosswalls Plywood sheathing applied directly over wood studs; no value
should be given to plywood applied over existing plaster or wood
sheathing.
1.2 times the value specified in the current
building code.
Crosswalls Drywall or plaster applied directly over wood studs. The value specified in the current building
code.
Crosswalls Drywall or plaster applied to sheathing over existing wood studs. 50 percent of the value specified in the
current building code.
Tension anchorsf Anchors extending entirely through unreinforced masonry wall
secured with bearing plates on far side of a wall 30 square inches
of area.b, c
5,400 lbs. per anchor for three-wythe
minimum walls.
2,700 lbs. for two-wythe walls.
Shear boltse, f Anchors embedded not less than 8 inches into unreinforced masonry
walls; anchors should be centered in 21/2-inch-diameter holes
with dry-pack or nonshrink grout around the circumference of the
anchor.
The value for plain masonry specified for
solid masonry TMS 402; and no value
larger than those given for3/4-inch bolts
should be used.
Combined tension and
shear anchorsf
Through-anchors—anchors meeting the requirements for shear and
for tension anchors.b, c
Tension—same as for tension anchors.
Shear—same as for shear anchors.
Combined tension and
shear anchorsf
Embedded anchors—anchors extending to the exterior face of the
wall with a 21/2-inch round plate under the head and drilled at an
angle of 221/2 degrees to the horizontal; installed as specified for
shear anchors.a, b, c
Tension—3,600 lbs. per anchor.
Shear—same as for shear anchors.
Infilled walls Reinforced masonry infilled openings in existing unreinforced
masonry walls; provide keys or dowels to match reinforcing.
Same as values specified for unreinforced
masonry walls.
Reinforced masonryd Masonry piers and walls reinforced per the current building code. The value specified in the current building
code for strength design.
Reinforced concreted Concrete footings, walls and piers reinforced as specified in the
current building code.
The value specified in the current building
code for strength design.

For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2, 1 pound = 4.4 N, 1 degree = 0.017 rad, 1 pound per foot = 14.43 N/m, 1 foot = 304.8 mm. a. Embedded anchors to be tested as specified in Section A107.4. b. Anchors shall be 1 /2 inch minimum in diameter. c. Drilling for anchors shall be done with an electric rotary drill; impact tools should not be used for drilling holes or tightening anchors and shear bolt nuts. d. Load factors or capacity reduction factors shall not be used. e. Other bolt sizes, values and installation methods may be used, provided that a testing program is conducted in accordance with Section A107.5.3. The

minimum in diameter. c. Drilling for anchors shall be done with an electric rotary drill; impact tools should not be used for drilling holes or tightening anchors and shear bolt nuts. d. Load factors or capacity reduction factors shall not be used. e. Other bolt sizes, values and installation methods may be used, provided that a testing program is conducted in accordance with Section A107.5.3. The

strength value shall be determined by multiplying the calculated allowable value, determined in accordance with Section A107.5.3, by 3.0, and the usable value shall be limited to not greater than 1.5 times the value given in the table. Bolt spacing shall not exceed 6 feet on center and shall be not less than 12 inches on center. f. An alternative adhesive anchor bolt system is permitted to be used providing: its properties and installation conform to an ICC Evaluation Service Report; and

the report states that the system’s use is in unreinforced masonry as an acceptable alternative to Sections A107.4 and A113.1 or TMS 402, Section 2.1.4. The report’s allowable values shall be multiplied by a factor of three to obtain strength values and the strength reduction factor, shall be taken equal to 1.0.