Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
Section 508
California Building Code (Title 24, Part 2) · 2022 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
508.1 General.¶
Each portion of a building shall be individually classified in accordance with Section 302.1. Where a building contains more than one occupancy group, the building or portion thereof shall comply with the applicable provisions of Section 508.2, 508.3, 508.4 or 508.5, or a combination of these sections.
Exceptions:
Occupancies separated in accordance with Section
Where required by Table 415.6.5, areas of Group H1, H-2 and H-3 occupancies shall be located in a detached building or structure.
508.2 Accessory occupancies.¶
Accessory occupancies are those occupancies that are ancillary to the main occupancy of the building or portion thereof. Accessory occupancies shall comply with the provisions of Sections 508.2.1 through 508.2.4.
508.2.1 Occupancy classification. Accessory occupancies shall be individually classified in accordance with Section 302.1. The requirements of this code shall apply to each portion of the building based on the occupancy classification of that space.
508.2.2 Allowable building height. The allowable height and number of stories of the building containing accessory occupancies shall be in accordance with Section 504 for the main occupancy of the building.
508.2.3 Allowable building area. The allowable area of the building shall be based on the applicable provisions of Section 506 for the main occupancy of the building. Aggregate accessory occupancies shall not occupy more than 10 percent of the floor area of the story in which they are located and shall not exceed the tabular values for nonsprinklered buildings in Table 506.2 for each such accessory occupancy.
508.2.4 Separation of occupancies. No separation is required between accessory occupancies and the main occupancy.
Exceptions:
Group H-2, H-3, H-4 and H-5 and L occupancies shall be separated from all other occupancies in accordance with Section 508.4.
Group R-1, R-2, R-2.1, R-2.2 and R-3 dwelling units and sleeping units shall be separated from other dwelling or sleeping units and from acces
sory occupancies contiguous to them in accordance with the requirements of Section 420.
3. Group I-2 and I-2.1 shall be separated from all other occupancies in accordance with Section 508.4. Exception: No separation is required between Group B, E and R-2 sleeping units accessory to Group I-2 and I-2.1 and covered exterior entrances required by Section 11B-206.4.10 or Section 1224.33.2.1 accessory to Group I-2.
4. Group I-3 and vehicle sally-ports shall be sepa- rated from all other occupancies in accordance with Section 508.4.
Exception: No separation is required between Group B, E, R-2 sleeping units and S-2 occu- pancies accessory to Group I-3 of Type I con- struction.
508.3 Nonseparated occupancies.¶
Buildings or portions of buildings that comply with the provisions of this section shall be considered as nonseparated occupancies.
508.3.1 Occupancy classification. Nonseparated occupancies shall be individually classified in accordance with Section 302.1. The requirements of this code shall apply to each portion of the building based on the occupancy classification of that space. In addition, the most restrictive provisions of Chapter 9 that apply to the nonseparated occupancies shall apply to the total nonseparated occupancy area.
508.3.1.1 High-rise buildings. Where nonseparated occupancies occur in a high-rise building, the most restrictive requirements of Section 403 that apply to the nonseparated occupancies shall apply throughout the high-rise building.
508.3.2 Allowable building area, height and number of stories. The allowable building area, height and number of stories of the building or portion thereof shall be based on the most restrictive allowances for the occupancy groups under consideration for the type of construction of the building in accordance with Section 503.1.
508.3.3 Separation. No separation is required between nonseparated occupancies.
Exceptions:
Group H-2, H-3, H-4 and H-5 , I-2, I-2.1 and L occupancies shall be separated from all other occupancies in accordance with Section 508.4.
Group R-1, R-2, R-2.1, R-2.2 and R-3 dwelling units and sleeping units shall be separated from other dwelling or sleeping units and from other occupancies contiguous to them in accordance with the requirements of Section 420.
3. Separation is required between Group I-3 and vehicle sally ports.
4. Where Group I-3 is not the main occupancy and the area is greater than 10 percent of the floor area, it shall be separated per Table 508.4.
5-16 2022 CALIFORNIA BUILDING CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
508.4 Separated occupancies.¶
Buildings or portions of buildings that comply with the provisions of this section shall be considered as separated occupancies.
508.4.1 Occupancy classification. Separated occupancies shall be individually classified in accordance with Section 302.1. Each separated space shall comply with this code based on the occupancy classification of that portion of the building. The most restrictive provisions of Chapter 9 that apply to the separate occupancies shall apply to the total nonfire-barrier-separated occupancy areas. Occupancy separations that serve to define fire area limits established in Chapter 9 for requiring a fire protection system shall also comply with Section 901.7.
508.4.2 Allowable building area. In each story, the building area shall be such that the sum of the ratios of the actual building area of each separated occupancy divided by the allowable building area of each separated occupancy shall not exceed 1.
GENERAL BUILDING HEIGHTS AND AREAS
508.4.3 Allowable building height and number of stories. Each separated occupancy shall comply with the building height limitations and story limitations based on the type of construction of the building in accordance with Section 503.1.
Exception: Special provisions of Section 510 shall permit occupancies at building heights and number of stories other than provided in Section 503.1.
508.4.4 Separation. Individual occupancies shall be separated from adjacent occupancies in accordance with Table 508.4.
508.4.4.1 Construction. Required separations shall be fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both, so as to completely separate adjacent occupancies. Mass timber elements serving as fire barriers or horizontal assemblies to separate occu
TABLE 508.4 REQUIRED SEPARATION OF OCCUPANCIES (HOURS) h
| OCCUPANCY | A, E | I-4i, R-2.1 | I-2j, I-2.1 |
I-3 | R-1a, R-2a, R2-2a, R-3a, R-3.1a, R-4a |
F-2, S-2b, U |
Be, F-1g, h, M, S-1 |
L | H-1 | H-2 | H-3, H-4 | H-5 | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| OCCUPANCY | S | NS | S | NS | S | NS | S | NS | S | NS | S | NS | S | NS | S | NS | S | NS | S | NS | S | NS | S | NS |
| A, E | N | N | 2 | 2 | 2 | NP | 2 | NP | 1 | 2 | N | 1 | 1 | 2 | 2 | NP | NP | NP | 3 | 4 | 2 | 3 | 2 | NP |
| I-4_i_,_ R-2.1_ | 2 | 2 | 1e | NP | 2 | NP | 2 | NP | 1 | NP | 1 | 2 | 1 | 2 | 2 | NP | NP | NP | 4 | NP | 2 | NP | 2 | NP |
| I-2_j, I-2.1_ | 2 | NP | 2 | NP | N | NP | 2 | NP | 2 | NP | 2 | NP | 2 | NP | 2 | NP | NP | NP | 4 | NP | 2 | NP | 2 | NP |
| I-3 | 2 | NP | 2 | NP | 2 | NP | N | NP | 2 | NP | 2 | 2 | 2 | 2 | 2 | NP | NP | NP | 4 | NP | ||||
| R_-1a, R-2a,_ _R-2-2a, R-3a, _ R-3.1a, R-4a |
1 | 2 | 1 | NP | 2 | NP | 2 | NP | N | N | 1c | 2c | 1 | 2 | 4 | NP | NP | NP | 3 | NP | 2 | NP | 2 | NP |
| F-2, S-2b, U | N | 1 | 1 | 2 | 2 | NP | 2 | 2 | 1c | 2c | N | N | 1 | 2 | 1 | NP | NP | NP | 3 | 4 | 2 | 3 | 2 | NP |
| Be, F-1_g, h_, M, S-1 |
1 | 2 | 1 | 2 | 2 | NP | 2 | 2 | 1 | 2 | 1 | 2 | N | N | 1 | NP | NP | NP | 2 | 3 | 1 | 2 | 1 | NP |
| L | 2 | NP | 2 | NP | 2 | NP | 2 | NP | 4 | NP | 1 | NP | 1 | NP | 1 | NP | NP | NP | 2 | NP | 1 | NP | 1 | NP |
| H-1 | NP | NP | NP | NP | NP | NP | _NP _ | NP | NP | NP | NP | NP | NP | NP | NP | NP | N | NP | NP | NP | NP | NP | NP | NP |
| H-2 | 3 | 4 | 4 | NP | 4 | NP | 4 | NP | 3 | NP | 3 | 4 | 2 | 3 | 2 | NP | NP | NP | N | NP | 1 | NP | 1 | NP |
| H-3, H-4 | 2 | 3 | 2 | NP | 2 | NP | 2 | NP | 2 | 3 | 1 | 2 | 1 | NP | NP | NP | 1 | NP | 1d | NP | 1 | NP | ||
| H-5 | 2 | NP | 2 | NP | 2 | NP | 2 | NP | 2 | NP | 1 | NP | 1 | NP | NP | NP | 1 | NP | 1 | NP | N | NP |
S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1. NS = Buildings not equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1. N = No separation requirement. NP = Not Permitted. a. See Section 420. b. The required separation from areas used only for private or pleasure vehicles shall be reduced by 1 hour but not to less than 1 hour. c. See Sections 406.3.2 and 406.6.4. d. Separation is not required between occupancies of the same classification. e. See Section 422.2 for ambulatory care facilities. f. Occupancy separations that serve to define fire area limits established in Chapter 9 for requiring fire protection systems shall also comply with Section
707.3.10 and Table 707.3.10 in accordance with Section 901.7. g. [SFM] Group I and F1 occupancies and Group R-2.1 and F-1 occupancies shall have a 3 hour separation. h. [SFM] Commercial kitchens not associated with cafeterias and similar dining facilities in Group I-2 and Group R-2.1 shall have a 2-hour separation and
shall be protected by an automatic sprinkler system. i. [SFM] Group E child-care separation with I-4 child care can be reduced to 1 hour with the installation of automatic fire sprinklers in accordance with
Section 903.3.1.1. j. When not considered an accessory use in accordance with Section 508.2.4, the required separation between Group I-2 and required covers for accessible
entrances and emergency vehicle entrances, when in accordance with Section 406.5.2 and protected by an automatic sprinkler system, shall be reduced by 1 hour but not to less than 1 hour. See Section 903.2.21.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
508.5.5 Spiral stairways. Spiral stairways that conform to the requirements of Section 1011.10 shall be permitted.
508.5.6 Vertical openings. Floor openings between floor levels of a live/work unit are permitted without enclosure.
[F] 508.5.7 Fire protection. The live/work unit shall be provided with a monitored fire alarm system where required by Section 907.2.9 and an automatic sprinkler system in accordance with Section 903.2.8.
508.5.8 Structural. Floors within a live/work unit shall be designed for the live loads in Table 1607.1, based on the function within the space.
Exception: Residential areas of live/work units constructed in accordance with the California Residen- tial Code shall not be required to comply with Table 1607.1.
508.5.9 Accessibility. Accessibility shall be designed in accordance with Chapter 11A and/or 11B, when applica- ble, for the function served.
508.5.10 Ventilation. The applicable ventilation requirements of the California Mechanical Code shall apply to each area within the live/work unit for the function within that space.
508.5.11 Plumbing facilities. The nonresidential area of the live/work unit shall be provided with minimum plumbing facilities as specified by the California Plumbing Code, based on the function of the nonresidential area. Where the nonresidential area of the live/work unit is required to be accessible, the plumbing fixtures specified by the California Plumbing Code shall be accessible.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Building Code (Title 24, Part 2)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix G — FLOOD-RESISTANT
- Appendix L — EARTHQUAKE RECORDING
- Appendix M — TSUNAMI-GENERATED
- Appendix N — REPLICABLE
- Appendix O — PERFORMANCE-BASED
- Chapter 1 — SCOPE AND ADMINISTRATION
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
▸Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 22 — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U – AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix F — RODENTPROOFING
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
- Appendix P — EMERGENCY HOUSING