CRSC · California Referenced Standards Code

What operating and installation instructions must accompany submitted samples?

When you submit a product sample for CRSC testing, always include a copy of the operating and installation instructions and any schematic wiring or installation drawings (drafts or manuals are acceptable). These documents let the testing authority install, wire, operate and evaluate the sample and must accompany the sample and test report. **§ 12-72-101(a)** **§ 12-72-302(b)**

Last reviewed: July 6, 2026

What the code requires — 2–4 sentences

When you submit a sample for investigation under the California Referenced Standards Code you must furnish a copy of the operating and installation instructions and any related drawings or wiring diagrams to be used as a guide in the examination and test. The State requires these documents even if they are not in final printed form. This requirement is set out in § 12-72-101(a) and the specific detector/instructions requirement in § 12-72-302(b).

The single most important rule: always include with the sample the operating/installation instructions and any schematic wiring or installation drawings (drafts or manuals are acceptable) so evaluators can install, test, and judge safe operation.

Key defined terms (first mention)

  • Operating and installation instructions — the manufacturer’s directions for installation, safe operation, testing and maintenance (including wiring/schematics where applicable). § 12-72-302(b)
  • Sample submitted for investigation — the physical unit(s) delivered for testing; the accompanying instructions are used to guide examination and test. § 12-72-101(a)

Requirements in detail

What must be furnished with the sample

  • A copy of the operating and installation instructions for the product under test. The copy may be a draft, manual, technical bulletin or other non-final printed form. § 12-72-302(b)
  • Any related schematic wiring diagrams and installation drawings needed to install and test the unit. § 12-72-302(b)
  • Test reports and supporting materials submitted for listing must include wiring diagrams, operating manuals and photographs as part of the test-report contents. § 12-72-101(a)
  • For fire alarm devices specifically, the device must be supplied with installation, operating and maintenance instructions that include a typical installation layout, description of operation and testing, maintenance procedures, household evacuation guidance, and notice to the local fire authority. § 12-72-204(a)

Use the table below to make decisions about what to include.

Decision-relevant dimension Required content / value Form allowed Purpose (what the examiner uses it for) Code Reference
What documents to send with a sample Operating & installation instructions + related schematic wiring diagrams + installation drawings Drafts, manual, technical bulletin — printed edition not required Guide installation, wiring, setup, operation and test of sample § 12-72-302(b)
Test report content when seeking listing Wiring diagrams, operating manuals, photographs, engineering analysis Formal report to accompany test results Provide evidence and enable review against performance standards § 12-72-101(a)
Fire-alarm device purchaser instructions Typical installation layout; operation, testing & maintenance procedures; evacuation info; local fire authority notice On unit or separate sheet; may be referenced by marking Ensure safe installation, user testing & emergency response § 12-72-204(a)
Required marking information (where applicable) Model, electrical rating, sensitivity setting, mounting position, fuses, etc. — some items may appear on wiring diagram rather than unit Permanently marked on unit or on installation wiring diagram Identify unit ratings and direct users to instructions/diagrams § 12-72-302(b)
Printed copy requirement None — a printed edition is not required for submission Drafts acceptable Speeds investigation — final printed manuals can follow § 12-72-302(b)

What the instructions should include (minimum/typical content)

  • Directions and information the manufacturer deems adequate for attaining proper and safe installation, operation and maintenance. § 12-72-302(b)
  • For devices seeking listing or evaluation, include sensitivity/rating information, electrical ratings, mounting orientation, identification of switches/lights/meters, reference to wiring diagrams, and any special cautions (radioactive material text, pressurized container warnings for gas-operated units, etc.). § 12-72-302(b)
  • For household fire alarm devices, supply a typical layout (recommended locations), testing/maintenance procedures and an evacuation plan; instructions may be on the device, separate sheet, or part of a manual, but must be referenced on the unit if not directly attached. § 12-72-204(a)

Exceptions & special cases

  • The instructions and drawings need not be in final printed form; drafts, technical bulletins or manuals are acceptable for investigation purposes. § 12-72-302(b)
  • Components or previously listed devices installed as part of a larger control unit may not require re-submission of component test reports, but the combined installation/wiring must be shown and the test report must identify listed components (catalog number, listing agency, report number/date). § 12-72-101(a)
  • If a device requires mounting in a definite position or connection to tubing/power lengths to function properly, the instructions and diagrams must make that clear because the sample will be tested in its intended position or with specified tubing lengths. § 12-72-203(a)(2–3)

If a specific additional instruction is required by a particular product standard (for example special servicing instructions for gas-operated alarms), that special text must be supplied (see marking and instructions provisions). § 12-72-204(a)

Common mistakes

  • Sending only the physical sample without any wiring diagrams or installation drawings — reviewers rely on those documents to install and test the unit. § 12-72-302(b)
  • Providing only final printed packaging text but omitting schematic wiring diagrams or installation drawings — wiring diagrams can be on a separate sheet and are required for evaluation. § 12-72-101(a)
  • Assuming a printed manual is required — drafts and technical bulletins are acceptable and often used; however, the content must be adequate for safe installation and testing. § 12-72-302(b)
  • Omitting safety or marking information that is required to appear on the unit or wiring diagram (for example electrical ratings or “Do Not Paint” warnings for thermal devices). § 12-72-302(b)

Worked example — concrete scenario

Scenario: Manufacturer submits a new ceiling-mounted smoke/combustion-products detector for listing.

  1. What to include with the sample:

    • A copy of the operating & installation instructions describing mounting, sensitivity adjustment, and maintenance (draft manual ok). § 12-72-302(b)
    • Schematic wiring diagram showing power input, interconnect circuits and connection points (may be presented as a separate installation wiring diagram). § 12-72-101(a)
    • Photographs of the unit and a wiring block diagram to be included in the test report. § 12-72-101(a)
    • If intended ceiling spacing or sensitivity is relevant, include instructions or data for the spacing allocation (detector sensitivity expressed in spacing limitations) because the device will be oven- or fire-tested for spacing qualification. § 12-72-203(b–c)
  2. Format and practical detail:

    • Provide 1 printed copy of the draft manual and one separate wiring schematic (paper or PDF is acceptable for the lab). No final printed book is required. § 12-72-302(b)
    • Mark the unit with required identification (manufacturer name, model, temperature rating) or reference the installation wiring diagram where that information appears. § 12-72-302(b)

Result: The lab can install the detector in the oven or test room per instructions, connect wiring per the schematic, run oven and fire tests, and include the wiring diagrams and operating manual in the test report required for listing. § 12-72-101(a)

Related provisions

  • § 12-72-101(a) — Test report contents: must include wiring, diagrams, operating manuals and photographs for review.
  • § 12-72-302(b) — Marking and instruction requirements for detectors; requires furnishing instructions, schematic wiring diagrams and installation drawings with sample.
  • § 12-72-201(b) — Instructions and drawings to be furnished with samples for single/multiple station fire alarm devices (similar instruction requirement).
  • § 12-72-204(a) — Specific instruction content required for fire alarm devices (installation layout, testing, evacuation, notice to local fire authority).
  • § 12-72-203(a–c) — Test setup considerations where intended mounting position and spacing/sensitivity determine how device is tested; instructions must make those conditions clear.
  • 12-3-2.3.1 — For other product areas (e.g., releasing systems), a copy of operating and installation instructions or equivalent must be furnished with samples; printed edition not required.

Code references

Grounded in the retrieved California Referenced Standards Code — click a citation to read the verbatim passage:

  • CRSC § 12-72 High relevance — show source text

    (b) Definitions. For the purpose of this standard, the following definitions shall apply:

    1. Fire alarm device, multiple station. Two or more gas-operated single station units interconnected by metal tubing to one or more remote alarm-sounding devices.

    2. Fire alarm device, single station. A self-contained fire alarm system comprising a heat detector, an alarm- sounding device and a stored energy source incorporated in one integral package. The basic types are gas- operated units and springwound units.

    3. Gas-operated type. A device having a temperature-sensitive eutectic element; compressed gas, usually in a liquid state in a cylinder; and a sounding means, such as a horn or whistle. When the eutectic element melts, the compressed gas is released in a gaseous state through the alarm-sounding device.

    4. Spring-wound type. A device having a temperature-sensitive bimetal or eutectic element and a spring-wound type mechanism with clapper mounted within a bell housing. The snap action of the bimetal or melting of the eutectic element releases the spring mechanism resulting in a bell-type sound.

    TEST REPORTS

    Sec. 12-72-201.

    (a) Test Report contents. The report shall include engineering data, and an analysis comparing the design against Sections 1272-201(b) through 12-72-202(g); it shall include operating manuals and photographs. The report shall set forth the tests performed in accordance with this standard and the results thereof.

    (b) Instructions and drawings. A copy of the operating and installation instructions and any related drawings is to be furnished with the sample submitted for investigation to be used as a guide in the examination and test of the unit and for this purpose they need not be in final printed form.

    The instructions and drawings shall include such directions and information as deemed by the manufacturer to be adequate for attaining proper and safe installation, operation and maintenance.

    (c) Rejection for cause. Compliance with these standards will not necessarily mean approval and listing, if, when examined and tested, it is found to have other features which may impair the result intended by these regulations. Unusual constructions may require application of additional performance tests. The State Fire Marshal may refuse to approve any item for cause. (See the Cali- fornia Electrical Code. )

    (d) Devices covered. This standard does not cover electrically operated single- or multiple-station fire alarm devices actuated by heat, smoke or combustion products.

    (e) Temperature classification. The temperature sensitive elements of single- and multiple-station fire alarm devices are to be identified as to their temperature of operation as follows:

    TEMPERATURE CLASSIFICATION RATING RANGE,
    °F (°C)
    MAXIMUM CEILING TEMPERATURE,
    °F (°C)
    Ordinary 135-174 (57-79) 100 (38)
    Intermediate 175-225 (79-107) 150 (66)

    The maximum rating of a fire alarm device is to be not more than 225°F (107°C).

    (f) Differing constructions. A control unit having materials or forms of construction differing from this standard may be investigated and tested according to the intent of this standard, and if found to be substantially equivalent may be given recognition for approval and listing. The office of the State Fire Marshal shall be consulted for general requirements and performance standards.

    2025 CALIFORNIA REFERENCED STANDARDS CODE 123

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

  • CRSC § 12-72 High relevance — show source text

    (c) Listed detectors. Detectors which have been tested to any other acceptable test standard may be evaluated provided such test incorporates all features of this standard.

    (d) Rejection for cause. Compliance with these standards will not necessarily mean approval and listing, if when examined and tested, it is found to have other features which may impair the result intended by these regulations. Unusual constructions may require application of additional performance tests. The State Fire Marshal may refuse to approve any item for cause. (See the Cali- fornia Electrical Code .)

    (e) Smoke detectors only.

    1. A combustion products detector, as covered by these requirements consists of an assembly of electrical components arranged to detect one or more products of combustion. The products of combustion may consist of but are not necessarily

    2025 CALIFORNIA REFERENCED STANDARDS CODE 133

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    PROTECTIVE SIGNALING SYSTEMS

    limited to gaseous combustion products, water vapor and visible as well as invisible smoke particles. The detector includes provision for the connection to a source of power, signaling and optional remote control circuits. 2. These requirements cover the following types of detectors: A. Detectors intended for open area protection, intended for connection to a compatible power supply or control unit for operation as part of a fire alarm system. B. Detectors intended solely for control of releasing devices such as electromagnetic door holders, fire dampers, etc.

    C. Detectors suitable for Items A and B above.

    1. This standard does not cover the following: A. Detectors for monitoring the smoke density within flues or stacks.

    B. Duct detectors.

    C. Power supplies and control units to which the detectors are intended to be connected. These are covered under the Standard Test Procedures for Protective Signaling Systems, SFM 12-72-1. D. Smoke detectors of the photoelectric type which are covered by the Standard for Smoke Detectors, Photoelectric Type, for Fire-Protective Signaling Systems, UL 168. 4. The manufacture, importation, distribution and disposal of smoke detectors containing radioactive material are subject to the safety requirements of state radiation control agencies and/or the U.S. Atomic Energy Commission. 5. Verification of an acceptable evaluation by the regulating agency involved is required prior to the investigation of the smoke detector to ensure compliance with this standard.

    (f) Differing constructions. A detector having materials or forms of construction differing from this standard may be investigated and tested according to the intent of this standard, and if found to be substantially equivalent may be given recognition for approval and listing. The office of the State Fire Marshal shall be consulted for general requirements and performance standards.

    (g) Operating and installation instructions.

    1. A copy of the operating and installation instructions and related schematic wiring diagrams and installation drawings are to be furnished with the sample submitted for investigation to be used as a guide in the examination and test of the detector and for this purpose need not be in final printed form. The information may be included in a manual or technical bulletin.
    2. The instructions and drawings should include such directions and information as deemed by the manufacturer to be adequate for attaining proper and safe installation, maintenance and operation of the detector. See Section 12-72-302 (b).

    GENERAL

    12-72-302.

    (a) Construction.

    1. A detector shall be so constructed that it will be reliable and sufficiently durable for its intended installation and use.
    2. A component of a detector shall comply with the requirements for that component, except that such requirements may be modified if appropriate for the particular application.
  • CRSC § 12-72 High relevance — show source text

    (f) Differing constructions. A detector having materials or forms of construction differing from this standard may be investigated and tested according to the intent of this standard, and if found to be substantially equivalent may be given recognition for approval and listing. The office of the State Fire Marshal shall be consulted for general requirements and performance standards.

    (g) Operating and installation instructions.

    1. A copy of the operating and installation instructions and related schematic wiring diagrams and installation drawings are to be furnished with the sample submitted for investigation to be used as a guide in the examination and test of the detector and for this purpose need not be in final printed form. The information may be included in a manual or technical bulletin.
    2. The instructions and drawings should include such directions and information as deemed by the manufacturer to be adequate for attaining proper and safe installation, maintenance and operation of the detector. See Section 12-72-302 (b).

    GENERAL

    12-72-302.

    (a) Construction.

    1. A detector shall be so constructed that it will be reliable and sufficiently durable for its intended installation and use.
    2. A component of a detector shall comply with the requirements for that component, except that such requirements may be modified if appropriate for the particular application.
    3. Except where specifically indicated otherwise, the construction requirements specified for a detector shall also apply for any remote accessories with which it is to be employed.
    4. Each detector is to be provided with a means for monitoring the relative sensitivity of the unit after it has been installed.
    5. The monitoring means may be by means of a jack or terminals for connection of a meter, or by a visual means which would be visible with the unit installed, or equivalent.
    6. The use of a plug-in type detector assembly, which may be removed readily for insertion of an adapter connected to metering equipment, would be acceptable.

    (b) Marking.

    1. A detector shall be permanently marked with the following information, except where it is indicated that the information may appear on an installation wiring diagram. A. Name or identifying symbol of the manufacturer or vendor. B. Model number or equivalent and serial number or equivalent. C. Electrical rating, in volts, amperes or watts, and frequency for each circuit. May appear on the installation wiring diagram. D. Sensitivity setting and reference to the region of sensitivity such as maximum, nominal or intermediate or minimum. If a detector is intended to be adjusted in the field, the range of sensitivity is to be indicated. The sensitivity shall be indicated as an instrument reading. A sensitivity indication other than an instrument reading may be employed if it provides an equivalent indication of the sensitivity of the detector. May appear on the installation wiring diagram. E. Correct mounting position if a unit is intended to be mounted in a definite position. This information may appear on the installation wiring diagram. F. Identification of lights, switches, meters, etc., regarding their function, unless their operation is obvious. G. Maximum rating of fuse in each fuseholder. Located adjacent to the fuseholder.

    134 2025 CALIFORNIA REFERENCED STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    PROTECTIVE SIGNALING SYSTEMS

    H. Reference to an installation wiring diagram, if not attached to the detector, by drawing number and issue number of date.

    I. For a detector which employs a radioactive material, the following information shall be indicated directly on the unit: type, amount, radiation symbol (optional), safe disposal and a caution notice which shall read as follows: CAUTION—Contains Radioactive Material, or its equivalent wording.

  • CRSC § 12-3 High relevance — show source text

    12-3-5.2.4 The exterior side of the assembly shall be covered by [3] / 4 -inch (19 mm) thick trade size CDX plywood, secured with minimum 1 [1] / 2 -inch (38 mm) nails or screws, secured at least every 12 inches (305 mm) to each stud, sill and header. The interior side of the assembly shall be covered with a layer of [1] / 2 -inch (13 mm) gypsum wallboard, secured with minimum 1 [1] / 4 -inch (32 mm) nails or screws at least every 12 inches (305 mm) to each stud, sill and header.

    2025 CALIFORNIA REFERENCED STANDARDS CODE 5

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    RELEASING SYSTEMS FOR SECURITY BARS IN DWELLINGS

    12-3-5.2.5 Openings in the test fixture shall be sized to accommodate the size of the assembly under test, as described in the installation instructions. Opening size shall be allowed to vary if the size used is judged to not affect the results of any test performed.

    12-3-5.3 Sample assembly.

    12-3-5.3.1 Samples of the releasing system shall arrive at the test site in the packaging anticipated for distribution and sale, and accompanied by the installation instructions. The samples are to be installed on the test fixture by a representative of the certification organization, using common hand and power tools as recommended by the instruction manual. Any specialty tools required for assembly shall be so identified in the instructions.

    12-3-5.3.2 When multiple tests are required on an assembly, they are allowed to be performed on the same test fixture, provided that new hole or openings are used for mounting. Portions of the test fixture shall be allowed to be replaced to accommodate new mounting holes or brackets.

    12-3-5.3.3 Samples that include grease, graphite, silicon or other lubricants shall also be tested with the lubricant removed or not applied.

    12-3-5.3.4 When assembled in accordance with the installation instructions the system shall be securely held in place in the test fixture and shall operate consistently in the intended fashion.

    SECTION 12-3-6—SECURE ATTACHMENT TEST

    12-3-6.1 Two samples of the system shall be subjected to the following test sequence.

    12-3-6.2 The system, when in the closed position, shall resist 50-pound (22 N) force without opening, loosening in the test fixture or damaging the releasing assembly. The force shall be applied on the exterior side of the test fixture in a location that is most likely to move or damage the system. The force shall be gradually applied perpendicular to the opening and held for a period of 1 minute. A 3 / 8 -inch (10 mm) diameter rope looped through the security bars, or similar arrangement, shall be used to apply the force.

    SECTION 12-3-7—OPERATION TEST

  • CRSC § 12-72 High relevance — show source text

    PROTECTIVE SIGNALING SYSTEMS

    TABLE 12-72-1D—ENDURANCE TEST Col2 Col3
    NORMAL SIGNALING PERFORMANCE OF DEVICE TOTAL NUMBER OF
    CYCLES DEVICE TO BE
    TESTED
    CYCLES PER
    MINUTE
    Continuous noncode signal for each operation of alarm signal initiating device 6,000 6
    A number of coded or noncode impulses for each operation of alarm signal initiating device 40,000 60
    Preliminary coded or noncode signal impulses followed by continuous signal impulses after
    each operation of alarm signal initiating device
    40,000
    resetting of device after
    each group of 40 impulses

    60
    Relays 40,000 60

    122 2025 CALIFORNIA REFERENCED STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    12-72-2 PROTECTIVE SIGNALING SYSTEMS

    SINGLE- AND MULTIPLE-STATION FIRE ALARM DEVICES MECHANICALLY OPERATED TYPE

    STANDARD 12-72-2

    STATE FIRE MARSHAL

    SCOPE

    Sec. 12-72-200.

    (a) Basic. This standard represents the minimum basic requirements for the construction and performance of single- and multiple-station fire alarm devices intended for indoor installation, and to be listed under this classification. The minimum design, construction and performance standards set forth herein are those deemed as minimum necessary to establish conformance to the regulations of the State Fire Marshal.

    (b) Definitions. For the purpose of this standard, the following definitions shall apply:

    1. Fire alarm device, multiple station. Two or more gas-operated single station units interconnected by metal tubing to one or more remote alarm-sounding devices.

    2. Fire alarm device, single station. A self-contained fire alarm system comprising a heat detector, an alarm- sounding device and a stored energy source incorporated in one integral package. The basic types are gas- operated units and springwound units.

    3. Gas-operated type. A device having a temperature-sensitive eutectic element; compressed gas, usually in a liquid state in a cylinder; and a sounding means, such as a horn or whistle. When the eutectic element melts, the compressed gas is released in a gaseous state through the alarm-sounding device.

    4. Spring-wound type. A device having a temperature-sensitive bimetal or eutectic element and a spring-wound type mechanism with clapper mounted within a bell housing. The snap action of the bimetal or melting of the eutectic element releases the spring mechanism resulting in a bell-type sound.

    TEST REPORTS

    Sec. 12-72-201.

    (a) Test Report contents. The report shall include engineering data, and an analysis comparing the design against Sections 1272-201(b) through 12-72-202(g); it shall include operating manuals and photographs. The report shall set forth the tests performed in accordance with this standard and the results thereof.

    (b) Instructions and drawings. A copy of the operating and installation instructions and any related drawings is to be furnished with the sample submitted for investigation to be used as a guide in the examination and test of the unit and for this purpose they need not be in final printed form.

  • CRSC § 12-3 High relevance — show source text

    SECTION 12-3-11—ABUSE TEST

    12-3-11.1 A sample shall comply with the Manual Actuation Test requirements in Sections 12-3-8.2 and 12-3-8.3 after being subjected to the simulated abuse provided in Section 12-3-11.2.

    12-3-11.2 The sample shall be subject to six impacts of 5 feet-pounds (6.8 N · m) each applied with a 2-inch diameter (51 mm) steel ball on portions of the release system that are most likely to adversely affect the operation of the system.

    MARKINGS AND INSTRUCTIONS

    SECTION 12-3-12—MARKINGS

    12-3-12.1 Security bars and the latching mechanism shall be permanently marked with the company name, model number and date of manufacture. When a manufacturer produces assemblies at more than one factory, each such assembly shall have a distinctive marking to identify it as the product of a particular factory.

    12-3-12.2 Symbols or diagrams shall be marked on the manual actuator to identify how to manually release the security bars. The diagram or symbols shall be readily visible to occupants when the assembly is mounted as intended.

    12-3-12.3 Security bars and the latching mechanism shall be marked with the name or logo of the testing agency certifying to compliance of the products with this standard, and identification of the standard as SFM SB-2000.

    12-3-12.4 Adhesive-backed labels used to provide required markings shall be suitable for the application and shall comply with UL Standard 969, 1995 Edition.

    SECTION 12-3-13—INSTRUCTION MANUAL

    12-3-13.1 Installation and operating instructions shall be provided with each system. Installation instructions shall describe how to install and initially test the system, and provide periodic testing and maintenance. Operating instructions shall be provided that include diagrams, drawing and symbols describing how to operate the system and escape in the event of a fire or other emergency.

    12-3-13.2 When the releasing mechanism assembly is provided separately from the security bar assembly in accordance with Section 12-3-3.1, the instruction manual shall describe the compatible security bars that have been investigated and found suitable for use with the releasing assembly. Security bars shall be identified by the manufacturer’s name and model number and maximum dimensions.

    12-3-13.3 The installation instructions shall include directions on mounting the actuator inside the room at a height not exceeding 48 inches (1.2 m) from the finished floor.

    2025 CALIFORNIA REFERENCED STANDARDS CODE 7

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    8 2025 CALIFORNIA REFERENCED STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    12-4A LABORATORY ANIMAL QUARTERS STANDARDS

    STANDARD 12-4A-1

    DEPARTMENT OF HEALTH SERVICES

    Authority: Sections 102, 208 and 25811.

    Reference: Sections 102, 208 and 436.5.

    LABORATORY ANIMAL QUARTERS

    Sec. 12-4A-101. Laboratory animal quarters shall comply with Chapter IV, “Guide for Care and Use of Laboratory Animals,” U.S. Department of Health, Education and Welfare, Publication Number 85-23, Revised 1985.

  • CRSC § 12-3 High relevance — show source text

    SECTION 12-3-2—GENERAL

    12-3-2.1 Components.

    12-3-2.1.1 Except as indicated in Section 12-3-2.1.2, a component of a product covered shall comply with the requirements for that component.

    12-3-2.1.2 A component need not comply with a specific requirement that: (a) Involves a feature or characteristic not needed in the application of the component in the product covered by these requirements, or (b) Is superseded by these requirements.

    12-3-2.1.3 A component shall be used in accordance with its recognized rating established for the intended conditions of use.

    12-3-2.1.4 Specific components are recognized as being incomplete in construction features or restricted in performance capabilities. Such components are intended for use only under limited conditions, such as certain temperatures not exceeding specific limits, and shall be used only under those specific conditions for which they have been recognized.

    12-3-2.2 Units of measurement.

    12-3-2.2.1 When a value for measurement is followed by a value in other units in parentheses, the first stated value is the requirement.

    12-3-2.3 Installation instructions.

    12-3-2.3.1 A copy of the operating and installation instructions or equivalent information is to be furnished with the samples submitted for investigation for use as a guide in the examination and test of the mechanism. For this purpose, a printed edition is not required.

    12-3-2.4 Definitions.

    12-3-2.4.1 Dwelling unit. A single unit, providing complete, independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, cooking and sanitation.

    2025 CALIFORNIA REFERENCED STANDARDS CODE 3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    RELEASING SYSTEMS FOR SECURITY BARS IN DWELLINGS

    12-3-2.4.2 Escape. For the purposes of these requirements, escape refers to movement of occupants from the interior of a residential dwelling unit to a safe point outside of the dwelling unit during an emergency fire condition.

    12-3-2.4.3 Emergency means of escape. A passage independent of and remote from the primary means of escape that provides a means of travel from living and sleeping spaces inside a dwelling unit to the outside.

    12-3-2.4.4 Means of escape. A concept included in building codes that, in most cases, requires sleeping rooms and living areas in dwelling units to be provided with at least one primary means of escape and one secondary means of escape to the outside.

    12-3-2.4.5 Primary means of escape. A door, stairway or ramp providing a means of unobstructed travel from living spaces inside a dwelling unit to the outside at street or ground level.

    12-3-2.4.6 Security bars. For the purposes of these requirements, the term “security bars” includes “burglar bars” and refers to metal and other bars, grilles, grates and other barriers that are designed to provide security for doors and windows in dwelling units. The purpose of security bars, by their mere presence on a building, is to deter a potential forced entry into the dwelling.

    CONSTRUCTION

    SECTION 12-3-3—ASSEMBLY

  • CRSC § 12-3 High relevance — show source text

    12-3-1.2 These requirements only cover the ability of the releasing system to be manually activated from the interior of a dwelling unit by an occupant to affect an escape through the protected opening.

    12-3-1.3 These requirements cover releasing systems intended for use on the interior side of doors or windows in all climatic locations.

    12-3-1.4 These requirements do not evaluate the ability of the releasing system or obstructions to resist an external forced entry attack.

    12-3-1.5 These requirements do not evaluate the ability of the releasing system or obstructions to be opened or removed from the exterior of the residential dwelling unit by emergency response personnel during rescue operations.

    12-3-1.6 Products covered by these requirements are intended for installation in dwelling units to protect door and window openings that are designated by the California Building Standards Code to be used as the secondary means of escape from the living area.

    12-3-1.7 Products covered by these requirements are not intended to be used to protect doors in means of egress path for nonresidential occupancies, the common egress path of multifamily residential dwelling units or the primary means of egress path in a single-family dwelling unit.

    12-3-1.8 These requirements do not cover window guards or fall prevention devices that are intended to prevent falls from upper story windows.

    12-3-1.9 These requirements do not apply to storm doors and windows or light duty screens used for insect control.

    12-3-1.10 A product that contains features, characteristics, components or materials new or different from those covered by these requirements, and that involve a risk of fire, electric shock or injury to persons shall be evaluated using the appropriate additional component and end-product requirements as determined necessary to maintain an acceptable level of safety.

    SECTION 12-3-2—GENERAL

    12-3-2.1 Components.

    12-3-2.1.1 Except as indicated in Section 12-3-2.1.2, a component of a product covered shall comply with the requirements for that component.

    12-3-2.1.2 A component need not comply with a specific requirement that: (a) Involves a feature or characteristic not needed in the application of the component in the product covered by these requirements, or (b) Is superseded by these requirements.

    12-3-2.1.3 A component shall be used in accordance with its recognized rating established for the intended conditions of use.

    12-3-2.1.4 Specific components are recognized as being incomplete in construction features or restricted in performance capabilities. Such components are intended for use only under limited conditions, such as certain temperatures not exceeding specific limits, and shall be used only under those specific conditions for which they have been recognized.

    12-3-2.2 Units of measurement.

    12-3-2.2.1 When a value for measurement is followed by a value in other units in parentheses, the first stated value is the requirement.

    12-3-2.3 Installation instructions.

    12-3-2.3.1 A copy of the operating and installation instructions or equivalent information is to be furnished with the samples submitted for investigation for use as a guide in the examination and test of the mechanism. For this purpose, a printed edition is not required.

    12-3-2.4 Definitions.

  • CRSC § 12-7 High relevance — show source text
    1. Turn the inside knob to retract the latch bolt.

    2. Open the door after the latch bolt is restricted to clear the strike.

    3. Release the knob allowing the latch bolt to return to its extended position by action of its own spring.

    After insertion of the latches or locks in the test door the torque in inch-pounds necessary to fully retract the latch bolts shall be recorded. The torque shall be the average recorded for the five latches or locks. Each sample shall be subjected to 800,000 operating cycles as described above. Each latch shall continue to extend itself per cycle 3 above throughout the test. At the end of the endurance test the torque to retract the latch bolts of any four latch bolts shall not exceed two times the initial average torque. If two latches fail to operate successfully at the end of the test or the torque of any four latches exceeds two times the initial average torque, an additional five latches or locks shall be subjected to the endurance test and the torque of any seven latches shall not exceed two times the initial average torque.

    (j) Roller latches.

    1. Fire test. Roller latches shall be installed in a composite test fire door in accordance with the manufacturer’s installation instructions and subjected to the fire test as described in SFM 12-7-4, for a period of 30 minutes. The latch shall be adjusted to an opening pressure of 20 pounds applied to the closing edge immediately above the latch. Throughout the test the latch shall require an applied pressure of 20 pounds to open the door.
    2. Endurance test. Five samples of the roller latch shall be subjected to the endurance test as described in Section 12-10-204 (i). The latch shall continue to extend the roller throughout the test without any failure. The opening pressure at the end of the test shall not be less than 15 pounds.
    3. Installation. Doors utilizing roller latches shall be installed in doors hung in steel frames only. Frame jambs shall be anchored to the floor to prevent spreading of the jambs. In other than concrete fill floors the jambs shall be anchored to a steel sill or steel floor plate extending between the jambs to prevent spreading of the frame. Horizontal bracing shall be provided in the wall in back of the strike.

    THICKNESS OF COATINGS TESTS

    Sec. 12-10-205. The thickness of cadmium, zinc or bronze plated coatings applied for corrosion resistance may be determined by either of the following methods:

    1. Cross sections of coated samples cut at 90 exposed edges polished and thickness measured with a suitable microscope and scale.

    2. Dropping test of a suitable reagent at a definite rate until coating is penetrated. The thickness is calculated from the known characteristics of the reagent at the observed temperature and time required for the end point to appear.

    Thickness testing shall not apply to other processes having equal corrosion resistance; acceptance shall be determined by comparison in salt fog atmosphere per ASTM Method B-117.

    MARKING

    Sec. 12-10-206. The name of the manufacturer, or trademark by which the manufacturer can be readily identified, shall be legibly marked on the latch or lock where it can be seen after installation. When the manufacturer produces similar devices, the type, model

    2025 CALIFORNIA REFERENCED STANDARDS CODE 79

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    EXITS

  • CRSC § 2203.6 High relevance — show source text

    2203.6 Standard operational procedures. Dust-producing equipment and all associated equipment, including dust-collection equipment, shall be maintained in accordance with the manufacturer’s instructions and specifications and applicable codes. The inspection, testing and maintenance program shall include the following, as applicable:

    1. Fire and explosion protection and prevention equipment, as applicable, in accordance with the appropriate NFPA standards.

    2. Dust-control equipment.

    3. Control of potential ignition sources.

    2025 CALIFORNIA FIRE CODE 22-5

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    COMBUSTIBLE DUST-PRODUCING OPERATIONS

    1. Electrical, process and mechanical equipment, including applicable process interlocks.
    2. Lubrication of bearings for dust-collection, dust-handling and dust-producing equipment.
    3. Additional maintenance in accordance with the manufacturer’s instructions and specifications for dust-collection, dusthandling and dust-producing equipment.

    Records shall be kept of maintenance and repairs performed. The standard operating procedures shall be submitted to the fire code official for review and approval. The written standard operating procedures shall be signed by the person responsible for facility operations.

    2203.7 Emergency response plan. A written emergency response plan shall be developed for preventing, preparing for and responding to work-related emergencies, including but not limited to fire and explosion. The following information shall be developed into the plan:

    1. Identification of dust hazards.

    2. Identification and location of all utilities to affected areas.

    3. Site plans or floor plans locating utility shutoff controls, including water, gas and power.

    4. The potential for explosion.

    5. Locations of fire-extinguishing equipment compatible with the hazards present.

    6. Any additional information required by the fire code official.

    2203.8 Training. The plans and procedures required in Sections 2203.5, 2203.6 and 2203.7 shall be approved by the fire code official. The plans and procedures shall be reviewed annually and updated as required by process changes. Initial and annual refresher training shall be provided to employees who are involved in operating, maintaining and supervising facilities that handle combustible dust. Initial and annual refresher training shall include:

    1. Workplace hazards.
    2. General orientation, plant diagrams and plant safety rules.
    3. Process description or flowchart.
    4. Equipment operation, safe startup and shutdown, and response to hazard conditions or an incident.
    5. The location and use of all related fire and explosion protection and prevention systems.
    6. Equipment maintenance requirements and practices, including visual inspections of conveyors and ducts.
    7. Housekeeping requirements, including the maintenance of the critical depth layer in Section 2203.1.
    8. Emergency response plans as required in Section 2203.7.

    The employer shall maintain records of initial and annual training and review.

    SECTION 2204—DUST EXPLOSION SCREENING TESTS

    2204.1 Combustibility and explosivity tests. Where combustibility or explosivity screening tests are required to analyze the combustible dust as part of compliance with Section 104.9 and Section 414.1.3 of the California Building Code, they shall be in accordance with Section 5.4 of NFPA 652.

    2204.2 Samples. Representative samples for the screening test shall be obtained in accordance with Section 5.5 of NFPA 652.

    SECTION 2205—STANDARDS

  • CRSC § 12-3 High relevance — show source text

    12-3-5.3.2 When multiple tests are required on an assembly, they are allowed to be performed on the same test fixture, provided that new hole or openings are used for mounting. Portions of the test fixture shall be allowed to be replaced to accommodate new mounting holes or brackets.

    12-3-5.3.3 Samples that include grease, graphite, silicon or other lubricants shall also be tested with the lubricant removed or not applied.

    12-3-5.3.4 When assembled in accordance with the installation instructions the system shall be securely held in place in the test fixture and shall operate consistently in the intended fashion.

    SECTION 12-3-6—SECURE ATTACHMENT TEST

    12-3-6.1 Two samples of the system shall be subjected to the following test sequence.

    12-3-6.2 The system, when in the closed position, shall resist 50-pound (22 N) force without opening, loosening in the test fixture or damaging the releasing assembly. The force shall be applied on the exterior side of the test fixture in a location that is most likely to move or damage the system. The force shall be gradually applied perpendicular to the opening and held for a period of 1 minute. A 3 / 8 -inch (10 mm) diameter rope looped through the security bars, or similar arrangement, shall be used to apply the force.

    SECTION 12-3-7—OPERATION TEST

    12-3-7.1 Following the Secure Attachment Test, each of the two samples of the system shall unlatch immediately without intentional delay during each of 10 attempts to operate the system, and the security bars shall be fully opened to create the opening specified in Section 12-3-3.10. During each attempt, the actuating mechanism shall be operated as intended, using a finger, hand or foot movement as described in the operating instructions provided to unlatch the security bars. The security bars shall then be opened to the full open position, and the system shall then be reset to the closed position. An examination shall be performed to verify that the security bars are completely reset prior to the next attempt.

    12-3-7.2 Springs provided in the latch or on the security bars that are intended to move the security bars from the latched position shall be removed or disabled prior to the test.

    12-3-7.3 Prior to the test, the assembly shall be operated and reset a number of times to acquaint the operator with the system and its opening and reselling operation. On some systems, it may be necessary to slam, tap or otherwise carefully align the security bars in the latch to successfully reset the system into the closed position.

    12-3-7.4 In the event that the actuating mechanism or assembly does not operate as intended during each of the 10 attempts, the test assembly, mounting method, actuating motion and system resetting procedure shall be reviewed to determine a potential cause of failure. After correcting any identified problems, the set of 10 operations shall be repeated with no unsuccessful attempts.

    SECTION 12-3-8—MANUAL ACTUATION TEST

    12-3-8.1 Following the Operation Test, each of the two sample assemblies shall be operated five times, and the forces required to unlatch the system shall be measured and recorded. These forces shall not exceed the values indicated in Sections 12-3-8.2 through 12-3-8.4.

  • CRSC § 12-72 High relevance — show source text

    (b) Normal operation.

    1. A detector shall be capable of operating for all conditions of its intended performance at all sensitivity settings when employed in conjunction with any related power supply or control unit with which it is intended to be employed and indicating devices to form the system combination covered by the installation wiring diagram and any supplementary information provided.

    2. The test voltage shall be in accordance with Section 12-72-303 (a), Item 5, and the combustion products detector shall be in the normal circuit supervisory standby condition and prepared for normal signaling operation when it is connected to related devices and circuits.

    3. The introduction of combustion products into the detector chamber such as produced by a smoldering cotton lamp wick, rope or equivalent, shall result in the operation of the detector in its intended manner. Section 12-72-303 (p), Item 2.

    (c) Power input and output. The input or output current of each circuit of a combustion products detector shall not exceed the marked rating by more than 10 percent when the detector is operated under the conditions of normal use and with the detector connected to a source of supply in accordance with Section 12-72-303 (a), Item 5.

    (d) Electrical supervision.

    1. All nonreliable components such as electronic tube heaters, blower motors, capacitors, functional heating elements, etc., the failure of which may result in an open or shorted condition shall be electrically supervised. See Sections 12-72-302 (e); 12-72-303 (a), Item 3; 12-72-303 (e) and 12-72-303 (s).

    2. All electrical circuits formed by conductors extending from the installation wiring connections for interconnecting to a power supply or system control units the failure of which may result in an open or ground fault shall be electrically supervised either at the detector or at the control unit to which a detector would be connected. See Section 12-72-302 (e).

    3. The requirements of Sections 12-72-392 (d), Items 1 and 2, do not apply to the following: A. Trouble indicating circuits. B. The circuits of a detector employed only for releasing device service if the fault results in the same operation of the unit as that obtained by detection of combustion products.

    142 2025 CALIFORNIA REFERENCED STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    PROTECTIVE SIGNALING SYSTEMS

    C. A circuit for a supplementary signal annunciator, signal sounding appliance, motor controller or similar appliance provided that a break or a ground fault in no way affects the normal operation of the unit except for omission of the supplementary feature.

    (e) Electrical supervision test.

    1. The electrical circuits formed by conductors extending from the installation wiring connections of a detector for interconnection to a power supply source or system control unit initiating device circuit shall be electrically supervised so that the detector trouble signal or circuit is energized under any of the following fault conditions if the fault prevents normal operation of the detector for fire alarm signals. A. Single open or single ground fault of the connecting field wiring. B. Failure of a nonreliable component. See Sections 12-72-303 (d), Item 1; 12-72-303 (a), Item 3; and 12-72-303 (s).
    2. A motor included in a detector, such as a blower motor which is required to operate continuously during normal operation, shall be supervised to indicate stalling or burnout.

Frequently asked questions

What if my operating manual is still a draft — is that acceptable?

Yes. The CRSC expressly permits non‑final printed forms — drafts, manuals or technical bulletins may be furnished for investigation. § 12-72-302(b)

Do I have to include wiring diagrams with the sample?

Yes. Related schematic wiring diagrams and installation drawings must be furnished with the sample and are used as a guide in examination and testing. § 12-72-302(b)

Must the instructions be physically attached to the unit?

Not necessarily. Instructions may be on the device, on a separate sheet, or part of a manual. If not attached, the unit’s marking must reference where the instructions or wiring diagram are located. § 12-72-204(a)

Will the lab accept electronic copies (PDF)?

The code does not mandate a format; it requires that copies be furnished. Practically, labs commonly accept PDFs, but confirm with the specific testing laboratory. The CRSC allows non-final printed forms. § 12-72-302(b)

If components are already listed, do I still send their manuals?

You should include identification (catalog number, listing agency, report number/date) for listed components in the test report; full component manuals may not need retesting, but the combined wiring and installation must be shown. § 12-72-101(a)

More in California Referenced Standards Code

Ask about the CRSC

Get cited, plain-English answers on the California Referenced Standards Code for your project — any code section, any scenario.

Start Free Trial

Related in the CRSC