Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
710 Smoke Partitions — 2025 California Building Code
California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Building Code (Title 24, Part 2) § 710 · Effective January 1, 2026 · Official source: Building Standards Commission
710.1 General.¶
Smoke partitions installed as required elsewhere in the code shall comply with this section.
710.2 Materials.¶
The walls shall be of materials permitted by the building type of construction. In Group I-2, smoke partitions shall have framing covered with noncombustible materials having an approved thermal barrier with an index of not less than 15 in accor- dance with FM 4880, UL 1040, NFPA 286 or UL 1715.
710.3 Fire-resistance rating.¶
Unless required elsewhere in the code, smoke partitions are not required to have a fire-resistance rating.
710.4 Continuity.¶
Smoke partitions shall extend from the top of the foundation or floor below to the underside of the floor or roof sheathing, deck or slab above or to the underside of the ceiling above where the ceiling membrane is constructed to limit the transfer of smoke.
Exception: In Group I-2, a lay-in ceiling system shall be considered capable of limiting the transfer of smoke where the ceiling tiles weigh not less than 1 pound per square foot (4.882 kg/m2) and where the HVAC system is fully ducted in accordance with the Cali- fornia Mechanical Code.
710.4.1 Smoke partition walls enclosing elevator lobbies. Smoke partition walls used to enclose elevator lobbies in accordance with Section 3006.3 shall form an enclosure that terminates at a fire barrier having a fire-resistance rating of not less than 1 hour, another smoke partition or an outside wall.
710.5 Openings.¶
Openings in smoke partitions shall comply with Sections 710.5.1 through 710.5.3.
7-18 2025 CALIFORNIA BUILDING CODE
FIRE AND SMOKE PROTECTION FEATURES
710.5.1 Windows. Windows in smoke partitions shall be sealed to resist the free passage of smoke or be automatic-closing upon detection of smoke.
710.5.2 Doors. Doors in smoke partitions shall comply with Sections 710.5.2.1 through 710.5.2.3.
710.5.2.1 Louvers. Doors in smoke partitions shall not include louvers.
Exception: Where permitted in accordance with Section 407.3.1.1.
710.5.2.2 Smoke and draft control doors. Where required elsewhere in the code, doors in smoke partitions shall meet the requirements for a smoke and draft control door assembly tested in accordance with UL 1784. The air leakage rate of the door assembly shall not exceed 3.0 cubic feet per minute per square foot [0.015424 m [3] /(s × m [2] )] of door opening at 0.10 inch of water (25 Pa) for both the ambient temperature test and the elevated temperature exposure test. Installation of smoke doors shall be in accordance with NFPA 105.
710.5.2.2.1 Smoke and draft control door labeling. Smoke and draft control doors complying only with UL 1784 shall be permitted to show the letter “S” on the manufacturer’s labeling.
710.5.2.3 Self- or automatic-closing doors. Where required elsewhere in the code, doors in smoke partitions shall be self- or automatic-closing by smoke detection in accordance with Section 716.2.6.6.
710.5.3 Pass-through openings in Group I-2, Condition 2. Where pass-through openings are provided in smoke partitions in Group I-2, Condition 2 occupancies, such openings shall comply with the following:
- The smoke compartment in which the pass-through openings occur does not contain a patient care suite or sleeping
room.
- Pass-through openings are installed in a wall, door or vision panel that is not required to have a fire-resistance rating.
- The top of the pass-through opening is located a maximum of 48 inches (1219 mm) above the floor.
- The aggregate area of all such pass-through openings within a single room shall not exceed 80 square inches (0.05 m [2] ).
710.6 Penetrations.¶
The space around penetrating items shall be filled with an approved material to limit the free passage of smoke.
710.7 Joints.¶
Joints shall be filled with an approved material to limit the free passage of smoke.
710.8 Ducts and air transfer openings.¶
The space around a duct penetrating a smoke partition shall be filled with an approved material to limit the free passage of smoke. Air transfer openings in smoke partitions shall be provided with a smoke damper complying with Section 717.3.2.2. For Group A, E, H, I, L and R occupancies, high-rise buildings, and other applications listed in Section 1.11 regulated by the Office of the State Fire Marshal, duct openings in smoke partitions shall also be provided with a smoke damper comply- ing with Section 717.3.2.2.
Exception s :
- Where the installation of a smoke damper will interfere with the operation of a required smoke control system in accordance with Section 909, approved alternative protection shall be utilized. 2. [SFM] Smoke dampers are not required in corridor penetrations where the duct is constructed of steel not less than 0.019- inch (0.40 mm) in thickness and there are no openings serving the corridor.