CRSC · California Referenced Standards Code
Marking, installation instructions, and component acceptance
This hub summarizes CRSC rules on product marking, required installation/operating instructions, and the acceptance of tested/listed components for code compliance.
Last reviewed: July 6, 2026
Overview
This area of the California Referenced Standards Code (CRSC) collects the requirements that manufacturers, listing agencies and installers must follow for product markings, installation/operating instructions, and how component parts are accepted for use in listed assemblies. It covers device-level marking (manufacturer, model, ratings, “Do Not Paint,” listing information), required installation wiring diagrams and technical bulletins, and the documentation and tests needed for acceptance and final approval of systems such as detectors, alarm devices, exit hardware and releasing assemblies (§12‑72‑204, §12‑72‑205, §12‑72‑302) .
The CRSC also explains marking and instruction obligations for specific standards (for example security bars and panic hardware) and the conditions under which individually tested and listed component parts need not be retested when incorporated into an assembly (§12‑3‑12, §12‑3‑13, §12‑10‑301; tested/listed component acceptance provisions) . These provisions matter because durable markings, clear installation instructions, and documented acceptance/testing are essential to safe, code-compliant installation, inspection and maintenance—and they are prerequisites to final approval by the authority having jurisdiction.
In this section
Code references
Grounded in the retrieved California Referenced Standards Code — click a citation to read the verbatim passage:
CRSC § 12-72 High relevance — show source text
(f) Differing constructions. A detector having materials or forms of construction differing from this standard may be investigated and tested according to the intent of this standard, and if found to be substantially equivalent may be given recognition for approval and listing. The office of the State Fire Marshal shall be consulted for general requirements and performance standards.
(g) Operating and installation instructions.
- A copy of the operating and installation instructions and related schematic wiring diagrams and installation drawings are to be furnished with the sample submitted for investigation to be used as a guide in the examination and test of the detector and for this purpose need not be in final printed form. The information may be included in a manual or technical bulletin.
- The instructions and drawings should include such directions and information as deemed by the manufacturer to be adequate for attaining proper and safe installation, maintenance and operation of the detector. See Section 12-72-302 (b).
GENERAL
12-72-302.
(a) Construction.
- A detector shall be so constructed that it will be reliable and sufficiently durable for its intended installation and use.
- A component of a detector shall comply with the requirements for that component, except that such requirements may be modified if appropriate for the particular application.
- Except where specifically indicated otherwise, the construction requirements specified for a detector shall also apply for any remote accessories with which it is to be employed.
- Each detector is to be provided with a means for monitoring the relative sensitivity of the unit after it has been installed.
- The monitoring means may be by means of a jack or terminals for connection of a meter, or by a visual means which would be visible with the unit installed, or equivalent.
- The use of a plug-in type detector assembly, which may be removed readily for insertion of an adapter connected to metering equipment, would be acceptable.
(b) Marking.
- A detector shall be permanently marked with the following information, except where it is indicated that the information may appear on an installation wiring diagram. A. Name or identifying symbol of the manufacturer or vendor. B. Model number or equivalent and serial number or equivalent. C. Electrical rating, in volts, amperes or watts, and frequency for each circuit. May appear on the installation wiring diagram. D. Sensitivity setting and reference to the region of sensitivity such as maximum, nominal or intermediate or minimum. If a detector is intended to be adjusted in the field, the range of sensitivity is to be indicated. The sensitivity shall be indicated as an instrument reading. A sensitivity indication other than an instrument reading may be employed if it provides an equivalent indication of the sensitivity of the detector. May appear on the installation wiring diagram. E. Correct mounting position if a unit is intended to be mounted in a definite position. This information may appear on the installation wiring diagram. F. Identification of lights, switches, meters, etc., regarding their function, unless their operation is obvious. G. Maximum rating of fuse in each fuseholder. Located adjacent to the fuseholder.
134 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
PROTECTIVE SIGNALING SYSTEMS
H. Reference to an installation wiring diagram, if not attached to the detector, by drawing number and issue number of date.
I. For a detector which employs a radioactive material, the following information shall be indicated directly on the unit: type, amount, radiation symbol (optional), safe disposal and a caution notice which shall read as follows: CAUTION—Contains Radioactive Material, or its equivalent wording.
CRSC § 90.2 High relevance — show source text
- After the carrier (service) pipe is installed in the casing, the end of the casing nearest the house or structure being supplied shall be sealed so that any leaking gas cannot migrate through the casing to the building.
A. If the properly sized casing plug is available for PE 2708 casings, as listed in GDS B-90.2, use it for this purpose. Wrap the casing plug with Tac-Tape (Code 507036) or equivalent tape wrap. If a suitable plug is not available, a plug of duct seal at least 1″ long should be used, followed by the Tac-Tape or equivalent. If the other end of the service conduit for the gas line terminates near another building or structure into which gas could migrate, take special precautions to vent the casing to a safe location.
B. PVC service conduit shall be sealed in accordance with Item 18A above.
PG&E Internal Information ©2021 Pacific Gas and Electric Company. All rights reserved.
TD-4001P-01-F01, Gas Design Standard (GDS) Template
Page 7 of 12
Gas Service and Mains in Plastic Casing A-75
Publication Date: 03/23/2021 Effective Date: 03/23/2021 Rev. 2c
Installation Requirements (continued)
A 3″ wide plastic marking tape with the words “Gas Line in Conduit” (Code 373371) shall be installed on PVC service conduit. The marking tape shall be spiral wrapped around the casing for its entire length and held in place with adhesive tape at 10′ intervals. The marking tape shall be wrapped such that the horizontal distance between spirals does not exceed 36″.
The owner of an empty casing shall furnish to PG&E, prior to acceptance of the casing, an as-built drawing (or service record) and a PG&E inspection record indicating that the casing was installed pursuant to this document.
Where a gas service or main is installed in a sleeve or conduit, document the information on the plat sheet and service order, as applicable. Refer to GDS A-93.1 for mapping and records management requirements.
Maintenance and Operations
Gas crews and other employees who could respond to a gas emergency should be made aware that some services and mains have been installed through plastic sleeves and conduits. They should be trained on how to recognize and to squeeze off pipe that has been so installed.
PE 2708 and PVC service conduits and gas main sleeves may be accessed by window cutting using Company-approved tools. Precautions shall be taken to avoid damaging the carrier pipe.
A gas service or main that is installed in a service conduit or gas main sleeve that has been squeezed off must be replaced. GDS A-93.1 provides specific replacement instructions.
Repair all damaged PVC service conduit in accordance with Numbered Document 058548.
If a broken service conduit or any other problems brought about by using a casing delays Company work, bill the applicant for lost time and associated repair or replacement costs before service completion.
Target Audience
Personnel who are involved in designing, procuring, or installing the equipment or material listed in this standard.
Definitions
Casing For the purposes of this gas design standard, a casing is also referred to as a sleeve or conduit. Casings are not pressurized and shall only be used to insert a natural gas carrier pipe.
Page 8 of 12 ©2021 Pacific Gas and Electric Company. All rights reserved.
CRSC § 1707.18.7 High relevance — show source text
installation instructions.
1707.18.7 Closed Cell Insulation. Buried horizontal open-loop system pipes passing parallel within 5 feet (1524 mm) of a wall, structure, or water pipe shall be insulated with R-2 minimum closed cell insulation.
1707.18.8 Tracer Markings. Means shall be provided for underground detection or utility location of the buried pipe system. This shall include, but is not limited to, metallic detectable tape, with a thickness of not less than 11/64 of an inch (4.4 mm) and a width of 6 inches (152 mm).
This warning marking shall be permanent, conspicuous and resistant to the environmental conditions and shall be placed within 1 foot to 2 feet (305 mm to 610 mm) on top of the horizontal piping of the heat exchanger installation.
1708.0 System Start-Up. 1708.1 General. The following requirements shall be verified prior to system start-up:
(1) Piping shall be cleaned, flushed, and purged.
(2) The ground-heat exchanger and building piping shall be cleaned, flushed, and, where required, shall be filled with the heat transfer fluid medium. The ground loop system shall be tested at the design flow rate(s) and differential pressure(s) recorded. Where the actual pressure change at design flow is more than +/- 10 percent of the design flow pressure drop, the cause shall be identified and corrective action taken.
(3) A method for the removal of air and a method for adding heat transfer fluid (where necessary) shall be provided.
(4) The heat pumps shall be operational and adjustments shall be made in accordance with the manufacturer’s
installation instructions.
(5) All necessary additional flow tests of the ground-heat exchanger shall be completed prior to heat pump start-up.
(6) Ground-heat exchanger and building piping, valves, and operating controls, shall be set, adjusted, and operating as required.
(7) The system shall be labeled at the loop charging valves with a permanent-type label, indicating the type of heat transfer fluid used. Where antifreeze is used, the labels shall indicate the antifreeze type and concentration.
(8) Supply and return lines, as well as associated isolation valves from individual boreholes or water wells, shall be identified and tagged.
(9) Supply and return lines on submerged systems shall be identified in an approved manner, at the point of entry to a surface water resource.
«
«
«
«
«
«
«
««
««
«
«
«
1708.2 Operation and Maintenance Manual. An operation and maintenance manual for the geothermal system shall be provided to the owner. The manual shall include information on required testing and maintenance of the system. Training shall be provided on the system’s operation, maintenance requirements, and on the content of the operation and maintenance manual. The operation and maintenance manual shall contain a layout of the ground-heat exchanger and building loop.
1708.3 Labeling and Marking. Ground source heat pump ground-loop system piping shall be marked with tape, metal tags, or other methods where it enters a building. The marking shall indicate the following words: “GROUND SOURCE HEAT PUMP-LOOP SYSTEM.” The marking shall indicate antifreeze used in the system by name and concentration.
1708.4 Documentation. The ground source heat pump system as-built installation drawings and instructions shall be provided to the building owner or designated agent.
CRSC § 1.44 High relevance — show source text
R704.2 Exterior Soffit installation where the design wind pressure is 30 psf or less. Where the design wind pressure is 30 pounds per square foot (1.44 kPa) or less, exterior soffit installation shall comply with Section R704.2.1, R704.2.2, R704.2.3 or R704.2.4. Soffit materials not addressed in Sections R704.2.1 through R704.2.4 shall be in accordance with the manufacturer’s installation instructions.
R704.2.1 Vinyl and aluminum exterior soffit panels. Vinyl and aluminum exterior soffit panels shall be installed using aluminum, galvanized, stainless steel or rust-preventative coated nails or staples or other approved corrosion-resistant fasteners specified by the manufacturer and shall be fastened at both ends to a supporting component such as a nailing strip, fascia or subfascia component in accordance with Figure R704.2.1(1). Where the unsupported span of exterior soffit panels is greater than 16 inches (406 mm), intermediate nailing strips shall be provided in accordance with Figure R704.2.1(2). Vinyl and aluminum exterior soffit panels shall be installed in accordance with the manufacturer’s installation instructions. Fascia covers shall be installed in accordance with the manufacturer’s installation instructions.
7-32 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
WALL COVERING
FIGURE R704.2.1(1)—TYPICAL SINGLE-SPAN VINYL AND ALUMINUM EXTERIOR SOFFIT PANEL SUPPORT
FASCIA SHALL BE
INSTALLED IN ACCORDANCE
WITH SECTION R704.4.
ATTACH EXTERIOR
SOFFIT
TO SUB-FASCIA OR
TO NAILING STRIP (NOT SHOWN)
RDANCE
.4.
FRAMING
MIN. 1X2 NAILING
STRIPCol2 Col3 Col4 Col5 Col6 Col7 R
OR
VINYL AND ALUMINUM
EXTERIOR SOFFIT
J-CHANNEL
UNSUPPORTED SPAN
LIMITED PER SECTION R704.2.1 OR R704.3.1R
OR
VINYL AND ALUMINUM
EXTERIOR SOFFIT
J-CHANNEL
UNSUPPORTED SPAN
LIMITED PER SECTION R704.2.1 OR R704.3.1R
OR
VINYL AND ALUMINUM
EXTERIOR SOFFIT
J-CHANNEL
UNSUPPORTED SPAN
LIMITED PER SECTION R704.2.1 OR R704.3.1R
OR
VINYL AND ALUMINUM
EXTERIOR SOFFIT
J-CHANNEL
UNSUPPORTED SPAN
LIMITED PER SECTION R704.2.1 OR R704.3.1R
OR
VINYL AND ALUMINUM
EXTERIOR SOFFIT
J-CHANNEL
UNSUPPORTED SPAN
LIMITED PER SECTION R704.2.1 OR R704.3.1R
OR
VINYL AND ALUMINUM
EXTERIOR SOFFIT
J-CHANNEL
UNSUPPORTED SPAN
LIMITED PER SECTION R704.2.CRSC § 1.5. High relevance — show source text
May appear on the installation wiring diagram. K. Reference to a specific model number or description of the instrument to be used for checking the sensitivity of the detector. May appear on the installation wiring diagram. L. A detector intended for permanent connection only to a wiring system other than metal-clad cable or conduit shall be marked to indicate the system or systems for which it is suitable. The marking shall be so located that it will be visible when power-supply connections to the detector are made or may appear on the installation wiring diagram. M. The State Fire Marshal’s listing label if required by Article 1.5. N. A detector which is not intended to be painted in the field shall be marked on the outside “DO NOT PAINT.” 2. An installation wiring diagram shall be provided with each detector illustrating the field connections to be made. The drawing may be attached to the unit or, if separate, shall be referenced in the marking attached to the unit with the drawing number and issue number and/or date.
- The drawing shall show a pictorial view of the installation terminals or leads to which field connections are made as they would appear when viewed during an installation and the minimum internal dimensions of a back box, if not provided with the detector, shall be specified. The terminal numbers on the detector shall agree with the numbers on the drawing. A drawing not attached to the detector unit shall be marked with the name or identifying symbol of the manufacturer’s or vendor’s drawing number, and an issue number and/or date.
- The following marking information is required to appear on the detector or the installation wiring diagram for the applicable circuits to which field connections are made. Where an electrical rating is indicated, it may be omitted if reference is made for connection to a specific control unit or equivalent. A. Supply circuit. Voltage, current or watts, and frequency. B. Initiating device circuit connections. For detectors intended to be connected only to the initiating device circuit of a fire alarm system control unit, at least two detectors shall be shown connected to a typical initiating device circuit. For a detector intended only for releasing device service, a typical connection shall be shown. For a detector suitable for both application, typical connections representing both types of connections shall be illustrated. C. Supplementary circuits. Voltage, current or watts, and frequency rating.
- Technical bulletin. A technical bulletin shall be provided by the manufacturer for each installation to be used as a reference by the installer. The bulletin shall include the manufacturer’s recommendations regarding typical detector locations. The information shall include guidelines on detector location, spacings, maintenance, servicing tests, etc., under various environmental conditions and physical configurations. Some conditions for which guidelines are required are:
A. Temperature B. Humidity C. Corrosive atmospheres D. Air movement (ventilating and air-conditioning systems) E. High ceilings F. Sloped ceilings G. Girder ceiling construction H. Small and large bays I. Open joist construction J. High stock piling K. Conditions produced by manufacturing processes 6. Detailed information shall be provided regarding the use of the facilities provided on the detector to monitor the sensitivity. Typical information that shall be provided includes: A. Nominal reading under clear condition B. Nominal reading when close to alarm C. Nominal reading at alarm condition D. Guidelines on instrument use for an engineering survey, installation and maintenance 7. Information regarding locations where not to install detectors shall also be provided to minimize the possibility of false alarms.
CRSC § 1.44 Medium relevance — show source text
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
WALL COVERING
R703.17 Cladding attachment over foam sheathing to masonry or concrete wall construction. Cladding shall be specified and installed in accordance with Section R703.3 and the cladding manufacturer’s instructions or an approved design. Foam sheathing shall be attached to masonry or concrete construction in accordance with the insulation manufacturer’s installation instructions or an approved design. Furring and furring attachments through foam sheathing into concrete or masonry substrate shall be designed to resist design loads determined in accordance with Section R301, including support of cladding weight as applicable. Fasteners used to attach cladding or furring through foam sheathing to masonry or concrete substrates shall be approved for application into masonry or concrete material and shall be installed in accordance with the fastener manufacturer’s instructions.
Exceptions:
- Where the cladding manufacturer has provided approved installation instructions for application over foam sheathing and connection to a masonry or concrete substrate, those requirements shall apply.
- For exterior insulation and finish systems, refer to Section R703.9.
- For anchored masonry or stone veneer installed over foam sheathing, refer to Section R703.8.
R703.18 Fiber-mat reinforced cementitious backer units. Fiber-mat reinforced cementitious backer units used on exterior walls as a substrate for the application of exterior finish materials shall comply with ASTM C1325. Installation shall be in accordance with the manufacturer’s installation instructions. Backer units shall be installed using corrosion-resistant fasteners. Finish materials shall be installed in accordance with the manufacturer’s instructions.
SECTION R704 —EXTERIOR SOFFITS AND FASCIAS
R704.1 General wind limitations. Where the design wind pressure is 30 pounds per square foot (1.44 kPa) or less, exterior soffits shall comply with Section R704.2. Where the design wind pressure exceeds 30 pounds per square foot (1.44 kPa), exterior soffits shall comply with Section R704.3. The design wind pressure on exterior soffits shall be determined using the component and cladding loads specified in Table R301.2.1(1) for walls using an effective wind area of 10 square feet (0.93 m [2] ) and adjusted for height and exposure in accordance with Table R301.2.1(2).
R704.2 Exterior Soffit installation where the design wind pressure is 30 psf or less. Where the design wind pressure is 30 pounds per square foot (1.44 kPa) or less, exterior soffit installation shall comply with Section R704.2.1, R704.2.2, R704.2.3 or R704.2.4. Soffit materials not addressed in Sections R704.2.1 through R704.2.4 shall be in accordance with the manufacturer’s installation instructions.
R704.2.1 Vinyl and aluminum exterior soffit panels. Vinyl and aluminum exterior soffit panels shall be installed using aluminum, galvanized, stainless steel or rust-preventative coated nails or staples or other approved corrosion-resistant fasteners specified by the manufacturer and shall be fastened at both ends to a supporting component such as a nailing strip, fascia or subfascia component in accordance with Figure R704.2.1(1). Where the unsupported span of exterior soffit panels is greater than 16 inches (406 mm), intermediate nailing strips shall be provided in accordance with Figure R704.2.1(2).
CRSC § 71.4 Medium relevance — show source text
reinforcement: verti-
cal, four5/8″ rebars; horizontal,3/8″ ties at
7″ pitch; cover: 11/2″.|71.4
tons|2 hrs|||7|2, 7|2| |C-11-RC-20|11″|11″ square columns; gravel concrete (4530
psi); reinforcement: vertical, four5/8″
rebars; horizontal,3/8″ ties at 7″ pitch;
cover: 11/2″ with1/2″ plaster.|58.8
tons|2 hrs|||7|2, 3, 9|2| |C-11-RC-21|11″|11″ square columns; gravel concrete (3520
psi); reinforcement: vertical, four5/8″
rebars; horizontal,3/8″ ties at 7″ pitch;
cover: 11/2″.|Vari-
able|1 hr
24 min|||7|1, 8|11/4| |C-11-RC-22|11″|11″ square columns; aggregate concrete
(3710 psi); reinforcement: vertical, four5/8″
rebars; horizontal,3/8″ ties at 7″ pitch;
cover: 11/2″.|58.8
tons|2 hrs|||7|2, 3,
10|2| |C-11-RC-23|11″|11″ square columns; aggregate concrete
(3190 psi); reinforcement: vertical, four5/8″
rebars; horizontal,3/8″ ties at 7″ pitch;
cover: 11/2″.|58.8
tons|2 hrs|||7|2, 3,
10|2| |C-11-RC-24|11″|11″ square columns; aggregate concrete
(4860 psi); reinforcement: vertical, four
5/8″ rebars; horizontal,3/8″ ties at 7″ pitch;
cover: 11/2″.|86.1
tons|1 hr
20 min|||7|1|11/3| |C-11-RC-25|11″|11″ square columns; aggregate concrete
(4850 psi); reinforcement: vertical, four 5/8″
rebars; horizontal,3/8″ ties at 7″ pitch;
cover: 11/2″.|58.8
tons|1 hr
59 min|||7|1|13/4| |C-11-RC-26|11″|11″ square columns; aggregate concrete
(3834 psi); reinforcement: vertical, four 5/8″
rebars; horizontal,5/16″ ties at 41/2″ pitch;
cover: 11/2″.|71.4
tons|53 min|||7|1|3/4|For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
CRSC § 0-60 Medium relevance — show source text
The nose of all ridge, hip and rake tiles shall be set in a bead
of roofer’s mastic.|The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips.
Rake5 tiles shall be nailed with two nails. The nose of all ridge, hip and rake tiles shall be set in a bead
of roofer’s mastic.| |110|0-60|The fastening system shall resist the wind forces in Section 1609.6.3.1.|The fastening system shall resist the wind forces in Section 1609.6.3.1.|The fastening system shall resist the wind forces in Section 1609.6.3.1.| |120|0-60|The fastening system shall resist the wind forces in Section 1609.6.3.1.|The fastening system shall resist the wind forces in Section 1609.6.3.1.|The fastening system shall resist the wind forces in Section 1609.6.3.1.| |130|0-60|The fastening system shall resist the wind forces in Section 1609.6.3.1.|The fastening system shall resist the wind forces in Section 1609.6.3.1.|The fastening system shall resist the wind forces in Section 1609.6.3.1.| |All|> 60|The fastening system shall resist the wind forces in Section 1609.6.3.1.|The fastening system shall resist the wind forces in Section 1609.6.3.1.|The fastening system shall resist the wind forces in Section 1609.6.3.1.| |INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGS
(Installations on solid sheathing without battens)|INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGS
(Installations on solid sheathing without battens)|INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGS
(Installations on solid sheathing without battens)|INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGS
(Installations on solid sheathing without battens)|INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGS
(Installations on solid sheathing without battens)| |Maximum Allow-
able Stress Wind
Speed,****Vasd
f (mph)|Mean roof
height (feet)|All roof slopes|All roof slopes|All roof slopes| |85|0-60|One fastener per tile.|One fastener per tile.|One fastener per tile.| |100|0-40|One fastener per tile.|One fastener per tile.|One fastener per tile.| |100|> 40-60|The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips. Rake tiles
shall be nailed with two nails. The nose of all ridge, hip and rake tiles shall be set in a bead of roofer’s mastic.|The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips.CRSC § 12-10 Medium relevance — show source text
The latch shall continue to extend the roller throughout the test without any failure. The opening pressure at the end of the test shall not be less than 15 pounds. 3. Installation. Doors utilizing roller latches shall be installed in doors hung in steel frames only. Frame jambs shall be anchored to the floor to prevent spreading of the jambs. In other than concrete fill floors the jambs shall be anchored to a steel sill or steel floor plate extending between the jambs to prevent spreading of the frame. Horizontal bracing shall be provided in the wall in back of the strike.
THICKNESS OF COATINGS TESTS
Sec. 12-10-205. The thickness of cadmium, zinc or bronze plated coatings applied for corrosion resistance may be determined by either of the following methods:
Cross sections of coated samples cut at 90 exposed edges polished and thickness measured with a suitable microscope and scale.
Dropping test of a suitable reagent at a definite rate until coating is penetrated. The thickness is calculated from the known characteristics of the reagent at the observed temperature and time required for the end point to appear.
Thickness testing shall not apply to other processes having equal corrosion resistance; acceptance shall be determined by comparison in salt fog atmosphere per ASTM Method B-117.
MARKING
Sec. 12-10-206. The name of the manufacturer, or trademark by which the manufacturer can be readily identified, shall be legibly marked on the latch or lock where it can be seen after installation. When the manufacturer produces similar devices, the type, model
2025 CALIFORNIA REFERENCED STANDARDS CODE 79
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
EXITS
number or letter designation identifying the listed product shall be legibly marked on the latch or case. Such identification may be an approved marking or label on the case.
FIGURE 12-10-2.1 — STATIC LOADING FIXTURE
80 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
EXITS
FIGURE 12-10-2-2—ENDURANCE LIFE TESTING APPARATUS
2025 CALIFORNIA REFERENCED STANDARDS CODE 81
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
82 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
EMERGENCY EXIT AND PANIC HARDWARE
STANDARD 12-10-3
STATE FIRE MARSHAL
SCOPE
Sec. 12-10-300.
(a) Exit door hardware. These requirements and methods of test apply to releasing devices actuated by a crossbar for outwardopening doors intended for use on exit doors.
(b) Fire-exit hardware. Releasing devices intended for use on doors bearing a fire-retardant classification shall also conform to the construction standards and performance tests specified in Fire Door Assembly Tests, SFM 12-7-4, Section 12-7-400.
CRSC § 5.410.2.4 Medium relevance — show source text
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
FUNCTIONAL PERFORMANCE TESTING
COMPLIANCE FORM
CALGreen Commissioning Requirement 5.410.2.4, Functional Performance Testing
5.410.2.4 Functional performance testing. [N] Functional performance tests shall demonstrate the correct installation and operation of each component, system and system-to-system interface in accordance with the approved plans and specifications. Functional performance testing reports shall contain information addressing each of the building components tested, the testing methods utilized, and include any readings and adjustments made.
Test forms have been developed for each piece of commissioned equipment and system and include the checked elements listed below. These tests have been executed with deficiencies corrected.
Col1 FUNCTIONAL TEST ELEMENTS INCLUDED 1. Date and parties participating 2. Signature block attesting test is complete and accurate 3. Prerequisites 4. Precautions 5. Instrumentation required 6. Reference to the source of what is being confirmed (sequences, packaged features, etc.) 7. Detailed step-by-step test instructions 8. Acceptance criteria 9. Results 10. Confirmation of returning to normal 11. Deficiency list
Cx Coordinator Signature Date
8-32 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
FUNCTIONAL PERFORMANCE TESTING
COMPLIANCE FORM
REPORT #
(e.g., FPT-003)SYSTEM/EQUIPMENT TEST REPORT
(See minimum report requirements on page 2 of this form.)PAGE/TAB # IN
COMMISSIONING REPORTTHIS FORM IS TO BE COMPLETED FOR THE TIME OF INSPECTION
Project Address: _______________________________________________________
Permit Number: ___________________________
List the functional test reports below for all systems to be tested (see Form 5.4-8.1, item #9).
MINIMUM REQUIREMENTS FOR TEST REPORT
Date and Party – Identification of the date of the test and the party conducting the test.
Signature Block – Signature of the designated commissioning lead and the equipment-installing contractor attesting that the recorded test results are accurate.
Prerequisites – Any conditions or related equipment checkout or testing that needs to be completed before conducting this test.
Precautions – Identification of the risks involved to the test team members and the equipment and how to mitigate them.
Instrumentation – Listing of the instrumentation and tools necessary to complete the test.
Reference – In each procedure item, identify the source for what is being confirmed (e.g., sequence of operation ID, operating feature, specification requirement, etc.)
Test Instructions – Step-by-step instructions of how to complete the test, including functions to test and the conditions under which the tests should be performed.
Acceptance Criteria – Measurable pass/fail criteria for each step of the test, as applicable.
Results – Expected system response and space to document the actual response, readings, results and adjustments.
CRSC § 110.6 Medium relevance — show source text
Exception 2 to Section 110.6(a)4: If the fenestration product is an alteration consisting of any area; replacement of glass in a skylight product in a building covered by the nonresidential standards, the default VT may be calculated as set forth in Reference Nonresidential Appendix NA6. 5. Labeling. Fenestration products and exterior doors shall: A. Have a temporary label for manufactured fenestration products and exterior doors or a label certificate when the component modeling approach (CMA) is used and for site-built fenestration meeting the requirements of Section 10-111(a)1. The temporary label shall not be removed before inspection by the enforcement agency; and B. Have a permanent label or label certificate when the component modeling approach (CMA) is used and for sitebuilt fenestration meeting the requirements of Section 10-111(a)2 if the product is rated using NFRC procedures. 6. Fenestration acceptance requirements. Before an occupancy permit is granted site-built fenestration products in other than single-family buildings shall be certified as meeting the Acceptance Requirements for Code Compliance, as specified in the Reference Nonresidential Appendix NA7 to ensure that site-built fenestration meets Standards requirements, including a matching label certificate for product(s) installed and be readily accessible at the project location. A certificate of accep
2025 CALIFORNIA ENERGY CODE 55
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
tance certifying that the fenestration product meets the acceptance requirements shall be completed, signed and submitted to the enforcement agency. Exception to Section 110.6(a): Fenestration products removed and reinstalled as part of a building alteration or addition.
(b) Installation of field-fabricated fenestration and exterior doors. Field-fabricated fenestration and field-fabricated exterior doors may be installed only if the compliance documentation has demonstrated compliance for the installation using U factors from Table 110.6-A and SHGC values from Table 110.6-B. Field-fabricated fenestration and field-fabricated exterior doors shall be caulked between the fenestration products or exterior door and the building, and shall be weatherstripped.
Exception to Section 110.6(b): Unframed glass doors and fire doors need not be weatherstripped or caulked.
TABLE 110.6-A—DEFAULT FENESTRATION PRODUCT U-FACTORS Col2 Col3 Col4 Col5 FRAME1,2 PRODUCT TYPE SINGLE PANE3, 4
U-FACTORDOUBLE PANE1, 3, 4
U-FACTORGLASS BLOCK2, 3
U-FACTORMetal Operable 1.28 0.79 0.87 Metal Fixed 1.19 0.71 0.72 Metal Greenhouse/garden window 2.26 1.40 NA Metal Glazed doors 1.25 0.77 NA Metal Skylight 1.98 1.3 NA Metal, thermal break Operable NA 0.66 NA Metal, CRSC § 9-7 Medium relevance — show source text
2025 CALIFORNIA FIRE CODE 9-7
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FIRE PROTECTION AND LIFE SAFETY SYSTEMS
pump and automatic sprinkler system riser rooms shall be provided with doors and unobstructed passageways large enough to allow removal of the largest piece of equipment.
901.4.7.1 Access. Automatic sprinkler system risers, fire pumps and controllers shall be provided with ready access. Where located in a fire pump room or automatic sprinkler system riser room, the door shall be permitted to be locked provided that the key is available at all times.
901.4.7.2 Marking on access doors. Access doors for automatic sprinkler system riser rooms and fire pump rooms shall be labeled with an approved sign. The lettering shall be in contrasting color to the background. Letters shall have a minimum height of 2 inches (51 mm) with a minimum stroke of [3] / 8 inch (10 mm).
901.4.7.3 Environment. Automatic sprinkler system riser rooms and fire pump rooms shall be maintained at a temperature of not less than 40°F (4°C). Heating units shall be permanently installed.
901.4.7.4 Lighting. Permanently installed artificial illumination shall be provided in the automatic sprinkler system riser rooms and fire pump rooms.
901.5 Administration of installation acceptance testing. Fire protection and life safety systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing.
901.5.1 Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire protection and life safety systems have been tested and approved.
901.6 Inspection, testing and maintenance. Fire protection and life safety systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection and life safety systems and equipment shall be inspected, tested and maintained or removed in accordance with Section 901.8.
All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equipment, material or systems required by these regulations shall be maintained in an operable condition at all times in accordance with this code and California Code of Regulations, Title 19, Division 1. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment, material or systems to their original normal and operational condition.
[California Code of Regulations, Title 19, Division 1, §1.14] Maintenance.
Every fire alarm system or device, sprinkler system, fire extinguisher, fire hose, fire-resistive assembly or any other fire safety assembly, device, material or equipment installed and retained in service in any building or structure subject to California Code of Regulations, Title 19, Division 1 regulations shall be maintained in an operable condition at all times in accordance with California Code of Regula- tions, Title 19, Division 1 regulations and with their intended use.
[California Code of Regulations, Title 19, Division 1, §3.24] Maintenance of Equipment.
Frequently asked questions
What must be permanently marked on a device?
Devices must be permanently marked with identifying information such as manufacturer name or symbol, model/serial number, electrical ratings, sensitivity and mounting position where applicable, identification of controls, fuse ratings, references to installation wiring diagrams, and required listing labels (for example the State Fire Marshal listing) — see §12‑72‑302(b) and §12‑72‑205 for fire alarm devices and detectors .
Are installation and operating instructions required, and what should they include?
Yes. Manufacturers must provide installation, operating and maintenance instructions (they may be attached to the unit or supplied as a manual) that include typical installation layouts, wiring diagrams, testing/maintenance procedures and technical bulletins with recommended locations, spacing and environmental guidance. See §12‑72‑204, §12‑72‑302 and related instruction sections for required content and format .
When can a component part be accepted without retesting?
Component parts, devices or equipment that have been tested and listed by an approved testing agency for the intended purpose generally need not be retested when used in an assembly; the listing/test report may be filed and evaluated for recognition of approval. See the tested-and-listed component acceptance provisions in the applicable standards (for example §12‑4‑1(c) and related sections) .
More in California Referenced Standards Code
- Administration and scope — CRSC Chapter 12 overview
- Air filter standards (Chapter 12‑71)
- Building and facility access / accessibility standards (Chapters 12‑11A, 12‑11B)
- Engineering regulations — quality and design of construction materials (12‑16 series)
- Exits and means of egress (Chapters 12‑10 series)
- Protective signaling systems and detectors (Chapters 12‑72‑1, ‑2, ‑3)
- Radiation shielding standards (Chapter 12‑31C)
- Referenced standards index / cross‑reference table (Part 12 listing of referenced standards)
- Releasing systems for security bars (egress-release standards)
- Standards for insulating materials (Chapter 12‑13)
Ask about the CRSC
Get cited, plain-English answers on the California Referenced Standards Code for your project — any code section, any scenario.
Start Free Trial