Chapter 16 — REFERENCED STANDARDS
Section A404
California Existing Building Code (Title 24, Part 10) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
PRESCRIPTIVE MEASURES FOR WEAK STORY
[BS] A404.1 Limitation. These prescriptive measures shall apply only to two-story buildings and only where deemed appropriate by the code official. These prescriptive measures rely on rotation of the second floor diaphragm to distribute the seismic load between the side and rear walls of the ground floor open area. In the absence of an existing floor diaphragm of wood structural panel or diagonal sheathing, a new wood structural panel diaphragm of minimum thickness of 3 /4 inch (19.1 mm) and with 10d common nails at 6 inches (152 mm) on center shall be applied.
[BS] A404.1.1 Additional conditions. To qualify for these prescriptive measures, the following additional conditions need to be satisfied by the retrofitted structure:
Diaphragm aspect ratio L/W is less than 0.67, where W is the diaphragm dimension parallel to the soft, weak or open-front wall line and L is the distance in the orthogonal direction between that wall line and the rear wall of the ground floor open area.
Minimum length of side shear walls = 20 feet (6096 mm).
Minimum length of rear shear wall = three-fourths of the total rear wall length.
Plan or vertical irregularities shall not be other than a soft, weak or open-front wall line.
Roofing weight less than or equal to 5 pounds per square foot (240 N/m 2 ).
Aspect ratio of the full second floor diaphragm meets the requirements of the building code for new construction.
[BS] A404.2 Minimum required retrofit.
[BS] A404.2.1 Anchor size and spacing. The anchor size and spacing shall be not less than 3 /4 inch (19.1 mm) in diameter at 32 inches (813 mm) on center. Where existing anchors are inadequate, supplemental or alternative approved connectors (such as new steel plates bolted to the side of the foundation and nailed to the sill) shall be used.
[BS] A404.2.2 Connection to floor above. Shear wall top plates shall be connected to blocking or rim joist at upper floor with not less than 18-gage galvanized steel angle clips 4 1 /2 inches (114 mm) long with 12-8d nails spaced
APPENDIX A
not farther than 16 inches (406 mm) on center, or by equivalent shear transfer methods.
[BS] A404.2.3 Shear wall sheathing. The shear wall sheathing shall be not less than 15 /32-inch (11.9 mm), 5-Ply Structural I with 10d nails at 4 inches (102 mm) on center at edges and 12 inches (305 mm) on center at field; blocked all edges with 3 by 4 board or larger. Where existing sill plates are less than 3-by thick, place flat 2-by on top of sill between studs, with flat 18-gage galvanized steel clips 4 1 /2 inches (114 mm) long with 12-8d nails or 3 /8-inch-diameter (9.5 mm) lags through blocking for shear transfer to sill plate. Stagger nailing from wall sheathing between existing sill and new blocking. Anchor new blocking to foundation as specified in this section.
ss than 3-by thick, place flat 2-by on top of sill between studs, with flat 18-gage galvanized steel clips 4 1 /2 inches (114 mm) long with 12-8d nails or 3 /8-inch-diameter (9.5 mm) lags through blocking for shear transfer to sill plate. Stagger nailing from wall sheathing between existing sill and new blocking. Anchor new blocking to foundation as specified in this section.
[BS] A404.2.4 Shear wall hold-downs. Shear walls shall be provided with hold-down anchors at each end. Two hold-down anchors are required at intersecting corners. Hold-downs shall be approved connectors with a minimum 5 /8-inch-diameter (15.9 mm) threaded rod or other approved anchor with a minimum allowable load of 4,000 pounds (17.8 kN). Anchor embedment in concrete shall be not less than 5 inches (127 mm). Tie-rod systems shall be not less than 5 /8 inch (15.9 mm) in diameter unless using high-strength cable. High-strength cable elongation shall not exceed 5 /8 inch (15.9 mm) under a 4,000 pound (17.8 kN) axial load.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Existing Building Code (Title 24, Part 10)
- Chapter 2 — DEFINITIONS
- Appendix A — GUIDELINES FOR
- Appendix B — SUPPLEMENTARY
- Appendix C — GUIDELINES FOR THE
- Chapter 1 — SCOPE AND ADMINISTRATION
- Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 4 — REPAIRS
- Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 6 — CLASSIFICATION OF WORK
- Chapter 7 — ALTERATIONS - LEVEL 1
- Chapter 8 — ALTERATIONS - LEVEL 2
- Chapter 9 — ALTERATIONS - LEVEL 3
- Chapter 10 — CHANGE OF OCCUPANCY
- Chapter 11 — ADDITIONS
- Chapter 12 — HISTORIC BUILDINGS
- Chapter 13 — PERFORMANCE COMPLIANCE METHODS
- Chapter 14 — RELOCATED OR MOVED BUILDINGS
- Chapter 15 — CONSTRUCTION SAFEGUARDS
▸Chapter 16 — REFERENCED STANDARDS
Overview- Section A100
- Section A101
- Section A102
- Section A103
- Section A104
- Section A105
- Section A106
- Section A107
- Section A108
- Section A109
- Section A110
- Section A111
- Section A112
- Section A113
- Section A114
- Section A201
- Section A205
- Section A202
- Section A203
- Section A204
- Section A206
- Section A207
- Section A301
- Section A302
- Section A303
- Section A304
- Section A401
- Section A402
- Section A403
- Section A404
- Section A405
- Section A406
- Section A407
- Section B101
- Section B102
- Section B103
- Section B104
- Section C101
- Section C102
- Section C103
- Section C104
- Section C201
- Section C202