Chapter 26 — PLASTIC

Section 2603

California Building Code (Title 24, Part 2) · 2022 edition · updated 2026-09-12 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

2603.1 General.

The provisions of this section shall govern the requirements and uses of foam plastic insulation in buildings and structures.

2603.1.1 Spray-applied foam plastic. Single- and multiple-component spray-applied foam plastic insulation shall comply with the provisions of Section 2603 and ICC 1100-2018.

2603.2 Labeling and identification.

Packages and containers of foam plastic insulation and foam plastic insulation components delivered to the job site shall bear the label of an approved agency showing the manufacturer’s name, product listing, product identification and information sufficient to determine that the end use will comply with the code requirements.

2603.2.1 Labeling of polystyrene foam insulation without flame retardants . In addition to the requirements of Sec- tion 2603.2, polystyrene foam insulation boards manufac-

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

PLASTIC

tured with no flame retardants added shall be labeled in accordance with this section.

1. Each board shall be labeled on each face every 8 square feet in red 1 /2-inch text with the following information:

WARNING - FIRE HAZARD This product is required to be installed below a minimum 3.5-inch-thick concrete slab on grade. NOT FOR VERTICAL OR ABOVE-GRADE APPLICATIONS This product contains NO flame retardants. Not tested for flame spread or smoke develop- ment requirements of the model building codes 2. Each package shall be labeled on at least two sides in red 1 /2-text with the following information:

WARNING – COMBUSTIBLE MATERIAL Keep away from ignition sources.

Maintain code required separation between product storage and structures under construc- tion (minimum 30 feet).

2603.3 Surface-burning characteristics.

Unless otherwise indicated in this section, foam plastic insulation and foam plastic cores of manufactured assemblies shall have a flame spread index of not more than 75 and a smoke-developed index of not more than 450 where tested in the maximum thickness intended for use in accordance with ASTM E84 or UL 723. Loose fill-type foam plastic insulation shall be tested as board stock for the flame spread and smoke-developed indices.

Exceptions:

  1. Smoke-developed index for interior trim as provided for in Section 2604.2.

  2. In cold storage buildings, ice plants, food plants, food processing rooms and similar areas, foam plastic insulation where tested in a thickness of 4 inches (102 mm) shall be permitted in a thickness up to 10 inches (254 mm) where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The approved automatic sprinkler system shall be provided in both the room and that part of the building in which the room is located.

  3. Foam plastic insulation that is a part of a Class A, B or C roof-covering assembly provided that the assembly with the foam plastic insulation satisfactorily passes NFPA 276 or UL 1256. The smokedeveloped index shall not be limited for roof applications.

  4. Foam plastic insulation greater than 4 inches (102 mm) in thickness shall have a maximum flame spread index of 75 and a smoke-developed index of 450 where tested at a minimum thickness of 4 inches (102 mm), provided that the end use is approved in accordance with Section 2603.9 using the maximum thickness and density intended for use.

  5. Flame spread and smoke-developed indices for foam plastic interior signs in covered and open mall buildings provided that the signs comply with Section 402.6.4.

6. Polystyrene foam insulation boards with a maximum thickness of 2 inches when installed below a mini- mum 3.5-inch-thick concrete slab on grade.

2603.4 Thermal barrier.

Except as provided for in Sections 2603.4.1 and 2603.9, foam plastic shall be separated from the interior of a building by an approved thermal barrier of 1 /2inch (12.7 mm) gypsum wallboard, heavy timber in accordance with Section 602.4 or a material that is tested in accordance with and meets the acceptance criteria of both the Temperature Transmission Fire Test and the Integrity Fire Test of NFPA 275. Combustible concealed spaces shall comply with Section 718.

2603.4.1 Thermal barrier not required. The thermal barrier specified in Section 2603.4 is not required under the conditions set forth in Sections 2603.4.1.1 through 2603.4.1.14.

2603.4.1.1 Masonry or concrete construction. A thermal barrier is not required for foam plastic installed in a masonry or concrete wall, floor or roof system where the foam plastic insulation is covered on each face by not less than 1-inch (25 mm) thickness of masonry or concrete.

2603.4.1.2 Cooler and freezer walls. Foam plastic installed in a maximum thickness of 10 inches (254 mm) in cooler and freezer walls shall:

  1. Have a flame spread index of 25 or less and a smoke-developed index of not more than 450, where tested in a minimum 4-inch (102 mm) thickness.

  2. Have flash ignition and self-ignition temperatures of not less than 600°F and 800°F (316°C and 427°C), respectively.

  3. Have a covering of not less than 0.032-inch (0.8 mm) aluminum or corrosion-resistant steel having a base metal thickness not less than 0.0160 inch (0.4 mm) at any point.

  4. Be protected by an automatic sprinkler system in accordance with Section 903.3.1.1. Where the cooler or freezer is within a building, both the cooler or freezer and that part of the building in which it is located shall be sprinklered.

2603.4.1.3 Walk-in coolers. In nonsprinklered buildings, foam plastic having a thickness that does not exceed 4 inches (102 mm) and a maximum flame spread index of 75 is permitted in walk-in coolers or freezer units where the aggregate floor area does not exceed 400 square feet (37 m 2 ) and the foam plastic is covered by a metal facing not less than 0.032-inchthick (0.81 mm) aluminum or corrosion-resistant steel having a minimum base metal thickness of 0.016 inch (0.41 mm). A thickness of up to 10 inches (254 mm) is permitted where protected by a thermal barrier.

26-4 2022 CALIFORNIA BUILDING CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

2603.4.1.4 Exterior walls, one-story buildings. For one-story buildings, foam plastic having a flame spread index of 25 or less, and a smoke-developed index of not more than 450, shall be permitted without thermal barriers in or on exterior walls in a thickness not more than 4 inches (102 mm) where the foam plastic is covered by a thickness of not less than 0.032-inch-thick (0.81 mm) aluminum or corrosion-resistant steel having a base metal thickness of 0.0160 inch (0.41 mm) and the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.

2603.4.1.5 Roofing. A thermal barrier is not required for foam plastic insulation that is a part of a Class A, B or C roof-covering assembly that is installed in accordance with the code and the manufacturer’s instructions and is either constructed as described in Item 1 or tested as described in Item 2.

  1. The roof assembly is separated from the interior of the building by wood structural panel sheathing not less than 0.47 inch (11.9 mm) in thickness bonded with exterior glue, with edges supported by blocking, tongue-and-groove joints, other approved type of edge support or an equivalent material.

  2. The assembly with the foam plastic insulation satisfactorily passes NFPA 276 or UL 1256.

2603.4.1.6 Attics and crawl spaces. Within an attic or crawl space where entry is made only for service of utilities, foam plastic insulation shall be protected against ignition by 1 1 /2-inch-thick (38 mm) mineral fiber insulation; 1 /4-inch-thick (6.4 mm) wood structural panel, particleboard or hardboard; 3 /8-inch (9.5 mm) gypsum wallboard, corrosion-resistant steel having a base metal thickness of 0.016 inch (0.4 mm); 1 1 /2-inchthick (38 mm) self-supported spray-applied cellulose insulation in attic spaces only or other approved material installed in such a manner that the foam plastic insulation is not exposed. The protective covering shall be consistent with the requirements for the type of construction.

2603.4.1.7 Doors not required to have a fire protec- tion rating. Where pivoted or side-hinged doors are permitted without a fire protection rating, foam plastic insulation, having a flame spread index of 75 or less and a smoke-developed index of not more than 450, shall be permitted as a core material where the door facing is of aluminum not less than 0.032 inch (0.8 mm) in thickness or steel having a base metal thickness of not less than 0.016 inch (0.4 mm) at any point.

2603.4.1.8 Exterior doors in buildings of Group R-2 or R-3. In occupancies classified as Group R-2 or R-3, foam-filled exterior entrance doors to individual dwelling units that do not require a fire-resistance rating shall be faced with aluminum, steel, fiberglass, wood or other approved materials.

2603.4.1.9 Garage doors. Where garage doors are permitted without a fire-resistance rating and foam plastic is used as a core material, the door facing shall

PLASTIC

be metal having a minimum thickness of 0.032-inch (0.8 mm) aluminum or 0.010-inch (0.25 mm) steel or the facing shall be minimum 0.125-inch-thick (3.2 mm) wood. Garage doors having facings other than those described in this section shall be tested in accordance with, and meet the acceptance criteria of, DASMA 107.

Exception: Garage doors using foam plastic insulation complying with Section 2603.3 in detached and attached garages associated with one- and twofamily dwellings need not be provided with a thermal barrier.

2603.4.1.10 Siding backer board. Foam plastic insulation of not more than 2,000 British thermal units per square feet (Btu/sq. ft.) (22.7 mJ/m 2 ) as determined by NFPA 259 shall be permitted as a siding backer board with a maximum thickness of 1 /2 inch (12.7 mm), provided that it is separated from the interior of the building by not less than 2 inches (51 mm) of mineral fiber insulation or equivalent or where applied as insulation with re-siding over existing wall construction.

2603.4.1.11 Interior trim. Foam plastic used as interior trim in accordance with Section 2604 shall be permitted without a thermal barrier.

2603.4.1.12 Interior signs. Foam plastic used for interior signs in covered mall buildings in accordance with Section 402.6.4 shall be permitted without a thermal barrier. Foam plastic signs that are not affixed to interior building surfaces shall comply with Chapter 8 of the California Fire Code .

2603.4.1.13 Type V construction. Foam plastic spray applied to a sill plate, joist header and rim joist in Type V construction is subject to all of the following:

  1. The maximum thickness of the foam plastic shall be 3 1 /4 inches (82.6 mm).

  2. The density of the foam plastic shall be in the range of 1.5 to 2.0 pcf (24 to 32 kg/m 3 ).

  3. The foam plastic shall have a flame spread index of 25 or less and an accompanying smoke-developed index of 450 or less when tested in accordance with ASTM E84 or UL 723.

2603.4.1.14 Floors. The thermal barrier specified in Section 2603.4 is not required to be installed on the walking surface of a structural floor system that contains foam plastic insulation where the foam plastic is covered by a minimum nominal 1 /2-inch-thick (12.7 mm) wood structural panel or approved equivalent. The thermal barrier specified in Section 2603.4 is required on the underside of the structural floor system that contains foam plastic insulation where the underside of the structural floor system is exposed to the interior of the building.

Exception: Foam plastic used as part of an interior floor finish.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

PLASTIC

2603.5 Exterior walls of buildings of any height.

Exterior walls of buildings of Type I, II, III or IV construction of any height shall comply with Sections 2603.5.1 through 2603.5.7. Exterior walls of cold storage buildings required to be constructed of noncombustible materials, where the building is more than one story in height, shall comply with the provisions of Sections 2603.5.1 through 2603.5.7. Exterior walls of buildings of Type V construction shall comply with Sections 2603.2, 2603.3 and 2603.4. Fireblocking shall be in accordance with Section 718.2.

2603.5.1 Fire-resistance-rated walls. Where the wall is required to have a fire-resistance rating, data based on tests conducted in accordance with ASTM E119 or UL 263 shall be provided to substantiate that the fire-resistance rating is maintained.

2603.5.2 Thermal barrier. Any foam plastic insulation shall be separated from the building interior by a thermal barrier meeting the provisions of Section 2603.4, unless special approval is obtained on the basis of Section 2603.9.

Exception: One-story buildings complying with Section 2603.4.1.4.

2603.5.3 Potential heat. The potential heat of foam plastic insulation in any portion of the wall or panel shall not exceed the potential heat expressed in Btu per square feet (mJ/m 2 ) of the foam plastic insulation contained in the wall assembly tested in accordance with Section 2603.5.5. The potential heat of the foam plastic insulation shall be determined by tests conducted in accordance with NFPA 259 and the results shall be expressed in Btu per square feet (mJ/m 2 ).

Exception: One-story buildings complying with Section 2603.4.1.4.

2603.5.4 Flame spread and smoke-developed indices. Foam plastic insulation, exterior coatings and facings shall be tested separately in the thickness intended for use, but not to exceed 4 inches (102 mm), and shall each have a flame spread index of 25 or less and a smoke-developed index of 450 or less as determined in accordance with ASTM E84 or UL 723.

Exception: Prefabricated or factory-manufactured panels having minimum 0.020-inch (0.51 mm) aluminum facings and a total thickness of 1 /4 inch (6.4 mm) or less are permitted to be tested as an assembly where the foam plastic core is not exposed in the course of construction.

2603.5.5 Vertical and lateral fire propagation. The exterior wall assembly shall be tested in accordance with and comply with the acceptance criteria of NFPA 285.

Exceptions:

  1. One-story buildings complying with Section 2603.4.1.4.

  2. Wall assemblies where the foam plastic insulation is covered on each face by not less than 1inch (25 mm) thickness of masonry or concrete and meeting one of the following:

2.1. There is no airspace between the insulation and the concrete or masonry.

2.2. The insulation has a flame spread index of not more than 25 as determined in accordance with ASTM E84 or UL 723 and the maximum airspace between the insulation and the concrete or masonry is not more than 1 inch (25 mm).

2603.5.6 Label required. The edge or face of each piece, package or container of foam plastic insulation shall bear the label of an approved agency. The label shall contain the manufacturer’s or distributor’s identification, model number, serial number or definitive information describing the product or materials’ performance characteristics and approved agency’s identification.

2603.5.7 Ignition. Exterior walls shall not exhibit sustained flaming where tested in accordance with NFPA 268. Where a material is intended to be installed in more than one thickness, tests of the minimum and maximum thickness intended for use shall be performed.

Exception: Assemblies protected on the outside with one of the following:

  1. A thermal barrier complying with Section 2603.4.

  2. A minimum 1-inch (25 mm) thickness of concrete or masonry.

  3. Glass-fiber-reinforced concrete panels of a minimum thickness of 3 /8 inch (9.5 mm).

  4. Metal-faced panels having minimum 0.019-inchthick (0.48 mm) aluminum or 0.016-inch-thick (0.41 mm) corrosion-resistant steel outer facings.

  5. A minimum 7 /8-inch (22.2 mm) thickness of stucco complying with Section 2510.

  6. A minimum 1 /4-inch (6.4 mm) thickness of fibercement lap, panel or shingle siding complying with Section 1404.16 and Section 1404.16.1 or 1404.16.2.

2603.6 Roofing.

Foam plastic insulation meeting the requirements of Sections 2603.2, 2603.3 and 2603.4 shall be permitted as part of a roof-covering assembly, provided that the assembly with the foam plastic insulation is a Class A, B or C roofing assembly where tested in accordance with ASTM E108 or UL 790.

2603.7 Foam plastic in plenums as interior finish or inte-rior trim.

rior trim. Foam plastic in plenums used as interior wall or ceiling finish, or interior trim, shall exhibit a flame spread index of 25 or less and a smoke-developed index of 50 or less when tested in accordance with ASTM E84 or UL 723 at the maximum thickness and density intended for use, and shall be tested in accordance with NFPA 286 and meet the acceptance criteria of Section 803.1.1. As an alternative to testing to NFPA 286, the foam plastic shall be approved based on tests conducted in accordance with Section 2603.9.

Exceptions:

  1. Foam plastic in plenums used as interior wall or ceiling finish, or interior trim, shall exhibit a flame spread index of 75 or less and a smoke-developed index of 450 or less when tested in accordance with

26-6 2022 CALIFORNIA BUILDING CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

ASTM E84 or UL 723 at the maximum thickness and density intended for use, where it is separated from the airflow in the plenum by a thermal barrier complying with Section 2603.4.

  1. Foam plastic in plenums used as interior wall or ceiling finish, or interior trim, shall exhibit a flame spread index of 75 or less and a smoke-developed index of 450 or less when tested in accordance with ASTM E84 or UL 723 at the maximum thickness and density intended for use, where it is separated from the airflow in the plenum by corrosion-resistant steel having a base metal thickness of not less than 0.0160 inch (0.4 mm).

  2. Foam plastic in plenums used as interior wall or ceiling finish, or interior trim, shall exhibit a flame spread index of 75 or less and a smoke-developed index of 450 or less when tested in accordance with ASTM E84 or UL 723 at the maximum thickness and density intended for use, where it is separated from the airflow in the plenum by not less than a 1inch (25 mm) thickness of masonry or concrete.

2603.8 Protection against termites.

In areas where the probability of termite infestation is very heavy in accordance with Figure 2603.8, extruded and expanded polystyrene, polyisocyanurate and other foam plastics shall not be installed on the exterior face or under interior or exterior foundation walls or slab foundations located below grade. The clearance between foam plastics installed above grade and exposed earth shall be not less than 6 inches (152 mm).

Exceptions:

  1. Buildings where the structural members of walls, floors, ceilings and roofs are entirely of noncombustible materials or preservative-treated wood.

PLASTIC

  1. An approved method of protecting the foam plastic and structure from subterranean termite damage is provided.

  2. On the interior side of basement walls.

2603.9 Special approval.

Foam plastic shall not be required to comply with the requirements of Section 2603.4 or those of Section 2603.6 where specifically approved based on largescale tests such as, but not limited to, NFPA 286 (with the acceptance criteria of Section 803.1.1.1), FM 4880, UL 1040 or UL 1715. Such testing shall be related to the actual end-use configuration and be performed on the finished manufactured foam plastic assembly in the maximum thickness intended for use. Foam plastics that are used as interior finish on the basis of special tests shall conform to the flame spread and smokedeveloped requirements of Chapter 8. Assemblies tested shall include seams, joints and other typical details used in the installation of the assembly and shall be tested in the manner intended for use.

[BS] 2603.10 Wind resistance. Foam plastic insulation complying with ASTM C578 and ASTM C1289 and used as exterior wall sheathing on framed wall assemblies shall comply with ANSI/FS 100 for wind pressure resistance.

[BS] 2603.11 Cladding attachment over foam sheathing to masonry or concrete wall construction. Cladding shall be specified and installed in accordance with Chapter 14 and the cladding manufacturer’s installation instructions or an approved design. Foam sheathing shall be attached to masonry or concrete construction in accordance with the insulation manufacturer’s installation instructions or an approved design. Furring and furring attachments through foam sheathing shall be designed to resist design loads determined in accordance with Chapter 16, including support of cladding weight as applicable. Fasteners used to attach clad

FIGURE 2603.8 TERMITE INFESTATION PROBABILITY MAP

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

PLASTIC

ding or furring through foam sheathing to masonry or concrete substrates shall be approved for application into masonry or concrete material and shall be installed in accordance with the fastener manufacturer’s installation instructions.

Exceptions:

  1. Where the cladding manufacturer has provided approved installation instructions for application over foam sheathing and connection to a masonry or concrete substrate, those requirements shall apply.

  2. For exterior insulation and finish systems, refer to Section 1407.

  3. For anchored masonry or stone veneer installed over foam sheathing, refer to Section 1404.

2603.11.1 Additional requirements. [OSHPD 1, 1R, 2, 4 & 5, DSA-SS, DSA-SS/CC] In addition to the require- ments of Section 2603.11, cladding and foam sheathing supports and attachments shall be designed and submitted to the enforcement agency for approval.

[BS] 2603.12 Cladding attachment over foam sheathing to cold-formed steel framing. Cladding shall be specified and installed in accordance with Chapter 14 and the cladding manufacturer’s approved installation instructions, including any limitations for use over foam plastic sheathing, or an approved design. Where used, furring and furring attachments shall be designed to resist design loads determined in accordance with Chapter 16. In addition, the cladding or furring attachments through foam sheathing to cold-formed steel framing shall meet or exceed the minimum fastening requirements of Sections 2603.12.1 and

2603.12.2, or an approved design for support of cladding weight.

Exceptions:

  1. Where the cladding manufacturer has provided approved installation instructions for application over foam sheathing, those requirements shall apply.

  2. For exterior insulation and finish systems, refer to Section 1407.

  3. For anchored masonry or stone veneer installed over foam sheathing, refer to Section 1404.

[BS] 2603.12.1 Direct attachment. Where cladding is installed directly over foam sheathing without the use of furring, cladding minimum fastening requirements to support the cladding weight shall be as specified in Table 2603.12.1.

[BS] 2603.12.2 Furred cladding attachment. Where steel or wood furring is used to attach cladding over foam sheathing, furring minimum fastening requirements to support the cladding weight shall be as specified in Table 2603.12.2. Where placed horizontally, wood furring shall be preservative-treated wood in accordance with Section 2303.1.9 or naturally durable wood and fasteners shall be corrosion resistant in accordance Section 2304.10.6. Steel furring shall have a minimum G60 galvanized coating.

2603.12.3 Additional requirements. [OSHPD 1, 1R, 2, 4 & 5, DSA-SS, DSA-SS/CC] In addition to the requirements of Section 2603.12, 2603.12.1 and 2603.12.2, cladding and foam sheathing supports and attachments shall be designed and submitted to the enforcement agency for approval.

[BS]TABLE 2603.12.1 CLADDING MINIMUM FASTENING REQUIREMENTS FOR DIRECT ATTACHMENT OVER FOAM PLASTIC SHEATHING TO SUPPORT CLADDING WEIGHT a

CLADDING FASTENER
THROUGH FOAM
SHEATHING INTO:
CLADDING
FASTENER TYPE
AND MINIMUM SIZEb
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
MAXIMUM THICKNESS OF FOAM SHEATHINGc
(inches)
CLADDING FASTENER
THROUGH FOAM
SHEATHING INTO:
CLADDING
FASTENER TYPE
AND MINIMUM SIZEb
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
16″ o.c. fastener horizontal spacing 16″ o.c. fastener horizontal spacing 16″ o.c. fastener horizontal spacing 16″ o.c. fastener horizontal spacing 24″ o.c. fastener horizontal spacing 24″ o.c. fastener horizontal spacing 24″ o.c. fastener horizontal spacing 24″ o.c. fastener horizontal spacing
CLADDING FASTENER
THROUGH FOAM
SHEATHING INTO:
CLADDING
FASTENER TYPE
AND MINIMUM SIZEb
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
Cladding weight Cladding weight Cladding weight Cladding weight Cladding weight Cladding weight Cladding weight Cladding weight
CLADDING FASTENER
THROUGH FOAM
SHEATHING INTO:
CLADDING
FASTENER TYPE
AND MINIMUM SIZEb
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
3 psf 11 psf 18 psf 25 psf 3 psf 11 psf 18 psf 25 psf
Cold-formed steel framing
(minimum penetration of
steel thickness plus 3
threads)
#8 screw into
33 mil steel or
thicker
6 3.00 2.95 2.20 1.45 3.00 2.35 1.25 DR
Cold-formed steel framing
(minimum penetration of
steel thickness plus 3
threads)
#8 screw into
33 mil steel or
thicker
8 3.00 2.55 1.60 0.60 3.00 1.80 DR DR
Cold-formed steel framing
(minimum penetration of
steel thickness plus 3
threads)
#8 screw into
33 mil steel or
thicker
12 3.00 1.80 DR DR 3.00 0.65 DR DR
Cold-formed steel framing
(minimum penetration of
steel thickness plus 3
threads)
#10 screw into
33 mil steel
6 4.00 3.50 2.70 1.95 4.00 2.90 1.70 0.55
Cold-formed steel framing
(minimum penetration of
steel thickness plus 3
threads)
#10 screw into
33 mil steel
8 4.00 3.10 2.05 1.00 4.00 2.25 0.70 DR
Cold-formed steel framing
(minimum penetration of
steel thickness plus 3
threads)
#10 screw into
33 mil steel
12 4.00 2.25 0.70 DR 3.70 1.05 DR DR
Cold-formed steel framing
(minimum penetration of
steel thickness plus 3
threads)
#10 screw into
43 mil steel or
thicker
6 4.00 4.00 4.00 3.60 4.00 4.00 3.45 2.70
Cold-formed steel framing
(minimum penetration of
steel thickness plus 3
threads)
#10 screw into
43 mil steel or
thicker
8 4.00 4.00 3.70 3.00 4.00 3.85 2.80 1.80
Cold-formed steel framing
(minimum penetration of
steel thickness plus 3
threads)
#10 screw into
43 mil steel or
thicker
12 4.00 3.85 2.80 1.80 4.00 3.05 1.50 DR

For SI: 1 inch = 25.4 mm, 1 pound per square foot (psf) = 0.0479 kPa, 1 pound per square inch = 0.00689 MPa. DR = design required, o.c. = on center. a. Cold-formed steel framing shall be minimum 33 ksi steel for 33 mil and 43 mil steel and 50 ksi steel for 54 mil steel or thicker. b. Screws shall comply with the requirements of AISI S240. c. Foam sheathing shall have a minimum compressive strength of 15 pounds per square inch in accordance with ASTM C578 or ASTM C1289.

26-8 2022 CALIFORNIA BUILDING CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

PLASTIC

[BS]TABLE 2603.12.2 FURRING MINIMUM FASTENING REQUIREMENTS FOR APPLICATION OVER FOAM PLASTIC SHEATHING TO SUPPORT CLADDING WEIGHT a

FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZEb
MINIMUM
PENETRATION
INTO WALL
FRAMING (inches)
FASTENER
SPACING IN
FURRING
(inches)
MAXIMUM THICKNESS OF FOAM SHEATHINGd
(inches)
FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZEb
MINIMUM
PENETRATION
INTO WALL
FRAMING (inches)
FASTENER
SPACING IN
FURRING
(inches)
16″ o.c. furringe 16″ o.c. furringe 16″ o.c. furringe 16″ o.c. furringe 24″ o.c. furringe 24″ o.c. furringe 24″ o.c. furringe 24″ o.c. furringe
FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZEb
MINIMUM
PENETRATION
INTO WALL
FRAMING (inches)
FASTENER
SPACING IN
FURRING
(inches)
Cladding weight Cladding weight Cladding weight Cladding weight Cladding weight Cladding weight Cladding weight Cladding weight
FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZEb
MINIMUM
PENETRATION
INTO WALL
FRAMING (inches)
FASTENER
SPACING IN
FURRING
(inches)
3 psf 11 psf 18 psf 25 psf 3 psf 11 psf 18 psf 25 psf
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
33 mil cold-
formed
steel stud
#8 screw Steel thickness
plus 3 threads
12 3.00 1.80 DR DR 3.00 0.65 DR DR
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
33 mil cold-
formed
steel stud
#8 screw Steel thickness
plus 3 threads
16 3.00 1.00 DR DR 2.85 DR DR DR
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
33 mil cold-
formed
steel stud
#8 screw Steel thickness
plus 3 threads
24 2.85 DR DR DR 2.20 DR DR DR
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
33 mil cold-
formed
steel stud
#10 screw Steel thickness
plus 3 threads
12 4.00 2.25 0.70 DR 3.70 1.05 DR DR
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
33 mil cold-
formed
steel stud
#10 screw Steel thickness
plus 3 threads
16 3.85 1.45 DR DR 3.40 DR DR DR
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
33 mil cold-
formed
steel stud
#10 screw Steel thickness
plus 3 threads
24 3.40 DR DR DR 2.70 DR DR DR
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
43 mil or
thicker cold-
formed
steel stud
#8 Screw Steel thickness
plus 3 threads
12 3.00 1.80 DR DR 3.00 0.65 DR DR
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
43 mil or
thicker cold-
formed
steel stud
#8 Screw Steel thickness
plus 3 threads
16 3.00 1.00 DR DR 2.85 DR DR DR
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
43 mil or
thicker cold-
formed
steel stud
#8 Screw Steel thickness
plus 3 threads
24 2.85 DR DR DR 2.20 DR DR DR
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
43 mil or
thicker cold-
formed
steel stud
#10 screw Steel thickness
plus 3 threads
12 4.00 3.85 2.80 1.80 4.00 3.05 1.50 DR
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
43 mil or
thicker cold-
formed
steel stud
#10 screw Steel thickness
plus 3 threads
16 4.00 3.30 1.95 0.60 4.00 2.25 DR DR
Minimum 33 mil
steel furring or
minimum 1x
wood furringc
43 mil or
thicker cold-
formed
steel stud
#10 screw Steel thickness
plus 3 threads
24 4.00 2.25 DR DR 4.00 0.65 DR DR

For SI: 1 inch = 25.4 mm, 1 pound per square foot (psf) = 0.0479 kPa, 1 pound per square inch = 0.00689 MPa. DR = Design Required, o.c. = on center. a. Wood furring shall be spruce-pine-fir or any softwood species with a specific gravity of 0.42 or greater. Steel furring shall be minimum 33 ksi steel.

Coldformed steel studs shall be minimum 33 ksi steel for 33 mil and 43 mil thickness and 50 ksi steel for 54 mil steel or thicker. b. Screws shall comply with the requirements of AISI S240. c. Where the required cladding fastener penetration into wood material exceeds 3/4 inch and is not more than 11/2 inches, a minimum 2-inch nominal wood

furring or an approved design shall be used. d. Foam sheathing shall have a minimum compressive strength of 15 pounds per square inch in accordance with ASTM C578 or ASTM C1289. e. Furring shall be spaced not more than 24 inches on center, in a vertical or horizontal orientation. In a vertical orientation, furring shall be located over wall

studs and attached with the required fastener spacing. In a horizontal orientation, the indicated 8-inch and 12-inch fastener spacing in furring shall be achieved by use of two fasteners into studs at 16 inches and 24 inches on center, respectively.

[BS] 2603.13 Cladding attachment over foam sheathing to wood framing. Cladding shall be specified and installed in accordance with Chapter 14 and the cladding manufacturer’s installation instructions. Where used, furring and furring attachments shall be designed to resist design loads determined in accordance with Chapter 16. In addition, the cladding or furring attachments through foam sheathing to framing shall meet or exceed the minimum fastening requirements of Section 2603.13.1 or 2603.13.2, or an approved design for support of cladding weight.

Exceptions:

  1. Where the cladding manufacturer has provided approved installation instructions for application over foam sheathing, those requirements shall apply.

  2. For exterior insulation and finish systems, refer to Section 1407.

  3. For anchored masonry or stone veneer installed over foam sheathing, refer to Section 1404.

[BS] 2603.13.1 Direct attachment. Where cladding is installed directly over foam sheathing without the use of furring, minimum fastening requirements to support the cladding weight shall be as specified in Table 2603.13.1.

[BS] 2603.13.2 Furred cladding attachment. Where wood furring is used to attach cladding over foam

sheathing, furring minimum fastening requirements to support the cladding weight shall be as specified in Table 2603.13.2. Where placed horizontally, wood furring shall be preservative-treated wood in accordance with Section 2303.1.9 or naturally durable wood and fasteners shall be corrosion resistant in accordance with Section 2304.10.6.

2603.13.3 Additional requirements. [DSA-SS, DSA- SS/CC, OSHPD 1, 1R, 2, 4 & 5] In addition to the requirements of Section 2603.13, 2603.13.1 and 2603.13.2, cladding and foam sheathing supports and attachments shall be designed and submitted to the enforcement agency for approval.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Building Code (Title 24, Part 2)
California Building Code (Title 24, Part 2)
  1. Chapter 2 — DEFINITIONS AND ABBREVIATIONS
  2. Appendix G — FLOOD-RESISTANT
  3. Appendix L — EARTHQUAKE RECORDING
  4. Appendix M — TSUNAMI-GENERATED
  5. Appendix N — REPLICABLE
  6. Appendix O — PERFORMANCE-BASED
  7. Chapter 1 — SCOPE AND ADMINISTRATION
  8. Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
  9. Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
  10. Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
  11. Chapter 6 — TYPES OF CONSTRUCTION
  12. Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
  13. Chapter 7A — MATERIALS AND CONSTRUCTION
  14. Chapter 8 — INTERIOR FINISHES
  15. Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
  16. Chapter 10 — MEANS OF EGRESS
  17. Chapter 11A — HOUSING ACCESSIBILITY
  18. Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
  19. Chapter 12 — INTERIOR ENVIRONMENT
  20. Chapter 14 — EXTERIOR WALLS
  21. Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
  22. Chapter 16 — STRUCTURAL DESIGN
  23. Chapter 16A — STRUCTURAL DESIGN
  24. Chapter 17 — SPECIAL INSPECTIONS AND TESTS
  25. Chapter 18 — SOILS AND FOUNDATIONS
  26. Chapter 19 — CONCRETE
  27. Chapter 20 — ALUMINUM
  28. Chapter 21 — MASONRY
  29. Chapter 22 — STEEL
  30. Chapter 23 — WOOD
  31. Chapter 24 — GLASS AND GLAZING
  32. Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
  33. Chapter 26 — PLASTIC
  34. Chapter 27 — ELECTRICAL
  35. Chapter 28 — MECHANICAL SYSTEMS
  36. Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
  37. Chapter 31 — SPECIAL CONSTRUCTION
  38. Chapter 31B — PUBLIC POOLS
  39. Chapter 31C — RADIATION
  40. Chapter 31D — FOOD ESTABLISHMENTS
  41. Chapter 31F — MARINE OIL TERMINALS
  42. Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
  43. Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
  44. Chapter 35 — REFERENCED STANDARDS
  45. Appendix A — EMPLOYEE QUALIFICATIONS
  46. Appendix B — BOARD OF APPEALS
  47. Appendix C — GROUP U – AGRICULTURAL BUILDINGS
  48. Appendix D — FIRE DISTRICTS
  49. Appendix F — RODENTPROOFING
  50. Appendix H — SIGNS
  51. Appendix I — PATIO COVERS
  52. Appendix J — GRADING
  53. Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
  54. Appendix P — EMERGENCY HOUSING

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.