407.1 General.

Occupancies in Group I-2 and I-2.1 shall comply with the provisions of Sections 407.1 through 407.13 and other applicable provisions of this code.

407.1.1 Construction. Group I-2 occupancies wherein mental health patients are restrained shall be housed in buildings of Type IA or Type IB construction.

Exception: Occupancies in Group I-2 wherein mental health patients are restrained are permitted to be housed in one-story buildings of Type IIA, Type IIIA or Type VA construction provided the floor area does not exceed 5,200 square feet (483 m 2 ) between fire walls of two-hour fire-resistive construction with openings protected by fire assemblies having a 1 1 /2-hour fire protection rating.

407.2 Corridors continuity and separation.

Corridors in occupancies in Group I-2 and I-2.1 shall be continuous to the exits and shall be separated from other areas in accordance with Section 407.3 except spaces conforming to Sections 407.2.1 through 407.2.5 .

407.2.1 Waiting and similar areas. Waiting areas and similar public-use areas or group meeting spaces constructed as required for corridors shall be permitted to be open to a corridor, only where all of the following criteria are met:

  1. The spaces are not occupied as care recipient’s sleeping rooms, treatment rooms, incidental uses listed in Table 509, in accordance with Section 509, or hazardous uses.

  2. The open space is protected by an automatic smoke detection system installed in accordance with Section 907.

  3. The corridors onto which the spaces open, in the same smoke compartment, are protected by an automatic smoke detection system installed in accordance with Section 907, and the smoke compartment in which the spaces are located is equipped throughout with quick-response sprinklers in accordance with Section 903.3.2.

  4. The space is arranged so as not to obstruct access to the required exits.

5. Each space is located to permit direct visual super- vision by the facility staff.

407.2.2 Nurse stations. Spaces for care providers’, supervisory staff, doctors’ and nurses’ charting, communications and related clerical areas shall be permit

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY AND USE

ted to be open to, or located within the corridor, provided the required construction along the perimeter of the corridor is maintained. Construction of nurse stations or portions of nurse stations, within the envelope of the corridor is not required to be fire-resistive rated. Nurse stations in new and existing facilities see the California Code of Regulations, Title 19, Division 1, Chapter 1, Subchapter 1, Article 3, Section 3.11(d) for storage and equipment requirements.

In detention or secure mental health facilities, the pro- visions above applies to enclosed nurse stations within the corridor.

407.2.3 Psychiatric treatment areas. Areas wherein psychiatric care recipients who are incapable of self-preservation are housed, or group meeting or multipurpose therapeutic spaces other than incidental uses in accordance with Section 509, under continuous supervision by facility staff, shall be permitted to be open to the corridor, where the following criteria are met:

  1. Each area does not exceed 1,500 square feet (140 m 2 ).

  2. The area is located to permit supervision by the facility staff.

  3. The area is arranged so as not to obstruct any access to the required exits.

  4. The area is equipped with an automatic smoke detection system installed in accordance with Section 907.2.

  5. Not more than one such space is permitted in any one smoke compartment.

  6. The walls and ceilings of the space are constructed as required for corridors.

407.2.4 Gift shops. Gift shops and associated storage that are less than 500 square feet (455 m 2 ) in area shall be permitted to be open to the corridor where such spaces are constructed as required for corridors.

407.2.5 Nursing home housing units. In Group I-2, Condition 1 occupancies, in areas where nursing home residents are housed, shared living spaces, group meeting or multipurpose therapeutic spaces shall be permitted to be open to the corridor, where all of the following criteria are met:

  1. The walls and ceilings of the space are constructed as required for corridors.

  2. The spaces are not occupied as resident sleeping rooms, treatment rooms, incidental uses in accordance with Section 509, or hazardous uses.

  3. The open space is protected by an automatic smoke detection system installed in accordance with Section 907.

  4. The corridors onto which the spaces open, in the same smoke compartment, are protected by an automatic smoke detection system installed in accordance with Section 907, and the smoke compartment in which the spaces are located is equipped throughout with quick-response sprinklers in accordance with Section 903.3.2.

  5. The space is arranged so as not to obstruct access to the required exits.

6. Each space is located to permit direct visual super- vision by the facility staff.

407.2.6 Nursing home cooking facilities. In Group I-2, Condition 1 occupancies, rooms or spaces that contain a cooking facility with domestic cooking appliances shall be permitted in fully sprinklered buildings where all of the following criteria are met:

  1. The number of care recipients housed in the smoke compartment shall not be greater than 30.

  2. The number of care recipients served by the cooking facility shall not be greater than 30.

  3. Only one cooking facility area shall be permitted in a smoke compartment.

4 . The space containing the domestic cooking facility shall be arranged so as not to obstruct access to the required exit.

5 . The cooking appliance shall comply with Section 407.2.7.

407.2.7 Domestic cooking appliances. In Group I-2 occupancies, installation of cooking appliances used in domestic cooking facilities shall comply with all of the following:

  1. The types of cooking appliances permitted shall be limited to ovens, cooktops, ranges, warmers and microwaves.

  2. Domestic cooking hoods installed and constructed in accordance with the California Mechanical Code shall be provided over cooktops and ranges.

  3. Cooktops and ranges shall be protected in accordance with Section 904.14.

  4. A shut-off for the fuel and electrical power supply to the cooking equipment shall be provided in a location to which only staff has access.

  5. A timer shall be provided that automatically deactivates the cooking appliances within a period of not more than 120 minutes.

  6. A portable fire extinguisher shall be provided. Installation shall be in accordance with Section 906, and the extinguisher shall be located within a 30foot (9144 mm) distance of travel from each domestic cooking appliance.

Exceptions:

  1. Cooktops and ranges located within smoke compartments with no patient sleeping or patient care areas are not required to comply with Items 3, 4 and 5 of this section.

  2. Cooktops and ranges used for care recipient training or nutritional counseling are not required to comply with Item 3 of this section.

407.3 Corridor wall construction.

Corridor walls shall be constructed as fire partitions in accordance with Section 708 .

4-20 2022 CALIFORNIA BUILDING CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY AND USE

  1. Rooms arranged as care suites complying with Section 407.4.4.

407.4.1.1 Locking devices. Locking devices that restrict access to a care recipient’s room from the corridor and that are operable only by staff from the corridor side shall not restrict the means of egress from the care recipient’s room.

Exceptions:

  1. This section shall not apply to rooms in psychiatric treatment and similar care areas.

  2. Locking arrangements in accordance with Section 1010.2.14.

407.4.1.2 Basement exits. All rooms below grade shall have not less than one exit access that leads directly to an exterior exit door opening directly to an exit discharge at grade plane or the public way.

407.4.2 Distance of travel. The distance of travel between any point in a Group I-2 and I-2.1 occupancy sleeping room, not located in a care suite, and an exit access door in that room shall be not greater than 50 feet (15 240 mm).

407.4.2.1 Two means of egress. Any sleeping room of more than 1,000 square feet (93 m 2 ) shall have no fewer than two exit access doors from the sleeping room located in accordance with Section 1007.1. Any room, other than sleeping rooms, with an area of more than 2,500 square feet (232 m 2 ) shall have no fewer than two exit access doors from the room located in accordance with Section 1007.1.

407.4.3 Reserved .

407.4.4 Group I-2 and I-2.1 care suites. Care suites in Group I-2 and I-2.1 shall comply with Sections 407.4.4.1 through 407.4.4.4 and either Section 407.4.4.5 or 407.4.4.6.

407.4.4.1 Exit access through care suites. Exit access from all other portions of a building not classified as a care suite shall not pass through a care suite.

407.4.4.2 Separation. Care suites shall be separated from other portions of the building, including other care suites, not less than a one-hour fire barrier complying with Section 707. Each suite of rooms shall be separated from the remainder of the building by not less than a one-hour fire barrier.

407.4.4.3 Access to corridor. Movement from habit- able rooms shall be in accordance with Sections 407.4.4.3.1, 407.4.4.3.2 and 407.4.4.5.3.

407.4.4.3.1 One intervening room. Movement from habitable rooms shall not require passage through more than one intervening room and 100 feet (30 480 mm) distance of travel within the care suite.

407.4.4.3.2 Two intervening rooms. Movement from habitable rooms other than sleeping rooms located within a care suite, shall not require passage through more than two intervening rooms and 50 feet (15 240 mm) distance of exit access travel within the care suite.

Exception: The distance of travel shall be permitted to be increased to 100 feet (38 100 mm)

407.3.1 Corridor doors. In fully sprinklered buildings, corridor doors, other than those in a wall required to be rated by Section 509.4 or for the enclosure of a vertical opening or an exit, shall not have a required fire protection rating and shall not be required to be equipped with selfclosing or automatic-closing devices, but shall provide an effective barrier to limit the transfer of smoke and shall be equipped with positive latching. In Group I-2 Occupancies, self-closing or automatic-closing devices are not required on corridor doors to patient sleeping rooms, treatment rooms and offices located in areas specified in Sections 1224 and 1225, excluding offices specified in Sections 1224.21 and 1225.8. Roller latches are not permitted. Other doors shall conform to Section 716.

407.3.1.1 Door construction. Corridor doors not required to have a fire protection rating shall comply with the following:

  1. Solid doors shall have close-fitting operational tolerances, head and jamb stops.

  2. Dutch-style doors shall have an astragal, rabbet or bevel at the meeting edges of the upper and lower door sections. Both the upper and lower door sections shall have latching hardware. Dutch-style doors shall have hardware that connects the upper and lower sections to function as a single leaf.

407.3.1.2 Swing of corridor doors. Corridor doors, other than those equipped with self-closing or auto- matic-closing devices shall not swing into the required width of corridors.

Exception: In detention and/or secure mental health facilities, doors may swing into required width of corridors as long as 44 inches clear is maintained with any one door open 90 degrees and clear corri- dor widths required in Chapter 12 can be maintained with doors open 180 degrees.

407.3.2 Glazing. In fully sprinklered buildings, fixed fully tempered or laminated glass in wood or metal frames may be used in corridor walls, provided the glazed area does not exceed 25 percent of the areas of the corridor wall of the room. The total area of glass in corridor walls is not limited when the glazing is fixed 1 /3-hour fire-protection-rated glaz- ing in approved frames and the size of individual glazed panel does not exceed 1,296 square inches (0.836 m 2 ).

407.4 Means of egress.

Group I-2 and I-2.1 occupancies shall be provided with means of egress complying with Chapter 10 and Sections 407.4.1 through 407.4.4. The fire safety and evacuation plans provided in accordance with Section 1002.2 shall identify the building components necessary to support a defend-in-place emergency response in accordance with Sections 403 and 404 of the California Fire Code .

407.4.1 Direct access to a corridor. Habitable rooms in Group I-2 and I-2.1 occupancies shall have an exit access door leading directly to a corridor.

Exceptions:

  1. Rooms with exit doors opening directly to the outside at ground level.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY AND USE

where an automatic fire sprinkler system is provided throughout the Group I-2 fire area and an automatic smoke detection system is provided throughout the care suite and installed in accor- dance with NFPA 72.

407.4.4.4 Doors within care suites. Doors in care suites serving habitable rooms shall be permitted to comply with one of the following:

  1. Manually operated horizontal sliding doors permitted in accordance with Exception 9 to Section 1010.1.2.

circulation space, shall be permitted to be grouped into care suites and shall conform to the limitations in Sections 407.4.4.6.1 and 407.4.4.6.2.

407.4.4.6.1 Area. Care suites of rooms, other than sleeping rooms, shall have an area not greater than 10,000 square feet ( 929 m 2 ).

407.4.4.6.2 Exit access. Any room or care suite, other than sleeping rooms, with an area of more than 2,500 square feet (232 m 2 ) shall have not fewer than two exit access doors from the room or care suite located in accordance with Section 1007.

407.4.5 Group I-2 and I-2.1 nonpatient-care suites. The means of egress provisions for nonpatient-care suites shall be in accordance with the primary use and occupancy of the suite.

407.4.5.1 Separation. Nonpatient-care suites shall be separated from other portions of the building, includ- ing other suites, by not less than a 1-hour fire barrier complying with Section 707. Each suite of rooms shall be separated from the remainder of the building by not less than a 1-hour fire barrier.

407.4.5.2 Area. Nonpatient-care suites of rooms shall have an area not greater than 10,000 square feet (929 m 2 ).

407.4.5.3 Automatic sprinkler system protection. Nonpatient-care suites shall be located in fully sprin- klered buildings.

407.5 Smoke barriers.

Smoke barriers shall be provided to subdivide every story used by persons receiving care, treatment or sleeping into not fewer than two smoke compartments. Smoke barriers shall be provided to subdivide other stories with an occupant load of 50 or more persons, regardless of occupancy or use, into not fewer than two smoke compartments. The smoke barrier shall be in accordance with Section 709.

Exceptions:

1. This requirement shall not apply to Group I-2.1 less than 10,000 ft 2 (929 m 2 ).

2. An area in an adjoining occupancy shall be permit- ted to serve as a smoke compartment for a Group I- 2.1 facility if the following criteria are met:

2.1. The separating wall and both compartments meet the requirements of 407.5.

2.2. The Group I-2.1 is less than 22,500 ft 2

(2100 m 2 ).

2.3. Access from the Group I-2.1 to the other occupancy is unrestricted.

3. This requirement shall not apply to the following:

3.1. Any story, not containing a Group I-2 or I- 2.1 occupancy, that is located above a story containing a Group I-2 or I-2.1 occupancy.

3.2. Areas that do not contain a Group I-2 or I- 2.1 occupancy, where such areas are sepa- rated from the Group I-2 or I-2.1 occupancy

  1. Power-operated doors permitted in accordance with Section 1010.1.2, Exception 7.

  2. Means of egress doors complying with Section

407.4.4.5 Care suites containing sleeping room areas. Sleeping rooms shall be permitted to be grouped into care suites where one of the following criteria is met:

1. The arrangement of the care suite allows for direct and constant visual supervision into the sleeping rooms by care providers.

2. In fully sprinklered buildings, an automatic smoke detection system is provided in the sleeping rooms and installed in accordance with Sec- tion 907.2.6.2.2, Item 1 and NFPA 72.

407.4.4.5.1 Area. Care suites containing sleeping rooms shall be not greater than 5,000 square feet ( 465 m 2 ) in area.

Exception s :

1. Care suites containing sleeping rooms shall be permitted to be not greater than 7,500 square feet (696 m 2 ) in area where an automatic fire sprinkler system is pro- vided throughout the Group I-2 fire area.

2. Care suites containing sleeping rooms shall be permitted to be not greater than 10,000 square feet (929 m 2 ) in area where an auto- matic fire sprinkler system is provided throughout the Group I-2 fire area and where an automatic smoke detection system is provided throughout the care suite and installed in accordance with Section 907 .

407.4.4.5.2 Exit access. Any sleeping room, or any care suite that contains sleeping rooms, of more than 1,000 square feet (93 m 2 ) shall have not fewer than two exit access doors from the care suite located in accordance with Section 1007.

407.4.4.5.3 Travel distance. The travel distance between any point in a care suite containing sleeping rooms and an exit access door from that care suite shall be not greater than 100 feet (30 480 mm).

407.4.4.6 Care suites not containing sleeping rooms. Areas not containing sleeping rooms, but only treatment areas and the associated rooms, spaces or

4-22 2022 CALIFORNIA BUILDING CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY AND USE

shall release all such doors within the same smoke compartment.

[F] 407.7 Automatic sprinkler system. Every facility as specified herein wherein more than six clients or patients are housed or cared for on the premises on a 24-hour per- day-basis shall have installed and maintained in an opera- ble condition in every building or portion thereof where clients or patients are housed, an automatic sprinkler system of a type approved by the state fire marshal. The provisions of this subsection shall apply to every person, firm or corporation establishing, maintaining or operating a hospital, children’s home, children’s nursery or institu- tion, or a home or institution for the care of aged or persons with dementia or other cognitive impairments, or any insti- tution for persons with mental illness or persons with developmental disabilities and any nursing or convalescent home, and to any state-owned or state-occupied building used for any of the types of facilities specified herein.

Exceptions:

1. This section shall not apply to homes or institutions for the 24-hour-per-day care of ambulatory children if all of the following conditions are satisfied:

1.1. The buildings or portions thereof in which children are housed are not more than two stories in height and are constructed and maintained in accordance with regulations adopted by the state fire marshal.

1.2. The buildings or portions thereof housing more than six such children shall have installed and maintained in an operable con- dition therein, a fire alarm system of a type approved by the state fire marshal. Such sys- tem shall be activated by detectors respond- ing to invisible particles of combustion other than heat, except that detectors used in clos- ets, usable under-floor areas, storage rooms, bathrooms, attached garages, attics, ple- nums, laundry rooms and rooms of similar use, may be heat-responsive devices.

1.3. The building or portions thereof do not house persons with mental illness or chil- dren with developmental disabilities.

2. This section shall not apply to any one-story building or structure of an institution or home for the care of the aged providing 24-hour-per-day care if such building or structure is used or intended to be used for the hous- ing of no more than six ambulatory aged persons. Such buildings or institutions shall have installed and main- tained in an operable condition herein a fire alarm sys- tem of a type approved by the state fire marshal. Such system shall be activated by detectors responding to either visible or invisible particles of combustion other than heat, except that detectors used in closets, usable under-floor areas, storage rooms, bathrooms, attached garages, attics, plenums, laundry rooms and rooms of similar use, may be heat-responsive devices.

by a horizontal exit in accordance with Sec- tion 1026.2.

3.3. Any story, not containing a Group I-2 or I- 2.1 occupancy, that is located more than one story below a story containing a Group I-2 or I-2.1 occupancy.

3.4. Any story housing only mechanical equip- ment where such story is located below a story containing a Group I-2 or I-2.1 occu- pancy and is separated from the story above by a horizontal assembly having not less than a 2 hour fire resistance-rating.

407.5.1 Smoke compartment size. Stories shall be divided into smoke compartments with an area of not more than 22,500 square feet (2092 m 2 ) in Group I-2 occupancies.

407.5.2 Exit access travel distance. The distance of travel from any point in a smoke compartment to a smoke barrier door shall be not greater than 200 feet (60 960 mm).

407.5.3 Refuge area. Refuge areas shall be provided within each smoke compartment. The size of the refuge area shall accommodate the occupants and care recipients from the adjoining smoke compartment. Where a smoke compartment is adjoined by two or more smoke compartments, the minimum area of the refuge area shall accommodate the largest occupant load of the adjoining compartments. The size of the refuge area shall provide the following:

  1. Not less than 30 net square feet (2.8 m 2 ) for each care recipient confined to bed or stretcher.

  2. Not less than 6 square feet (0.56 m 2 ) for each ambulatory care recipient not confined to bed or stretcher and for other occupants.

Areas or spaces permitted to be included in the calculation of refuge area are corridors, sleeping areas, treatment rooms, lounge or dining areas and other low-hazard areas.

407.5.4 Independent egress. A means of egress shall be provided from each smoke compartment created by smoke barriers without having to return through the smoke compartment from which means of egress originated. Smoke compartments that do not contain an exit shall be provided with direct access to not less than two adjacent smoke compartments.

407.5.5 Horizontal assemblies. Horizontal assemblies supporting smoke barriers required by this section shall be designed to resist the movement of smoke. Elevator lobbies shall be in accordance with Section 3006.2.

407.6 Automatic-closing doors.

Automatic-closing doors with hold-open devices shall comply with Sections 709.5 and 716.2.

407.6.1 Activation of automatic-closing doors. Automatic-closing doors on hold-open devices in accordance with Section 716.2.6.6 shall also close upon activation of a fire alarm system, an automatic sprinkler system, or both. The automatic release of the hold-open device on one door

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY AND USE

707 and a 1-hour horizontal assembly constructed in accor- dance with Section 711 or both.

407.13 Special Hazards.

407.13.1 Storage and handling of flammable, combustible liquids and hazardous materials shall be in accordance with the California Fire Code.

407.13.2 All exterior openings in a boiler room or room containing central heating equipment, if located below openings in another story, or if less than 10 feet (3048 mm) from other doors or windows of the same building, shall be protected by a fire assembly having a three- fourths-hour fire protection rating.

407.13.3 Safety padding. See Sections 308.1 and 408.14.

407.13.4 Floor surfaces. Rooms occupied by patients whose personal liberties are restrained shall have noncom- bustible floor surfaces see Sections 308.1 and 804.4.3.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Building Code (Title 24, Part 2)
California Building Code (Title 24, Part 2)
  1. Chapter 2 — DEFINITIONS AND ABBREVIATIONS
  2. Appendix G — FLOOD-RESISTANT
  3. Appendix L — EARTHQUAKE RECORDING
  4. Appendix M — TSUNAMI-GENERATED
  5. Appendix N — REPLICABLE
  6. Appendix O — PERFORMANCE-BASED
  7. Chapter 1 — SCOPE AND ADMINISTRATION
  8. Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
  9. Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
  10. Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
  11. Chapter 6 — TYPES OF CONSTRUCTION
  12. Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
  13. Chapter 7A — MATERIALS AND CONSTRUCTION
  14. Chapter 8 — INTERIOR FINISHES
  15. Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
  16. Chapter 10 — MEANS OF EGRESS
  17. Chapter 11A — HOUSING ACCESSIBILITY
  18. Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
  19. Chapter 12 — INTERIOR ENVIRONMENT
  20. Chapter 14 — EXTERIOR WALLS
  21. Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
  22. Chapter 16 — STRUCTURAL DESIGN
  23. Chapter 16A — STRUCTURAL DESIGN
  24. Chapter 17 — SPECIAL INSPECTIONS AND TESTS
  25. Chapter 18 — SOILS AND FOUNDATIONS
  26. Chapter 19 — CONCRETE
  27. Chapter 20 — ALUMINUM
  28. Chapter 21 — MASONRY
  29. Chapter 22 — STEEL
  30. Chapter 23 — WOOD
  31. Chapter 24 — GLASS AND GLAZING
  32. Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
  33. Chapter 26 — PLASTIC
  34. Chapter 27 — ELECTRICAL
  35. Chapter 28 — MECHANICAL SYSTEMS
  36. Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
  37. Chapter 31 — SPECIAL CONSTRUCTION
  38. Chapter 31B — PUBLIC POOLS
  39. Chapter 31C — RADIATION
  40. Chapter 31D — FOOD ESTABLISHMENTS
  41. Chapter 31F — MARINE OIL TERMINALS
  42. Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
  43. Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
  44. Chapter 35 — REFERENCED STANDARDS
  45. Appendix A — EMPLOYEE QUALIFICATIONS
  46. Appendix B — BOARD OF APPEALS
  47. Appendix C — GROUP U – AGRICULTURAL BUILDINGS
  48. Appendix D — FIRE DISTRICTS
  49. Appendix F — RODENTPROOFING
  50. Appendix H — SIGNS
  51. Appendix I — PATIO COVERS
  52. Appendix J — GRADING
  53. Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
  54. Appendix P — EMERGENCY HOUSING

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.