Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES

Section 705 — EXTERIOR WALLS

2025 California Building Code (Title 24, Part 2) · 2025 edition · ingested 2026-07-07 · California

Full text via GoCodebook AI

We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.

Ask about this chapter

705.1 General. Exterior walls shall comply with this section.

705.1 General. Exterior walls shall comply with this section.

705.2 Projections.

705.2 Projections. Cornices, eave overhangs, exterior balconies and similar projections extending beyond the exterior wall shall conform to the requirements of this section and Section 1405. Exterior egress balconies and exterior exit stairways and ramps shall comply with Sections 1021 and 1027, respectively. Projections shall not extend any closer to the line used to determine the fire separation distance than shown in Table 705.2. Exception: Buildings on the same lot and considered as portions of one building in accordance with Section 705.3 are not required to comply with this section for…

705.3 Buildings on the same lot.

705.3 Buildings on the same lot. For the purposes of determining the required wall and opening protection, projections and roofcovering requirements, buildings on the same lot shall be assumed to have an imaginary line between them. Where a new building is to be erected on the same lot as an existing building, the location of the assumed imaginary line with relation to the existing building shall be such that the exterior wall and opening protection of the existing building meet the criteria as set forth in Sections 705.5 and 705.9. Exceptions: 1. Two or more buildings on the same lot shall…

705.4 Materials.

705.4 Materials. Exterior walls shall be of materials permitted by the building’s type of construction.

705.5 Fire-resistance ratings.

705.5 Fire-resistance ratings. For other than Group A, E, H, I, L and R occupancies, high-rise buildings, and other applications listed in Section 1.11 exterior walls shall be fire-resistance rated in accordance with Table 601, based on the type of construction, and Table 705.5, based on the fire separation distance. The required fire-resistance rating of exterior walls with a fire separation distance of greater than 10 feet (3048 mm) shall be rated for exposure to fire from the inside. The required fire-resistance rating of exterior walls with a fire separation distance of less than or equal…

705.6 Continuity.

705.6 Continuity. The fire-resistance rating of exterior walls shall extend from the top of the foundation or floor/ceiling assembly below to one of the following: 1. The underside of the floor sheathing, roof sheathing, deck or slab above. 2. The underside of a floor/ceiling or roof/ceiling assembly having a fire-resistance rating equal to or greater than the exterior wall and the fire separation distance is greater than 10 feet. Parapets shall be provided as required by Section 705.12.

705.7 Structural stability.

705.7 Structural stability. Interior structural elements that brace the exterior wall but that are not located within the plane of the exterior wall shall have the minimum fire-resistance rating required in Table 601 for that structural element. Structural elements that brace the exterior wall but are located outside of the exterior wall or within the plane of the exterior wall shall have the minimum fireresistance rating required in Table 601 and Table 705.5 for the exterior wall. 705.7.1 Floor assemblies in Type III construction. In Type III construction where a floor assembly supports…

705.8 Unexposed surface temperature.

705.8 Unexposed surface temperature. Where protected openings are not limited by Section 705.9, the limitation on the rise of temperature on the unexposed surface of exterior walls as required by ASTM E119 or UL 263 shall not apply. Where protected openings are limited by Section 705.9, the limitation on the rise of temperature on the unexposed surface of exterior walls as required by ASTM E119 or UL 263 shall not apply provided that a correction is made for radiation from the unexposed exterior wall surface in accordance with the following formula: Equation 7-1 A e = A + ( A f × F eo )…

705.9 Openings.

705.9 Openings. Openings in exterior walls shall comply with Sections 705.9.1 through 705.9.6. Table 1: TABLE 705.9—MAXIMUM AREA OF EXTERIOR WALL OPENINGS<brBASED ON FIRE SEPARATION DISTANCE AND DEGREE OF OPENING PROTECTIONCol2Col3 --------- FIRE SEPARATION DISTANCE (feet) DEGREE OF OPENING PROTECTION ALLOWABLE AREAa 0 to less than 3b, c, kUnprotected, Nonsprinklered (UP, NS)Not Permittedk 0 to less than 3b, c, kUnprotected, Sprinklered (UP, S)iNot Permittedk 0 to less than 3b, c, kProtected (P)Not Permittedk 3 to less than 5d, eUnprotected, Nonsprinklered (UP, NS)Not Permitted 3 to less than…

705.10 Joints.

705.10 Joints. Joints made in or between exterior walls required by this section to have a fire-resistance rating shall comply with Section 715. Exception: Joints in exterior walls that are permitted to have unprotected openings. 705.10.1 Voids. The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 715.4.

705.11 Ducts and air transfer openings.

705.11 Ducts and air transfer openings. Penetrations by air ducts and air transfer openings in fire-resistance-rated exterior walls required to have protected openings shall comply with Section 717. Exception: Foundation vents installed in accordance with this code are permitted.

705.12 Parapets. Parapets shall be provided on exterior walls of buildings.

705.12 Parapets. Parapets shall be provided on exterior walls of buildings. Exceptions: A parapet need not be provided on an exterior wall where any of the following conditions exist: 1. The wall is not required to be fire-resistance rated in accordance with Table 705.5 because of fire separation distance. 2. The building has an area of not more than 1,000 square feet (93 m [2] ) on any floor. 3. Walls that terminate at roofs of not less than 2-hour fire-resistance-rated construction or where the roof, including the deck or slab and supporting construction, is constructed entirely of…

705.13 Exterior graphics on exterior walls of high-rise buildings.

705.13 Exterior graphics on exterior walls of high-rise buildings. Where installed on the exterior walls of high-rise buildings, exterior graphics, both permanent and temporary, greater than 100 square feet in area or greater than 10 feet in either dimension shall comply with the following conditions subject to the review and approval of the fire code official and building official: 1. The materials used for graphics installed at a height greater than 40 feet above the grade plane shall be noncombustible mate- rials or shall have a flame spread index not greater than 25 when tested in…