CPC · California Plumbing Code
How are piping, materials and surrounding structures required to be protected?
The CPC requires that plumbing piping be installed so it won't be broken, corrode, freeze, or weaken the structure: don't embed pipes in concrete or masonry, seal holes where pipes pass through ground slabs, provide for thermal expansion and settlement, protect pipes that are close to exposed framing with steel nail plates, and restore fire‑rated assemblies after penetrations per the building code (see **§ 312.0**, **§ 312.2**, **§ 312.7**) .
Last reviewed: July 6, 2026
What the code requires — 2-4 sentences
The California Plumbing Code requires that piping, tubing, and related materials be installed and protected so they are not subject to breakage, undue strain, corrosion, freezing, or damage — and that penetrations of fire‑resistance‑rated assemblies be restored in accordance with the building code. Key general rules are found in § 312.0, installation rules (including the prohibition on embedding piping in concrete) are in § 312.2, and fire‑resistance/penetration rules are addressed in § 312.7. The specific CPC text for these requirements is in the provided code files (see § citations below) .
Protect piping so it won’t break, corrode, freeze, or weaken the structure — and don’t embed plumbing directly in concrete or masonry.
Requirements in detail
1) General protection (what to protect and why)
- Piping passing under or through walls must be protected from breakage. Piping exposed to cinders or corrosive materials must be protected from external corrosion in an approved manner. Voids where piping passes through concrete floors on the ground must be sealed to prevent ingress/settlement issues (§ 312.1) .
- Bolded compliance concept: make provisions for expansion of hot‑water piping so thermal movement does not create stress or damage (§ 312.1) .
2) Installation rules (support, movement, and embedment)
- Piping shall be installed so piping and connections are not subject to undue strains or stresses; provisions must be made for expansion, contraction, and structural settlement (§ 312.2) .
- No plumbing piping shall be directly embedded in concrete or masonry — this is an explicit prohibition in § 312.2; routing in sleeves, conduit, or accessible chase is required where concrete would otherwise enclose pipe (§ 312.2) .
- Structural members must not be seriously weakened by cutting or notching for piping; those limits are defined by the California Building Code / Residential Code and enforced here (§ 312.2) .
3) Fire‑resistance and penetrations
- When piping penetrates a fire‑resistance‑rated wall, partition, floor, floor/ceiling assembly, roof/ceiling assembly or shaft enclosure, the penetration shall be protected and the fire‑resistance rating restored in accordance with the California Building Code or California Residential Code (i.e., firestop systems and tested assemblies per those codes) (§ 312.7) .
4) Localized mechanical protection (nail plates and similar)
- Where plastic or copper piping penetrates framing members and comes to within 1 inch (25.4 mm) of the exposed framing, it must be protected by steel nail plates of not less than No. 18 gauge (0.0478 in / 1.2 mm) thickness. The plate must extend at least 1½ inches (38 mm) past the outside diameter of the pipe (§ 312.9) .
Decision‑relevant dimensions / values (quick reference)
| Decision item | Required value / action | Code Reference |
|---|---|---|
| Do not embed plumbing piping in concrete or masonry | Prohibited — route in sleeve/conduit or otherwise avoid direct embedment | § 312.2 |
| Seal voids around piping through concrete floors on the ground | Voids shall be sealed | § 312.1 |
| Protection when piping within 1 in of exposed framing | Install steel nail plate ≥ No. 18 gauge (0.0478 in / 1.2 mm) | § 312.9 |
| Nail plate extension beyond pipe | Extend at least 1½ in (38 mm) along the framing member | § 312.9 |
| Penetrations of fire‑rated assemblies | Firestop and restore rating per Building/Residential Code | § 312.7 |
| Protect piping from external corrosion/ corrosive soils | Provide approved corrosion protection or choose corrosion‑resistant materials | § 312.1 and § 312.4 |
(Entries above are taken from the CPC text excerpts in the provided files) .
Exceptions & special cases
- Firestop and rating restoration are not prescribed in detail by the CPC text in § 312.7; instead the CPC directs installers to the California Building Code / California Residential Code for fire‑resistance detailing and approved systems (§ 312.7) .
- Some specialized piping (for example, certain gas piping installations in floors) has additional or alternate rules in the Mechanical / Fuel Gas sections; where CPC text defers to other codes, follow those referenced codes and the Authority Having Jurisdiction (AHJ). See, for example, fuel‑gas floor embedding guidance in the Mechanical/NFPA‑based sections referenced elsewhere in the code files (see related provisions) .
- NOTE: I searched the provided CPC documents for § 312.11 but did not find text for § 312.11 in the uploaded files. Because that section was not present in the retrieved files I cannot state or cite its contents here. If you want § 312.11 specifically, please upload the code page or allow me to search additional files.
Common mistakes
- Assuming embedding small‑diameter plumbing in slab is allowed — the CPC explicitly states no direct embedment in concrete or masonry (§ 312.2) .
- Failing to provide thermal expansion allowance for hot‑water runs; installers sometimes rigidly fasten long runs without expansion loops or joints (contrary to § 312.1 and § 312.2) .
- Not sealing voids where piping passes through ground‑level concrete floors — leaving gaps can allow pest, moisture, or settling damage (see § 312.1) .
- Overlooking the need to restore fire‑resistance rating after creating a penetration; the CPC defers to the building code for the required firestop systems (§ 312.7) .
- Using nail plates that are too thin or not extending the required distance past the pipe — the CPC requires No. 18 gauge and 1½ in extension for the plate (§ 312.9) .
Worked example — concrete scenario applying the rule
Scenario: A plumber routes 3/4‑inch copper water tubing vertically through a 2x10 wood floor and the tubing will be within ¾ inch of the exposed face of the bottom of the joist.
How the CPC applies:
- Because the tubing will be within 1 inch (25.4 mm) of the exposed framing surface, the installer must protect the tubing with a steel nail plate not less than No. 18 gauge (0.0478 in / 1.2 mm) thick. The plate must extend at least 1½ in (38 mm) beyond the outside diameter of the pipe along the framing member (§ 312.9) .
- If the run passes through a concrete slab on grade, the installer may not embed the pipe directly in the slab (that is prohibited by § 312.2) — instead the installer must route the piping in a sleeve, conduit, or other approved protective method and seal any void where the sleeve passes through the slab (§ 312.1, § 312.2) .
- If the piping penetrates a fire‑resistance‑rated floor assembly, the penetration must be firestopped and the assembly’s rating restored per the Building Code (§ 312.7) .
Practical steps the plumber would take:
- Install the copper tube with sufficient clearance; where within 1 in, fit a No. 18 steel nail plate extending 1½ in past the pipe. (See § 312.9) .
- Where the run crosses a ground‑level concrete slab, run the pipe through an approved sleeve and seal the annular space after completing the piping (See § 312.1 and § 312.2) .
- If the location is a rated assembly, coordinate with the project firestop submittal to ensure the penetration detail restores the rating per the Building Code (§ 312.7) .
Related provisions
- § 312.1 — General protection requirements (walls, corrosive materials, sealing voids, expansion) .
- § 312.3 — Building sewer and drainage piping location limits (distance from building). See CPC for the specific 2 ft (610 mm) and 1 ft (305 mm) values referenced there .
- § 312.4 — Corrosion, erosion, and mechanical damage protection requirements .
- § 312.9 — Steel nail plate requirements and minimum dimensions for protection of piping near exposed framing members .
- Mechanical / Fuel Gas exceptions and floor embedding guidance (for some gas piping) — see the Mechanical / Fuel Gas chapters and NFPA‑based sections (examples in the provided Mechanical/Fuel Gas excerpts) where minimum 1½ in (38 mm) concrete cover for embedded gas piping in certain occupancies is discussed (see Mechanical / Fuel Gas references) .
- Firestop and rated assembly restoration — see the California Building Code / California Residential Code provisions referenced by § 312.7 for tested systems and rating restoration requirements .
(If you want a printout or scanned image of the exact CPC pages for § 312.0 – § 312.9 or a search for § 312.11 specifically, upload those pages and I will cite them directly. I could not find § 312.11 in the uploaded files.)
Code references
Grounded in the retrieved California Plumbing Code — click a citation to read the verbatim passage:
CPC § 312.0 High relevance — show source text
Note: Accessory dwelling units are not required to have inde- pendent service utility (drainage) connections provided they meet the specific requirements in Government Code Section 65852.2.
312.0 Protection of Piping, Tubing, Materials, and Structures.
312.1 General. Piping passing under or through walls shall be protected from breakage. Piping passing through or under cinders or other corrosive materials shall be protected from external corrosion in an approved manner. Approved provisions shall be made for expansion of hot water piping. Voids around piping passing through concrete floors on the ground shall be sealed.
312.2 Installation. Piping in connection with a plumbing system shall be so installed that piping or connections will not be subject to undue strains or stresses, and provisions shall be made for expansion, contraction, and structural settlement. No plumbing piping shall be directly embedded in concrete or masonry. No structural member shall be seriously weakened or impaired by cutting, notching, or otherwise, as defined in the California Building Code or California Residential Code . 312.3 Building Sewer and Drainage Piping. No building sewer or other drainage piping or part thereof, constructed of materials other than those approved for use under or within a building, shall be installed under or within 2 feet (610 mm) of a building or structure, or less than 1 foot (305 mm) below the surface of the ground. 312.4 Corrosion, Erosion, and Mechanical Damage. Piping subject to corrosion, erosion, or mechanical damage shall be protected in an approved manner. 312.5 Protectively Coated Pipe. Protectively coated pipe or tubing shall be inspected and tested, and a visible void, damage, or imperfection to the pipe coating shall be repaired in an approved manner. 312.6 Freezing Protection. No water, soil, or waste pipe shall be installed or permitted outside of a building, in attics or crawl spaces, or in an exterior wall unless, where necessary, adequate provision is made to protect such pipe from freezing. 312.7 Fire-Resistant Construction. Piping penetrations of fire-resistance-rated walls, partitions, floors, floor/ceiling assemblies, roof/ceiling assemblies, or shaft enclosures shall be protected in accordance with the requirements of the Cal- ifornia Building Code or California Residential Code . 312.8 Waterproofing of Openings. Joints at the roof around pipes, ducts, or other appurtenances shall be made watertight by the use of lead, copper, galvanized iron, or other approved flashings or flashing material. Exterior wall openings shall be made watertight. Counterflashing shall not restrict the required internal cross-sectional area of the vent. 312.9 Steel Nail Plates. Plastic piping or tubing, and copper or copper alloy piping or tubing penetrating framing members to within 1 inch (25.4 mm) of the exposed framing shall be protected by steel nail plates not less than No. 18 gauge (0.0478 inches) (1.2 mm) in thickness. The steel nail plate shall extend along the framing member not less than 1 [1] ⁄ 2 inches (38 mm) beyond the outside diameter of the pipe or tubing. Fuel gas piping shall be protected in accordance with Section 1210.4.3.
CPC § 310.13 High relevance — show source text
ante rooms.
310.13 [SFM] For applications listed in Section 1.11.0 regu- lated by the Office of the State Fire Marshal, plastic piping shall not be exposed as a portion of the interior room finish in a build- ing or structure if the piping has a flame-spread rating exceed- ing 75 when tested in accordance with ASTM E84, “Test for Surface Burning Characteristics of Building Materials.” 310.14 Services/Systems and Utilities. [OSHPD 1, 2, 4 & 5] Refer to Sections 1224.4.1, 1225.2.1 and 1228.4.1.1, Cal- ifornia Building Code. 310.15 Telephone and Data Equipment Rooms.
[OSHPD 1, 4 & 5] Where telecommunications service entrance rooms, technology equipment centers, or technology distribution rooms are provided in accordance with Section 1224.5 of the California Building Code, plumbing equipment and fixtures that are not directly related to the support of the room shall not be installed in or pass through the room.
311.0 Independent Systems. 311.1 General. The drainage system of each new building and new work installed in an existing building shall be separate and independent from that of any other building, and, where available, every building shall have an independent connection with a public or private sewer.
Exception: Where one building stands in the rear of another building on an interior lot, and no public or private sewer is available or can be constructed to the rear building through an adjoining court, yard, or driveway, the building drain from the front building shall be permitted to be extended to the rear building.
Note: Accessory dwelling units are not required to have inde- pendent service utility (drainage) connections provided they meet the specific requirements in Government Code Section 65852.2.
312.0 Protection of Piping, Tubing, Materials, and Structures.
312.1 General. Piping passing under or through walls shall be protected from breakage. Piping passing through or under cinders or other corrosive materials shall be protected from external corrosion in an approved manner. Approved provisions shall be made for expansion of hot water piping. Voids around piping passing through concrete floors on the ground shall be sealed.
312.2 Installation. Piping in connection with a plumbing system shall be so installed that piping or connections will not be subject to undue strains or stresses, and provisions shall be made for expansion, contraction, and structural settlement. No plumbing piping shall be directly embedded in concrete or masonry. No structural member shall be seriously weakened or impaired by cutting, notching, or otherwise, as defined in the California Building Code or California Residential Code . 312.3 Building Sewer and Drainage Piping. No building sewer or other drainage piping or part thereof, constructed of materials other than those approved for use under or within a building, shall be installed under or within 2 feet (610 mm) of a building or structure, or less than 1 foot (305 mm) below the surface of the ground. 312.4 Corrosion, Erosion, and Mechanical Damage. Piping subject to corrosion, erosion, or mechanical damage shall be protected in an approved manner. **312.5 Protectively Coated Pipe.
CPC § 1.11.0. High relevance — show source text
only those sections
that are listed below
Chapter/Section||||||||||||||||||||||||| |Adopting Agency
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended
sections listed below)
Adopt only those sections
that are listed below
Chapter/Section|||||||||||||||||||||||||This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
2025 CALIFORNIA PLUMBING CODE 303
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
304 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHAPTER 14
FIRESTOP PROTECTION
1401.0 General.
1401.1 Applicability. Piping penetrations of required fireresistance-rated walls, partitions, floors, floor/ceiling assemblies, roof/ceiling assemblies, or shaft enclosures shall be protected in accordance with the requirements of the building code, and this chapter.
1402.0 Construction Documents.
1402.1 Penetrations. Construction documents shall indicate with sufficient detail how penetrations of fire-resistancerated assemblies shall be firestopped prior to obtaining design approval.
1403.0 Installation.
1403.1 Materials. Firestop systems shall be installed in accordance with this chapter, the building code, and the manufacturer’s installation instructions.
1404.0 Combustible Piping Installations. 1404.1 General Requirements. Combustible piping installations shall be protected in accordance with the appropriate fire resistance rating requirements in the building code that list the acceptable area, height, and type of construction for use in specific occupancies to assure compliance and integrity of the fire resistance rating prescribed. 1404.2 Fire-Resistance Rating. Where penetrating a fireresistance-rated wall, partition, floor, floor-ceiling assembly, roof-ceiling assembly, or shaft enclosure, the fire-resistance rating of the assembly shall be restored to its original rating. 1404.3 Firestop Systems. Penetrations shall be protected by an approved penetration firestop system installed as tested in accordance with ASTM E119, ASTM E814, UL 263, or UL 1479 with a positive pressure differential of not less than 0.01 of an inch of water (0.002 kPa). Systems shall have an F rating of not less than 1 hour but not less than the required fireresistance rating of the assembly being penetrated. Systems protecting floor penetrations shall have a T rating of not less than 1 hour but not less than the required fire-resistance rating of the floor being penetrated. Floor penetrations contained within the cavity of a wall at the location of the floor penetration do not require a T rating. No T rating shall be required for floor penetrations by piping that is not in direct contact with combustible material.
1404.4 Connections. Where piping penetrates a rated assembly, the combustible piping shall not connect to noncombustible piping unless it is capable of being demonstrated that the transition is in accordance with Section 1404.3.
CPC § 5703.6.4 High relevance — show source text
Exception: Vapor-recovery piping is allowed to be tested using an inert gas.
5703.6.4 Protection from vehicles. Guard posts or other approved means shall be provided to protect piping, valves or fittings subject to vehicular damage in accordance with Section 312.
5703.6.5 Protection from external corrosion and galvanic action. Where subject to external corrosion, piping, related fluidhandling components and supports for both underground and above-ground applications shall be fabricated from noncorrosive materials, and coated or provided with corrosion protection. Dissimilar metallic parts that promote galvanic action shall not be joined.
5703.6.6 Valves. Piping systems shall contain a sufficient number of manual control valves and check valves to operate the system properly and to protect the plant under both normal and emergency conditions. Piping systems in connection with pumps shall contain a sufficient number of such valves to control properly the flow of liquids in normal operation and in the event of physical damage or fire exposure.
5703.6.6.1 Backflow protections. Connections to pipelines or piping by which equipment (such as tank cars, tank vehicles or marine vessels) discharges liquids into storage tanks shall be provided with check valves or block valves for automatic protection against backflow where the piping arrangement is such that backflow from the system is possible. Where loading and unloading is done through a common pipe system, a check valve is not required. However, a block valve, located in an area where it is provided with ready access or remotely operable, shall be provided.
5703.6.6.2 Manual drainage. Manual drainage-control valves shall be located at approved locations remote from the tanks, diked area, drainage system and impounding basin to ensure their operation in a fire condition.
5703.6.7 Connections. Above-ground tanks with connections located below normal liquid level shall be provided with internal or external isolation valves located as close as practical to the shell of the tank. Except for liquids whose chemical characteristics are incompatible with steel, such valves, where external, and their connections to the tank shall be of steel.
5703.6.8 Piping supports. Piping systems shall be substantially supported and protected against physical damage and excessive stresses arising from settlement, vibration, expansion, contraction or exposure to fire. The supports shall be protected against exposure to fire by one of the following:
- Draining liquid away from the piping system at a minimum slope of not less than 1 percent.
- Providing protection with a fire-resistance rating of not less than 2 hours.
- Other approved methods.
5703.6.9 Flexible joints. Flexible joints shall be listed and approved and shall be installed on underground liquid, vapor and vent piping at all of the following locations:
- Where piping connects to underground tanks.
- Where piping ends at pump islands and vent risers.
- At points where differential movement in the piping can occur.
5703.6.9.1 Fiberglass-reinforced plastic piping. Fiberglass-reinforced plastic (FRP) piping is not required to be provided with flexible joints in locations where both of the following conditions are present:
- Piping does not exceed 4 inches (102 mm) in diameter.
- Piping has a straight run of not less than 4 feet (1219 mm) on one side of the connection where such connections result in a change of direction.
In lieu of the minimum 4-foot (1219 mm) straight run length, approved and listed flexible joints are allowed to be used under dispensers and suction pumps, at submerged pumps and tanks, and where vents extend above ground.
CPC § 2025 High relevance — show source text
The safety requirements provide protection for piping, material, and structures, with provisions for installation practices, removing stress and strain of the pipe, sleeving, and hanger support. The building’s structural stability is protected by the regulations for cutting and notching of structural members.
Chapter 4 Plumbing Fixtures and Fixture Fittings.
This chapter regulates the minimum number of plumbing fixtures of a specific type and quality for each building. The fixtures must be properly installed to be usable by the individuals occupying the building. The quality and design of every fixture must conform to the applicable referenced standard. Compliance with this chapter will result in a building or structure having acceptable plumbing fixtures for the sanitary, hygienic, cleaning, washing, and food preparation needs of the occupants. In addition to ensuring resilient fixtures, the chapter also takes into consideration gender-neutral facilities and contains provisions for privacy compartments.
Chapter 5 Water Heaters.
Chapter 5 regulates the design, approval, installation, and safety devices of fuel burning and other types of water heaters with the combustion air requirements for ventilation and dilution of flue gases for appliances installed in buildings. This chapter does not apply to direct-vent appliances. In addition, this chapter regulates the design, construction, installation, and maintenance of chimneys, vents, and their connections to fuel-burning appliances. Methods to supply combustion air may be supplied from an indoor air supply, outdoor air supply, a combination of indoor and outdoor air supply, mechanical air supply, or an engineered system. Combustion air provisions are based on the number of openings and the total opening size required based on the total energy input rating of the appliance. An acceptable air supply for combustion and ventilation is necessary for the proper operation of fuel-burning appliances. A shortage of combustion air can result in incomplete combustion and the production of poisonous gases, such as carbon monoxide or appliance overheating. Ventilation air provides cooling for the appliance casing and internal controls. Inadequate ventilation of the space in which an appliance is installed can result in increased surrounding temperatures that stress the appliance itself or other appliances in the vicinity.
xiv 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FORMAT OF THE UNIFORM PLUMBING CODE
Chapter 6 Water Supply and Distribution.
Chapter 6 regulates the design, material, and installation of water supply and distribution systems, including residential fire sprinklers. The water supply and distribution system is designed to achieve the correct water pressure and flow rates and avoid cross-connections. For fixtures to perform properly, an acceptable supply of potable water is essential to their operation and use. Cross-connections and backflow are ranked as the highest priority because of the long history of recognized health risks posed by cross-connections, outbreaks, or cases of waterborne disease. Piping materials and components are evaluated for their possible effect on the potable water with which they are in contact. The intent is to control the potential adverse health effects produced by indirect additives, products, and materials that come in contact with potable water. When selecting materials for water supply and distribution systems, consider water pressure, water temperature, compatibility with the water supply, durability, support, and sustainability.
CPC § 0.0508 High relevance — show source text
(1) A steel striker barrier not less than 0.0508 of an inch (1.3 mm) thick, or equivalent, is installed between the tubing and the finished wall and extends at least 4 inches (102 mm) beyond concealed penetrations of plates, firestops, wall studs, and so on.
(2) The tubing is installed in single runs and is not rigidly secured. [NFPA 54:7.3.4] 1210.4.4 Industrial Occupancies. In industrial occupancies, gas piping in solid floors such as concrete shall be laid in channels in the floor and covered to permit access to the piping with a minimum of damage to the building. Where piping in floor channels could be exposed to excessive moisture or corrosive substances, the piping shall be protected in an approved manner.
[NFPA 54:7.3.5.1] 1210.4.5 Other Occupancies. In other than industrial occupancies and where approved by the Authority Having Jurisdiction, gas piping embedded in concrete floor slabs constructed with portland cement shall be surrounded with a minimum of 1 [1] ⁄ 2 inches (38 mm) of concrete and shall not be in physical contact with other metallic structures such as reinforcing rods or electrically neutral conductors. All piping, fittings, and risers shall be protected against corrosion in accordance with Section 1210.3.1. Piping shall not be embedded in concrete slabs containing quickset additives or cinder aggregate. [NFPA 54:7.3.5.2] 1210.5 Piping in Vertical Chases. Where gas piping exceeding 5 psi (34 kPa) is located within vertical chases in accordance with Section 1208.4(4), the requirements of Section 1210.5.1 through Section 1210.5.3 shall apply. [NFPA 54:7.4] 1210.5.1 Pressure Reduction. Where pressure reduction is required in branch connections for compliance with Section 1208.4, such reduction shall take place either inside the chase or immediately adjacent to the outside wall of the chase. Regulator venting and downstream overpressure protection shall comply with Section 1208.7.4 and Section 1208.8 through Section 1208.10.4. The regulator shall be
accessible for service and repair and vented in accordance with one of the following:
(1) Where the fuel gas is lighter than air, regulators equipped with a vent limiting means shall be permitted to be vented into the chase. Regulators not equipped with a vent limiting means shall be permitted to be vented either directly to the outdoors or to a point within the top 1 foot (305 mm) of the chase.
(2) Where the fuel gas is heavier than air, the regulator vent shall be vented only directly to the outdoors.
[NFPA 54:7.4.1]
1210.5.2 Chase Construction. Chase construction shall comply with local building codes with respect to fire resistance and protection of horizontal and vertical openings. [NFPA 54:7.4.2]
CPC § 1210.1.1 High relevance — show source text
1210.1.1 Cover Requirements. Underground piping systems shall be installed with a minimum of 12 inches (305 mm) of cover. The minimum cover shall be increased to 18 inches (457 mm) if external damage to the pipe or tubing from external forces is likely to result. Where a minimum of 12 inches (305 mm) of cover cannot be provided, the piping shall be installed in conduit.
[NFPA 54:7.1.2.1 – 7.1.2.1(B)]
1210.1.2 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench. [NFPA 54:7.1.2.2]
1210.1.2.1 Backfilling. Where flooding of the trench is done to consolidate the backfill, care shall be exercised to see that the pipe is not floated from its firm bearing on the trench bottom. [NFPA 54:7.1.2.3]
1210.1.3 Protection Against Corrosion. Steel pipe and steel tubing installed underground shall be installed in accordance with Section 1210.1.3.1 through Section 1210.1.3.9. [NFPA 54:7.1.3]
1210.1.3.1 Zinc Coating. Zinc coating (galvanizing) shall not be deemed adequate protection for underground gas piping. [NFPA 54:7.1.3.1]
1210.1.3.2 Underground Piping. Underground piping shall comply with one or more of the following unless approved technical justification is provided to demonstrate that protection is unnecessary:
(1) The piping shall be made of corrosion-resistant material that is suitable for the environment in
which it will be installed.
(2) Pipe shall have a factory-applied, electrically insulating coating. Fittings and joints between sections of coated pipe shall be coated in accordance with the coating manufacturer’s instructions.
(3) The piping shall have a cathodic protection system installed, and the system shall be maintained in accordance with Section 1210.1.3.3 or
Section 1210.1.3.6. [NFPA 54:7.1.3.2]
SHUTOFF VALVE
APPLICATIONSTANDARDS
Appliance shutoff valve up
to ½ psiCSA/ANSI Z21.15/CSA 9.1
Appliance shutoff valve up
to ½ psiASME B16.44
Appliance shutoff valve up
to ½ psiASME B16.33 marked 125 G
Appliance shutoff valve up
to ½ psiANSI LC 4/CSA 6.32
Valve up to ½ psiASME B16.44
Valve up to ½ psiASME B16.33 marked 125 G
Valve up to ½ psiANSI LC 4/CSA 6. CPC § 7.3.4 High relevance — show source text
the tubing and the finished wall and extends at least 4 inches (102 mm) beyond concealed penetrations of plates, firestops, wall studs, and so on.
(2) The tubing is installed in single runs and is not rigidly secured. [NFPA 54:7.3.4]
1310.4.4 Industrial Occupancies. In industrial occupancies, gas piping in solid floors such as concrete shall be laid in channels in the floor and covered to permit access to the piping with a minimum of damage to the building. Where piping in floor channels could be exposed to excessive moisture or corrosive substances, the piping shall be protected in an approved manner.
[NFPA 54:7.3.5.1]
1310.4.5 Other Occupancies. In other than industrial occupancies and where approved by the Authority Having Jurisdiction, gas piping embedded in concrete floor slabs constructed with Portland cement shall be surrounded with a minimum of 1 [1] ⁄ 2 inches (38 mm) of concrete and shall not be in physical contact with other metallic structures such as reinforcing rods or electrically neutral conductors. All piping, fittings, and risers shall be protected against corrosion in accordance with Section 1310.3.1. Piping shall not be embedded in concrete slabs containing quickset additives or cinder aggregate. [NFPA 54:7.3.5.2]
1310.5 Piping in Vertical Chases. Where gas piping exceeding 5 psi (34 kPa) is located within vertical chases in accordance with Section 1310.6, the requirements of Section 1310.5.1 through Section 1310.5.3 shall apply. [NFPA 54:7.4]
1310.5.1 Pressure Reduction. Where pressure reduction is required in branch connections for compliance with Section 1310.6, such reduction shall take place either inside the chase or immediately adjacent to the outside wall of the chase. Regulator venting and downstream overpressure protection shall comply with Section 1308.6.4 and Section 1308.7. The regulator shall be accessible for service and repair, and vented in accordance with one of the following:
(1) Where the fuel gas is lighter than air, regulators equipped with a vent limiting means shall be permitted to be vented into the chase. Regulators not equipped with a vent limiting means shall be permitted to be vented either directly to the outdoors or to a point within the top 1 foot (305 mm) of the chase.
(2) Where the fuel gas is heavier than air, the regulator vent shall be vented only directly to the outdoors.
[NFPA 54:7.4.1]
1310.5.2 Chase Construction. Chase construction
shall comply with local building codes with respect to fire resistance and protection of horizontal and vertical openings. [NFPA 54:7.4.2]
1310.5.3 Ventilation. A chase shall be ventilated to the
outdoors and only at the top. The opening(s) shall have a minimum free area [in square inches (square meters)] equal to the product of one-half of the maximum pressure in the piping [in pounds per square inch (kilopas
cals)] times the largest nominal diameter of that piping
CPC § 25270.2 High relevance — show source text
as described in Health and Safety Code Section 25270.2(o)(1)(C)(i)._ 3. Piping systems connected to a petroleum hazardous waste tank in an underground area that complies with the hazardous waste tank standards pursuant to the California Code of Regulations, Title 22, Chapter 15, Article 10 (commencing with Section 66265.190), and the facility has been issued a unified program facility permit pursu- ant to Health and Safety Code Section 25404.2 for generation, treatment, accumulation or storage of hazardous waste, as described in Health and Safety Code Section 25270.2(o)(1) (C)(ii).
5703.6.3 Testing. Unless tested in accordance with the applicable section of ASME B31.9, piping, before being covered, enclosed or placed in use, shall be hydrostatically tested to 150 percent of the maximum anticipated pressure of the system, or pneumatically tested to 110 percent of the maximum anticipated pressure of the system, but not less than 5 pounds per square inch gauge (psig) (34.47 kPa) at the highest point of the system. This test shall be maintained for a sufficient time period to complete visual inspection of joints and connections. For not less than 10 minutes, there shall be no leakage or permanent distortion. Care shall be exercised to ensure that these pressures are not applied to vented storage tanks. Such storage tanks shall be tested independently from the piping.
2025 CALIFORNIA FIRE CODE 57-7
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FLAMMABLE AND COMBUSTIBLE LIQUIDS
5703.6.3.1 Existing piping. Existing piping shall be tested in accordance with this section where the fire code official has reasonable cause to believe that a leak exists. Piping that could contain flammable or combustible liquids shall not be tested pneumatically. Such tests shall be at the expense of the owner or operator.
Exception: Vapor-recovery piping is allowed to be tested using an inert gas.
5703.6.4 Protection from vehicles. Guard posts or other approved means shall be provided to protect piping, valves or fittings subject to vehicular damage in accordance with Section 312.
5703.6.5 Protection from external corrosion and galvanic action. Where subject to external corrosion, piping, related fluidhandling components and supports for both underground and above-ground applications shall be fabricated from noncorrosive materials, and coated or provided with corrosion protection. Dissimilar metallic parts that promote galvanic action shall not be joined.
5703.6.6 Valves. Piping systems shall contain a sufficient number of manual control valves and check valves to operate the system properly and to protect the plant under both normal and emergency conditions. Piping systems in connection with pumps shall contain a sufficient number of such valves to control properly the flow of liquids in normal operation and in the event of physical damage or fire exposure.
5703.6.6.1 Backflow protections. Connections to pipelines or piping by which equipment (such as tank cars, tank vehicles or marine vessels) discharges liquids into storage tanks shall be provided with check valves or block valves for automatic protection against backflow where the piping arrangement is such that backflow from the system is possible. Where loading and unloading is done through a common pipe system, a check valve is not required. However, a block valve, located in an area where it is provided with ready access or remotely operable, shall be provided.
CPC § 5703.6.8 High relevance — show source text
5703.6.8 Piping supports. Piping systems shall be substantially supported and protected against physical damage and excessive stresses arising from settlement, vibration, expansion, contraction or exposure to fire. The supports shall be protected against exposure to fire by one of the following:
- Draining liquid away from the piping system at a minimum slope of not less than 1 percent.
- Providing protection with a fire-resistance rating of not less than 2 hours.
- Other approved methods.
5703.6.9 Flexible joints. Flexible joints shall be listed and approved and shall be installed on underground liquid, vapor and vent piping at all of the following locations:
- Where piping connects to underground tanks.
- Where piping ends at pump islands and vent risers.
- At points where differential movement in the piping can occur.
5703.6.9.1 Fiberglass-reinforced plastic piping. Fiberglass-reinforced plastic (FRP) piping is not required to be provided with flexible joints in locations where both of the following conditions are present:
- Piping does not exceed 4 inches (102 mm) in diameter.
- Piping has a straight run of not less than 4 feet (1219 mm) on one side of the connection where such connections result in a change of direction.
In lieu of the minimum 4-foot (1219 mm) straight run length, approved and listed flexible joints are allowed to be used under dispensers and suction pumps, at submerged pumps and tanks, and where vents extend above ground.
5703.6.10 Pipe joints. Joints shall be liquid tight and shall be welded, flanged or threaded except that listed flexible connectors are allowed in accordance with Section 5703.6.9. Threaded or flanged joints shall fit tightly by using approved methods and materials for the type of joint. Joints in piping systems used for Class I liquids shall be welded where located in concealed spaces within buildings.
Nonmetallic joints shall be approved and shall be installed in accordance with the manufacturer’s instructions.
Pipe joints that are dependent on the friction characteristics or resiliency of combustible materials for liquid tightness of piping shall not be used in buildings. Piping shall be secured to prevent disengagement at the fitting.
5703.6.11 Bends. Pipe and tubing shall be bent in accordance with ASME B31.9.
SECTION 5704—STORAGE
5704.1 General. The storage of flammable and combustible liquids in containers and tanks shall be in accordance with this section and the applicable sections of Chapter 50.
5704.2 Tank storage. The provisions of this section shall apply to:
- The storage of flammable and combustible liquids in fixed above-ground and underground tanks. Exception: Tanks connected to building heating systems installed in accordance with Section 605.4.
57-8 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FLAMMABLE AND COMBUSTIBLE LIQUIDS
- The storage of flammable and combustible liquids in fixed above-ground tanks inside of buildings. Exception: Tanks connected to building heating systems installed in accordance with Section 605.4.
- The storage of flammable and combustible liquids in portable tanks whose capacity exceeds 660 gallons (2498 L).
- The installation of such tanks and portable tanks.
CPC § 1.11.0. High relevance — show source text
Agency
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended
sections listed below)
Adopt only those sections
that are listed below
Chapter/Section|BSC|BSC-
CG|SFM|1|2|1-AC|AC|** SS**|SS/CC|1|1R|2|3|4|5|6|6|6|6|6|6|6|6|6| |Adopting Agency
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended
sections listed below)
Adopt only those sections
that are listed below
Chapter/Section|||X|||||||X|X|X|X|X|X|X||||||||| |Adopting Agency
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended
sections listed below)
Adopt only those sections
that are listed below
Chapter/Section||||||||||||||||||||||||| |Adopting Agency
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended
sections listed below)
Adopt only those sections
that are listed below
Chapter/Section||||||||||||||||||||||||| |Adopting Agency
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended
sections listed below)
Adopt only those sections
that are listed below
Chapter/Section||||||||||||||||||||||||| |Adopting Agency
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended
sections listed below)
Adopt only those sections
that are listed below
Chapter/Section|||||||||||||||||||||||||This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
2025 CALIFORNIA PLUMBING CODE 303
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
304 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHAPTER 14
FIRESTOP PROTECTION
1401.0 General.
1401.1 Applicability. Piping penetrations of required fireresistance-rated walls, partitions, floors, floor/ceiling assemblies, roof/ceiling assemblies, or shaft enclosures shall be protected in accordance with the requirements of the building code, and this chapter.
1402.0 Construction Documents.
1402.1 Penetrations. Construction documents shall indicate with sufficient detail how penetrations of fire-resistancerated assemblies shall be firestopped prior to obtaining design approval.
1403.0 Installation.
1403.1 Materials. Firestop systems shall be installed in accordance with this chapter, the building code, and the manufacturer’s installation instructions.
CPC § 603.5.17 High relevance — show source text
603.5.17 Potable Water Outlets and Valves. Potable water outlets, freeze-proof yard hydrants, combination stop-and-waste valves, or other fixtures that incorporate a stop and waste feature that drains into the ground shall not be installed underground. 603.5.18 Pure Water Process Systems. The water supply to a pure water process system, such as dialysis water systems, semiconductor washing systems, and similar process piping systems, shall be protected from backpressure and backsiphonage by a reduced-pressure principle backflow preventer. 603.5.18.1 Dialysis Water Systems. The individual connections of the dialysis related equipment to the dialysis pure water system shall not require additional backflow protection. 603.5.19 Garbage Can Washers. Where garbage can washers are connected to a potable water supply system, the connection shall be protected against backflow in accordance with Table 603.2.
603.5.20 Plumbing Fixture Fittings. Plumbing fixture fittings with integral backflow protection shall comply with ASME A112.18.1/CSA B125.1. 603.5.21 Swimming Pools, Spas, and Hot Tubs. Potable water supply to swimming pools, spas, and hot tubs shall be protected by an air gap or a reduced pressure principle backflow preventer in accordance with the following:
(1) The unit is equipped with a submerged fill line.
(2) The potable water supply is directly connected to the unit circulation system. 603.5.22 Chemical Dispensers. The water supply to chemical dispensers shall be protected against backflow by one of the following:
(1) The chemical dispenser shall comply with ANSI/CAN/ASSE/IAPMO 1055. Where an installation involves a water source coming from a faucet with an integrated vacuum breaker device, a pressure bleed device conforming to IAPMO PS 104 shall be used to protect the vacuum breaker device.
(2) Water supply shall be protected by one of the following methods:
(a) Air gap
(b) Atmospheric vacuum breaker (AVB)
(c) Pressure vacuum breaker backflow prevention assembly (PVB)
(d) Spill-resistant pressure vacuum breaker (SVB)
(e) Reduced-pressure principle backflow prevention assembly (RP)
«
«
«
2025 CALIFORNIA PLUMBING CODE 145
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
WATER SUPPLY AND DISTRIBUTION
604.0 Materials.
604.1 Pipe, Tube, and Fittings. Pipe, tube, fittings, solvent cement, thread sealants, solders, and flux used in potable water systems intended to supply drinking water shall comply with NSF/ANSI/CAN 61. Where pipe fittings and valves are made from copper alloys containing more than 15 percent zinc by weight and are used in plastic piping systems, they shall be resistant to dezincification and stress corrosion cracking in compliance with NSF/ANSI 14.
Materials used in the water supply system, except valves and similar devices, shall be of a like material, except where otherwise approved by the Authority Having Jurisdiction.
Materials for building water piping and building supply piping shall comply with the applicable standards referenced in Table 604.1.
CPC § 309.0 High relevance — show source text
2025 CALIFORNIA PLUMBING CODE 469
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
IS 33
Uniform Plumbing Code References for Ductile Iron and PVC Pressure Building Supply and Exterior Cold-Water Piping
The following sections of the 2024 Uniform Plumbing Code apply to ductile iron and PVC pressure building supply and exterior cold-water piping.
Chapter 3 General Regulations
309.0 Workmanship
312.0 Protection of Piping, Materials, and Struc tures
313.0 Hangers, Supports, and Anchors
314.0 Trenching, Excavation, and Backfill
Chapter 6 Water Supply and Distribution
604.0 Materials (water piping)
Table 604.1 Materials for Building Supply and Water Distribution Piping and Fittings
605.4 Ductile Iron Pipe and Joints
605.12 PVC Plastic Pipe and Joints
605.16.2 Plastic Pipe to Other Materials
609.0 Installation, Testing, Unions, and Location
Abbreviations
IAPMO International Association of Plumbing and Mechanical Officials
UPC Uniform Plumbing Code published by IAPMO
AWWA American Water Works Association
CSA Canadian Standards Association
Applicable Standards.
ASME B16.4 Gray Iron Threaded Fittings Classes 125 and 250
ASTM D1785 Poly (Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40, 80, and 120
ASTM D2241 Poly (Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)
ASTM D2466 Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40
ASTM D2467 Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80
ASTM F1970 Special Engineered Fittings, Appurtenances or Valves for use in Poly (Vinyl Chloride) (PVC) or Chlorinated Poly (Vinyl Chloride) (CPVC) Systems
AWWA C110 Ductile Iron and Gray-Iron Fittings
AWWA C111 Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings
AWWA C151 Ductile-Iron Pipe, Centrifugally Cast
AWWA C153 Ductile-Iron Compact Fitting
AWWA C900 Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 4 in. through 12 in. (100 mm through 300 mm)
AWWA C904 Crosslinked Polyethylene (PEX) Pressure Tubing, ½ in. through 3 In. (13 mm through 76 mm), for Water Service
AWWA C907 Injection-Molded Polyvinyl Chloride (PVC) Pressure Fittings, 4 In, through 12 in (100 mm through 300 mm) for Water, Wastewater and Reclaimed Water Service
IAPMO/
ANSI UPC-1 Uniform Plumbing Code
470 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CPC § 4.6 Medium relevance — show source text
Considerations are soil density; clearance from obstacles, utilities, and structures; location of bends, and water service locations. Excavations and shoring shall be in accordance with jurisdictional safety requirements. (c) Set Up Fuse the proper length of polyethylene pipe in accordance with ASTM F2620, or ASTM D3261 and fuse the end to a small length that is attached to the pulling head. A rod pusher cable is pushed through the damaged host pipe and attached to the pulling cable, which is then drawn through the pipe. The clevis end of the cable is attached to the pulling head. The pulling equipment is then set up according to the manufacturer’s instructions.
(d) Pulling Pull the pulling head through. Once the pull is done, complete the connection to the existing piping.
4.6 Cleanouts
4.6.1 Plug Each cleanout fitting for cast-iron pipe shall consist of a cast-iron or brass body and an approved plug. Each cleanout for galvanized wrought-iron, galvanized steel, copper, or brass pipe shall consist of a brass plug as specified in Table 1, or a standard weight brass cap, or an approved ABS or PVC plastic plug, or an approved stainless-steel cleanout or plug. Plugs shall have raised square heads or approved countersunk rectangular slots. 4.6.2 Approved Each cleanout fitting and each cleanout plug, or cap shall be of an approved type.
452 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
IS 26
4.6.3 Watertight and Gastight
Cleanouts shall be designed to be watertight and gastight.
5 Testing and Inspection Requirements
5.1 Media
The piping of the building sewer shall be tested with water. The Authority Having Jurisdiction shall be permitted to require the removal of cleanouts, etc., to ascertain whether the pressure has reached all parts of the system.
5.2 Water Test
The system shall be tested by plugging the end of the building sewer at its points of connection to the public sewer or private sewage disposal system and completely filling the building sewer with water from the lowest to the highest point thereof.
5.3 Inspections
The completed piping shall be internally inspected by camera unless waived by the Administrative Authority.
TABLE 1
CLEANOUTS (See Section 4.6.1)
NPS SIZE OF CLEANOUT
(inches)THREADS PER INCH 1.5 1.5 11.5
21.5 11.5
2.52.5 8
32.5 8
4 & larger3.5 8 Note: For SI units: 1 inch = 25 mm
Uniform Plumbing Code References
The following sections of the 2024 Uniform Plumbing Code apply.
105.2 Required Inspections
105.2.2 Other Inspections
105.3 Testing of Systems
301.2 Minimum Standards
309.0 Workmanship
312.0 Protection of Piping, Materials, and Structures
CPC § 4.1 Medium relevance — show source text
- 100°F
(16°C-38°C)|1 h|6 h|2 h|12 h|6 h|24 h| |40°F-60°F
(4°C-16°C)|2 h|12 h|4 h|24 h|12 h|48 h| |10°F- 40°F
(-12°C+4°C)|8 h|48 h|16 h|96 h|48 h|8 days| |*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|*If gaps or loose fits are encountered in the system, double these cure times.|
2025 CALIFORNIA PLUMBING CODE 467
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
IS 33
FIGURE 1
LOCATION OF THRUST BLOCKS (STANDARD AND METRIC COMBINED) A COMPARISON OF THRUST-BLOCK AREAS (See Section 4.1)
468 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
IS 33
FIGURE 2
THRUST BLOCK BEARING AREA (See Section 5.2.2)
2025 CALIFORNIA PLUMBING CODE 469
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
IS 33
Uniform Plumbing Code References for Ductile Iron and PVC Pressure Building Supply and Exterior Cold-Water Piping
The following sections of the 2024 Uniform Plumbing Code apply to ductile iron and PVC pressure building supply and exterior cold-water piping.
Chapter 3 General Regulations
309.0 Workmanship
312.0 Protection of Piping, Materials, and Struc tures
313.0 Hangers, Supports, and Anchors
314.0 Trenching, Excavation, and Backfill
Chapter 6 Water Supply and Distribution
604.0 Materials (water piping)
Table 604.1 Materials for Building Supply and Water Distribution Piping and Fittings
605.4 Ductile Iron Pipe and Joints
605.12 PVC Plastic Pipe and Joints
605.16.2 Plastic Pipe to Other Materials
609.0 Installation, Testing, Unions, and Location
Abbreviations
IAPMO International Association of Plumbing and Mechanical Officials
UPC Uniform Plumbing Code published by IAPMO
AWWA American Water Works Association
CSA Canadian Standards Association
Applicable Standards.
ASME B16.4 Gray Iron Threaded Fittings Classes 125 and 250
ASTM D1785 Poly (Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40, 80, and 120
ASTM D2241 Poly (Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)
- 100°F
CPC § 11.0 Medium relevance — show source text
11.0 - 1.11.11_|||X|||||||||||||||||||||| |1.13.0||||||||||||||||||||X||||| |Division II - Scope and
Administration||||||||||||||||||||||||| |101.0||||||||||X|X|X||X|X|||||||||| |102.0||||||||||X|X|X||X|X|||||||||| |103.0||||||||||X|X|X||X|X|||||||||| |104.2 Items 1 & 2||||X|X|||||||||||||||||||| |104.3.1||||||||||X|X|X||X|X|||||||||| |104.4.3.1|X|||||||||||||||||||||||| |105.0||||||||||X|X|X||X|X||||||||||This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
2 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHAPTER 1
ADMINISTRATION
DIVISION I
CALIFORNIA ADMINISTRATION
1.1.0 General.
1.1.1 Title. These regulations shall be known as the Califor- nia Plumbing Code, may be cited as such and will be referred to herein as “this code.” The California Plumbing Code is Part 5 of thirteen parts of the official compilation and publi- cation of the adoption, amendment, and repeal of plumbing regulations to the California Code of Regulations, Title 24, also referred to as the California Building Standards Code. This part incorporates by adoption the 2024 Uniform Plumb- ing Code of the International Association of Plumbing and Mechanical Officials with necessary California amendments.
1.1.2 Purpose. The purpose of this code is to establish the minimum requirements to safeguard the public health, safety and general welfare through structural strength, means of egress facilities, stability, access to persons with disabilities, sanitation, adequate lighting and ventilation, and energy con- servation; safety to life and property from fire and other haz- ards attributed to the built environment; and to provide safety to fire fighters and emergency responders during emergency operations.
1.1.3 Scope. The provisions of this code shall apply to the construction, alteration, movement, enlargement, replace- ment, repair, equipment, use and occupancy, location, main- tenance, removal, and demolition of every building or structure or any appurtenances connected or attached to such buildings or structures throughout the State of California.
CPC § 1502.4 Medium relevance — show source text
Inspection and Testing . . . . . . . . .310
1502.4 Separation Requirements . . . . . . .311
1502.5 Abandonment . . . . . . . . . . . . . . . .311
1502.6 Sizing . . . . . . . . . . . . . . . . . . . . . .312
1503.0 Gray Water Systems . . . . . . . . . .312
1503.1 General . . . . . . . . . . . . . . . . . . . . .312
1503.2 System Requirements . . . . . . . . .313
1503.3 Connections to Potable and
Reclaimed (Recycled) Water Systems . . . . . . . . . . . . . . . . . . . . .313
1503.4 Location . . . . . . . . . . . . . . . . . . . .313
1503.5 Plot Plan Submission . . . . . . . . . .313
1503.6 Prohibited Location . . . . . . . . . . . .313
Table 1503.4 Location of Gray Water System . . .314
1503.7 Drawings and Specifications . . . .314
1503.8 Procedure for Estimating Gray Water Discharge . . . . . . . . .314
1503.9 Gray Water System Components . . . . . . . . . . . . . . . . .315
1504.0 Subsurface Irrigation System Zones . . . . . . . . . . . . . . . .316
1504.1 General . . . . . . . . . . . . . . . . . . . . .316
1504.2 Required Area of Subsurface Irrigation Fields, Subsoil Irrigation Fields, and Mulch Basins . . . . . . . . . . . . . . . .316
1504.3 Determination of Maximum
Absorption Capacity . . . . . . . . . . .316
Table 1504.2 Design of Six Typical Soils . . . . . .316
1504.4 Groundwater Level . . . . . . . . . . . .316
1504.5 Irrigation, Disposal Field and Mulch Basin Construction . . . . . .316
Table 1504.5.3 Subsoil Irrigation Field Construction . . . . . . . . . . . . . . . . .318
Table 1504.5.5 Subsurface Irrigation Design Criteria for Six Typical Soils . . . . .318
1504.6 Reserved . . . . . . . . . . . . . . . . . . .318
1504.7 Reserved . . . . . . . . . . . . . . . . . . .318
1504.8 Gray Water System Color and Marking Information . . . . . . . .318
1504.9 Other Collection and
Distribution Systems . . . . . . . . . . .318
1504.10 Testing . . . . . . . . . . . . . . . . . . . . .318
1504.11 Maintenance . . . . . . . . . . . . . . . . .318
1505.0 Recycled Water Supply Systems in Buildings . . . . . . . . . .318
CPC § 705.10 Medium relevance — show source text
Waste,
and Vent (DWV), Sewer, Sanitary, and Storm Plumbing Sys-
tems for Above and Below Ground Use|Joints|705.10|340 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFERENCED STANDARDS
TABLE 1701.1 (continued) REFERENCED STANDARDS
STANDARD NUMBER STANDARD TITLE APPLICATION REFERENCED
SECTIONASTM C1540-2020 Standard Specification for Heavy-Duty Shielded Couplings
Joining Hubless Cast Iron Soil Pipe and FittingsJoints 705.2.2 ASTM C1563-2008
(R2021)Standard Test Method for Gaskets for Use in Connection with
Hub and Spigot Cast Iron Soil Pipe and Fittings for Sanitary
Drain, Waste, Vent, and Storm Piping ApplicationsJoints 705.2.2 ASTM C1822-2021 Standard Specification for Insulating Covers on Accessible
Lavatory PipingMiscellaneous 403.3 ASTM D1253-2014 Standard Test Method for Residual Chlorine in Water Miscellaneous 1506.10.6, 1603.4.1 ASTM D1785-2021a Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
Pipe, Schedules 40, 80, and 120Piping Table 604.1, Table
701.2ASTM D2235-2021 Standard Specification for Solvent Cement for Acrylonitrile-
Butadiene-Styrene (ABS) Plastic Pipe and FittingsJoints 705.1.2 ASTM D2239-2021 Standard Specification for Polyethylene (PE) Plastic Pipe
(SIDR-PR) Based on Controlled Inside DiameterPiping Table 604.1 ASTM D2241-2020 Standard Specification for Poly (Vinyl Chloride) (PVC) Pressure-
Rated Pipe (SDR Series)Piping Table 604.1 ASTM D2464-2015 Standard Specification for Threaded Poly (Vinyl Chloride)
(PVC) Plastic Pipe Fittings, Schedule 80Fittings Table 604.1 ASTM D2466-2021 Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
Pipe Fittings, Schedule 40Fittings Table 604.1 ASTM D2467-2020 Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic
Pipe Fittings, Schedule 80Fittings Table 604.1 ASTM D2513-2020 Standard Specification for Polyethylene (PE) Gas Pressure
Pipe, Tubing, and FittingsPiping 1208.5.4, 1208.5.6.2,
1208.5.10.2,
1210.1.7.1(1)ASTM D2564-2020 Standard Specification for Solvent Cements for Poly (Vinyl
Chloride) (PVC) Plastic Piping SystemsJoints 605.12.2, 705.6. CPC § 1501.0 Medium relevance — show source text
1501.0 General . . . . . . . . . . . . . . . . . . . . .309
1501.1 Applicability . . . . . . . . . . . . . . . . . .309
1501.2 System Design . . . . . . . . . . . . . . .309
1501.3 Permit . . . . . . . . . . . . . . . . . . . . . .309
1501.4 Component Identification . . . . . . .309
1501.5 Maintenance and Inspection . . . .309
1501.6 Operation and Maintenance Manual . . . . . . . . . . . . . . . . . . . . .309
1501.7 Minimum Water Quality Requirements . . . . . . . . . . . . . . . .309
Table 1501.5 Recommended Minimum Alternate Water Source Testing, Inspection, and Maintenance Frequency . . . . . . . . . . . . . . . . . . .310
1501.8 Material Compatibility . . . . . . . . . .310
1501.9 Signage . . . . . . . . . . . . . . . . . . . .310
1501.10 System Controls . . . . . . . . . . . . . .310
1502.0 Inspection and Testing . . . . . . . . .310
1502.1 General . . . . . . . . . . . . . . . . . . . . .310
1502.2 Supply System Inspection and Test . . . . . . . . . . . . . . . . . . . .310
1502.3 Cross-Connection
Inspection and Testing . . . . . . . . .310
1502.4 Separation Requirements . . . . . . .311
1502.5 Abandonment . . . . . . . . . . . . . . . .311
1502.6 Sizing . . . . . . . . . . . . . . . . . . . . . .312
1503.0 Gray Water Systems . . . . . . . . . .312
1503.1 General . . . . . . . . . . . . . . . . . . . . .312
1503.2 System Requirements . . . . . . . . .313
1503.3 Connections to Potable and
Reclaimed (Recycled) Water Systems . . . . . . . . . . . . . . . . . . . . .313
1503.4 Location . . . . . . . . . . . . . . . . . . . .313
1503.5 Plot Plan Submission . . . . . . . . . .313
1503.6 Prohibited Location . . . . . . . . . . . .313
Table 1503.4 Location of Gray Water System . . .314
1503.7 Drawings and Specifications . . . .314
1503.8 Procedure for Estimating Gray Water Discharge . . . . . . . . .314
1503.9 Gray Water System Components . . . . . . . . . . . . . . . . .315
1504.0 Subsurface Irrigation System Zones . . . . . . . . . . . . . . . .316
1504.1 General . . . . . . . . . . . . . . . . . . . . .316
CPC § 304.8 Medium relevance — show source text
r>|5890
| |1600
|42
|89
|167
|343
|514
|989
|1580
|2790
|5680
| |1700
|41
|86
|162
|332
|497
|957
|1530
|2700
|5500
| |1800
|40
|83
|157
|322
|482
|928
|1480
|2610
|5330
| |1900
|39
|81
|152
|312
|468
|901
|1440
|2540
|5180
| |2000|38|79|148|304|455|877|1400|2470|5040|For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa
- Table entries are rounded to 3 significant digits.2025 CALIFORNIA PLUMBING CODE 239
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(4) SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2.1(e)]* Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10 GAS: GAS: NATURAL NATURAL INLET PRESSURE: INLET PRESSURE: 2.0 psi 2.0 psi PRESSURE DROP: PRESSURE DROP: ** 1.0 psi** ** 1.0 psi** SPECIFIC GRAVITY: SPECIFIC GRAVITY: 0.60 **0. CPC § 304.8 Medium relevance — show source text
r>37
35
34|83
79
76
73
70|169
161
155
148
143|296
282
270
260
250|420
400
383
368
355|896
855
819
787
758|1610
1540
1470
1420
1360|2540
2430
2320
2230
2150|5300
5050
4840
4650
4480| |1600
1700
1800
1900
2000|1600
1700
1800
1900
2000|33
32
31
30
29|68
66
64
62
60|138
134
130
126
122|241
234
227
220
214|343
331
321
312
304|732
708
687
667
648|1320
1270
1240
1200
1170|2080
2010
1950
1890
1840|4330
4190
4060
3940
3830|For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.8947 kPa Notes: 1 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 2 Table entries are rounded to 3 significant digits.
2025 CALIFORNIA PLUMBING CODE 263
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
California Plumbing Code Medium relevance — show source text
5
10
15
20|NA
NA
NA
NA
NA|NA
NA
NA
NA
NA|38
35
NA
NA
NA|NA
NA
NA
NA
NA|NA
NA
NA
NA
NA|73
67
59
NA
NA|NA
NA
NA
NA
NA|NA
NA
NA
NA
NA|123
115
105
95
80|NA
NA
NA
NA
NA|NA
NA
NA
NA
NA|200
183
170
156
144|163
NA
NA
NA
NA|520
NA
NA
NA
NA|273
252
235
217
202| |30|2
5
10
15
20
30|NA
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|41
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|81
75
66
NA
NA
NA|NA
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|136
127
113
105
88
NA|NA
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|215
196
182
168
155
NA|158
NA
NA
NA
NA
NA|578
NA
NA
NA
NA
NA|302
279
260
240
223
182| |50|2
5
10
15
20
30|NA
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|91
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|160
149
136
124
NA
NA|NA
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|250
228
212
195
180
NA|NA
NA
NA
NA
NA
NA|NA
NA
NA
NA
NA
NA|350
321
301
278
258
NA| |Minimum
internal area of
chimney
(square inches)|Minimum
internalCPC § 304.8 Medium relevance — show source text
6
64
62
60|138
134
130
126
122|241
234
227
220
214|343
331
321
312
304|732
708
687
667
648|1320
1270
1240
1200
1170|2080
2010
1950
1890
1840|4330
4190
4060
3940
3830|For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.8947 kPa Notes: 1 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 2 Table entries are rounded to 3 significant digits.
2025 CALIFORNIA PLUMBING CODE 263
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
TABLE 1215.2(29) SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.3.1(f)]2, 3 Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10 Col11 GAS: GAS: UNDILUTED PROPANE UNDILUTED PROPANE INLET PRESSURE: INLET PRESSURE: 11.0 in. w.c. 11.0 in. w.c. PRESSURE DROP: PRESSURE DROP: 0.5 in. w.c. 0.5 in. w.c. SPECIFIC GRAVITY: SPECIFIC GRAVITY: 1.50 1.50 INTENDED USE: TUBE SIZING BETWEEN SINGLE OR SECOND STAGE (LOW PRESSURE) REGULATOR AND APPLIANCE INTENDED USE: TUBE SIZING BETWEEN SINGLE OR SECOND STAGE (LOW PRESSURE) REGULATOR AND APPLIANCE INTENDED USE: TUBE SIZING BETWEEN SINGLE OR SECOND STAGE (LOW PRESSURE) REGULATOR AND APPLIANCE INTENDED USE: TUBE SIZING BETWEEN SINGLE OR SECOND STAGE (LOW PRESSURE) REGULATOR AND APPLIANCE INTENDED USE: TUBE SIZING BETWEEN SINGLE OR SECOND STAGE (LOW PRESSURE) REGULATOR AND APPLIANCE **INTENDED USE: TUBE California Plumbing Code Medium relevance — show source text
5
8|NA
NA
NA|NA
NA
NA|265
246
237|NA
NA
NA|NA
NA
NA|349
327
317|382
NA
NA|725
NA
NA|445
422
408|549
673
747|1021
1003
985|650
638
621| |10|2
5
10|216
NA
NA|518
NA
NA|297
276
261|271
334
NA|654
635
NA|387
364
345|373
459
547|808
789
758|490
465
441|536
657
771|1142
1121
1088|722
710
665| |15|2
5
10
15|211
261
NA
NA|611
591
NA
NA|335
312
294
278|264
325
392
452|776
755
722
692|440
414
392
372|362
444
531
606|965
942
907
873|560
531
504
481|520
637
749
841|1373
1348
1309
1272|840
825
774
738| |20|2
5
10
15
20|206
255
312
NA
NA|675
655
622
NA
NA|374
348
330
311
292|258
317
382
442
NA|864
842
806
773
NA|490
461
437
414
392|252
433
517
591
663|1079
1055
1016
979
944|625
594
562
539
510|508
623
733
823
911|1544
1518
1475
1434
1394|950
930
875
835
800| |30|2
5California Plumbing Code High relevance — show source text
RATING IN THOUSANDS OF BTU PER HOUR**|APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR| |HEIGHT
H
(feet)|LATERAL
L
(feet)|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR| |6|0
2
5|39
31
28|70
55
51|116
94
88|170
141
128|232
194
177|312
260
242|500
415
390|750
620
600| |8|0
2
5
10|42
32
29
24|76
61
56
49|126
102
95
86|185
154
141
131|252
210
194
180|340
284
264
250|542
451
430
406|815
680
648
625| |10|0
2
5
10
15|45
35
32
27
NA|84
67
61
54
46|138
111
104
94
84|202
168
153
143
130|279
233
215
200
186|372
311
289
274
258|606
505
480
455
432|912
760
724
700
666| |15|0
2
5
10
15
20|49
39
35
30
NA
NA|91
72
67
58
50
NA|151
122
110
103
93
82|223
186
170
158
144
132|312
260
240
223
207
195|420
350
325
308
291
273|684
570
540
514
488
466|1040
865
825
795
760
726| |20|0
2
5CPC § 5704.4.3 High relevance — show source text
5704.4.3 Spill control and secondary containment. Storage areas shall be provided with spill control and secondary containment in accordance with Section 5703.4.
Exception: Containers stored on approved containment pallets in accordance with Section 5004.2.3 and containers stored in cabinets and lockers with integral spill containment.
5704.4.4 Security. Storage areas shall be protected against tampering or trespassers by fencing or other approved control
measures.
5704.4.5 Protection from vehicles. Guard posts or other means shall be provided to protect exterior storage tanks from vehicular damage. Where guard posts are installed, the posts shall be installed in accordance with Section 312.
5704.4.6 Clearance from combustibles. The storage area shall be kept free from weeds, debris and combustible materials not necessary to the storage. The area surrounding an exterior storage area shall be kept clear of such materials for a minimum distance of 15 feet (4572 mm).
5704.4.7 Weather protection. Weather protection for outdoor storage shall be in accordance with Section 5004.13.
5704.4.8 Empty containers and tank storage. The storage of empty tanks and containers previously used for the storage of flammable or combustible liquids, unless free from explosive vapors, shall be stored as required for filled containers and tanks. Tanks and containers when emptied shall have the covers or plugs immediately replaced in openings.
SECTION 5705—DISPENSING, USE, MIXING AND HANDLING
5705.1 Scope. Dispensing, use, mixing and handling of flammable liquids shall be in accordance with Section 5703 and this section. Tank vehicle and tank car loading and unloading and other special operations shall be in accordance with Section 5706.
Exception: Containers of organic coatings having no fire point and which are opened for pigmentation are not required to comply with this section.
5705.2 Liquid transfer. Liquid transfer equipment and methods for transfer of Class I, II and IIIA liquids shall be approved and be in accordance with Sections 5705.2.1 through 5705.2.6.
5705.2.1 Pumps. Where positive-displacement pumps are used, they shall be provided with pressure relief discharging back to the tank, pump suction or other approved location, or shall be provided with interlocks to prevent over-pressure.
5705.2.2 Pressured systems. Where gases are introduced to provide for transfer of Class I liquids, or Class II and III liquids transferred at temperatures at or above their flash points by pressure, only inert gases shall be used. Controls, including pressure relief devices, shall be provided to limit the pressure so that the maximum working pressure of tanks, containers and piping systems cannot be exceeded. Where devices operating through pressure within a tank or container are used, the tank or container shall be a pressure vessel approved for the intended use. Air or oxygen shall not be used for pressurization.
Exception: Air transfer of Class II and III liquids at temperatures below their flash points.
5705.2.3 Piping, hoses and valves. Piping, hoses and valves used in liquid transfer operations shall be approved or listed for the intended use.
California Plumbing Code Medium relevance — show source text
2
5
10
15
20
30|184
175
215
265
312
360
461|1168
823
806
777
750
723
670|647
533
521
501
481
461
426|229
219
269
327
379
433
541|1542
1069
1049
1017
985
955
895|852
698
684
662
638
615
574|312
296
366
440
507
570
704|1971
1346
1324
1287
1251
1216
1147|1056
863
846
821
794
768
720|454
424
524
620
702
780
937|2996
1999
1971
1927
1884
1841
1759|1545
1308
1283
1243
1205
1166
1101| |50|0
2
5
10
15
20
30|176
168
204
253
299
345
442|1292
971
953
923
894
866
809|704
613
602
583
562
543
502|220
209
257
313
363
415
521|1724
1273
1252
1217
1183
1150
1086|948
811
795
765
736
708
649|295
280
347
418
481
544
674|2223
1615
1591
1551
1512
1473
1399|1189
1007
991
963
934
906
848|428
401
496
589
668
741
892|3432
2426
2396
2347
2299
2251
2159|1818
1509
1490
1455
1421
1387
1318| |100|0
2
5CPC § 0.34 Medium relevance — show source text
32 to 0.34|250|4.5|5.0|5.0|5.0|5.0| |251 to 350|0.29 to 0.32|200|3.0|4.0|4.5|4.5|4.5| |201 to 250|0.27 to 0.30|150|2.5|2.5|2.5|3.0|3.0| |141 to 200|0.25 to 0.29|125|1.5|1.5|2.0|2.0|2.0| |105 to 140|0.22 to 0.28|100|1.0|1.0|1.5|1.5|1.5|
For SI units: °C=(°F-32)/1.8, 1 inch = 25 mm, 1 British thermal unit inch per hour square foot degree Fahrenheit = [0.1 W/(m•K)]
Notes: 1 For insulation outside the stated conductivity range, the minimum thickness ( T ) shall be determined as follows: T = r {(1 + t / r ) [K] [/] [k ] – 1}
Where:
T = minimum insulation thickness (inches). r = actual outside radius of pipe (inches). t = insulation thickness listed in this table for applicable fluid temperature and pipe size. K = conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature [Btu•in/(h•ft [2] - °F)] [W/(m•K)]. k = the upper value of the conductivity range listed in this table for the applicable fluid temperature. 2 These thicknesses are on energy efficiency considerations only. Additional insulation is sometimes required relative to safety issues/surface temperature. 3 For piping smaller than 1 1 ⁄ 2 inches (40 mm) or less and located in partitions within conditioned spaces, reduction of these thicknesses by 1 inch (25.4 mm) shall be permitted (before thickness adjustment required in footnote 1) but not to thicknesses below 1 inch (25.4 mm). 4 For direct-buried heating and hot water system piping, reduction of these thicknesses by 1 1 ⁄ 2 inch (40 mm) shall be permitted (before thickness adjustment required in footnote 1) but not to thicknesses below 1 inch (25.4 mm). 5 Table E 503.7.3(1) is based on steel pipe. Nonmetallic pipes schedule 80 thickness or less shall use the table values. For other nonmetallic pipes having thermal resistance more than that of steel pipe, reduced insulation thicknesses are permitted where documentation is provided showing that the pipe with the proposed insulation has no more heat transfer per foot (mm) than a steel pipe of the same size with the insulation thickness shown in Table E 503.7.3(1).
474 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
APPENDIX E
TABLE E 503.7.3(2) MINIMUM PIPE INSULATION THICKNESS FOR COOLING SYSTEMS (CHILLED WATER, BRINE, AND REFRIGERANT) [1,2,3,4 ]
[ASHRAE 90.1: TABLE 6.8.3-2]
CPC § 2306.6.2.3 Medium relevance — show source text
2306.6.2.3 Overfill protection. Overfill protection shall be provided for above-ground flammable and combustible liquid storage tanks in accordance with Sections 5704.2.7.5.8 and 5704.2.9.7.5.
2306.6.2.4 Siphon prevention. An approved antisiphon method shall be provided in the piping system to prevent flow of liquid by siphon action.
2306.6.2.5 Emergency relief venting. Above-ground storage tanks, tank compartments and enclosed secondary containment spaces shall be provided with emergency relief venting in accordance with Chapter 57.
2306.6.2.6 Spill containers. A spill container having a capacity of not less than 5 gallons (19 L) shall be provided for each fill connection. For tanks with a top fill connection, spill containers shall be noncombustible and shall be fixed to the tank and
2025 CALIFORNIA FIRE CODE 23-7
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
equipped with a manual drain valve that drains into the primary tank. For tanks with a remote fill connection, a portable spill container is allowed.
2306.6.2.7 Piping for tanks in underground areas. Piping systems connected to a tank in an underground area shall also comply with Section 5703.6.2.2.
2306.6.3 Piping, valves, fittings and ancillary equipment for underground tanks. Piping, valves, fittings and ancillary equipment for underground tanks shall comply with Chapter 57 and NFPA 30A.
2306.7 Fuel-dispensing systems for flammable or combustible liquids. The design, fabrication and installation of fuel-dispensing systems for flammable or combustible liquid fuels shall be in accordance with Sections 2306.7.1 through 2306.7.9.2.4. Alcoholblended fuel-dispensing systems shall also comply with Section 2306.8.
2306.7.1 Listed equipment. Electrical equipment, dispensers, hose, nozzles and submersible or subsurface pumps used in fueldispensing systems shall be listed.
2306.7.2 Fixed pumps required. Class I and II liquids shall be transferred from tanks by means of fixed pumps designed and equipped to allow control of the flow and prevent leakage or accidental discharge.
2306.7.3 Mounting of dispensers. Dispensing devices, except those installed on top of a protected above-ground tank that qualifies as vehicle-impact resistant, shall be protected against physical damage by mounting on a concrete island 6 inches (152 mm) or more in height, or shall be protected in accordance with Section 312. Dispensing devices shall be installed and securely fastened to their mounting surface in accordance with the dispenser manufacturer’s instructions. Dispensing devices installed indoors shall be located in an approved position where they cannot be struck by an out-of-control vehicle descending a ramp or other slope.
2306.7.3.1 Additional impact protection. The fire code official is authorized to require additional impact protection in accordance with Section 312 where dispensing devices are located in areas near parking areas, multiple dispensing devices, highway on- and off-ramps, and other areas where there is a higher potential for vehicle impacts.
**2306.7.4 Dispenser emergency shutoff valve.
California Plumbing Code Medium relevance — show source text
2
5
10
15
20|190
182
224
277
325
374|1053
708
692
666
640
616|573
468
457
437
419
400|238
227
279
339
393
448|1379
914
896
866
838
810|750
611
596
570
549
526|326
309
381
457
526
592|1751
1146
1126
1092
1060
1028|927
754
734
702
677
651|473
443
547
646
730
808|2631
1689
1665
1626
1587
1550|1346
1098
1074
1037
1005
973| |30|0
2
5
10
15
20
30|184
175
215
265
312
360
461|1168
823
806
777
750
723
670|647
533
521
501
481
461
426|229
219
269
327
379
433
541|1542
1069
1049
1017
985
955
895|852
698
684
662
638
615
574|312
296
366
440
507
570
704|1971
1346
1324
1287
1251
1216
1147|1056
863
846
821
794
768
720|454
424
524
620
702
780
937|2996
1999
1971
1927
1884
1841
1759|1545
1308
1283
1243
1205
1166
1101| |50|0
2
5CPC § 1-33 Medium relevance — show source text
112 Service Utilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-33
113 Means of Appeals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-33
114 Violations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-34
115 Stop Work Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-34
CHAPTER 2 DEFINITIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
201 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
202 Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
CHAPTER 3 OCCUPANCY CLASSIFICATION AND USE . . . . .3-1
301 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
302 Occupancy Classification and Use Designation . . . . 3-3
303 Assembly Group A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
304 Business Group B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
305 Educational Group E . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
306 Factory Group F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
307 High-Hazard Group H . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
308 Institutional Group I . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
309 Mercantile Group M. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
310 Residential Group R. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
311 Storage Group S. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
312 Utility and Miscellaneous Group U . . . . . . . . . . . . . . 3-18
313 Laboratories Group L [SFM]. . . . . . . . . . . . . . . . . . . . . . .3-19
Frequently asked questions
What does “not directly embedded in concrete” mean in practice?
It means you may not encase plumbing pipe directly in concrete or masonry pours. Provide a sleeve/conduit, route piping in an accessible chase, or use approved protective methods instead, per § 312.2 .
If my piping passes through a slab on grade, what must I do?
Seal the annular void around the piping where it passes through the slab and avoid embedding the piping directly in the concrete; use sleeves or other approved protection (§ 312.1, § 312.2) .
When is a steel nail plate required?
When plastic, copper, or copper‑alloy piping penetrates framing members to within 1 inch (25.4 mm) of an exposed face, install a steel nail plate No. 18 gauge thick that extends 1½ in (38 mm) beyond the pipe (§ 312.9) .
Do I need to firestop plumbing penetrations?
Yes — penetrations of fire‑resistance‑rated assemblies must be protected and the assembly rating restored in accordance with the California Building Code or California Residential Code, as required by § 312.7 .
I can’t find § 312.11 — can you tell me what it says?
I searched the uploaded CPC files and did not find text for § 312.11. I cannot cite or summarize it from these files. Please upload the page or allow me access to the missing code text if you need § 312.11 specifically.
More in California Plumbing Code
- Administration
- Definitions
- General Regulations
- Plumbing Fixtures and Fixture Fittings
- Water Heaters
- Water Supply and Distribution
- Sanitary Drainage (Drain, Waste, and Vent)
- Indirect Wastes
- Vents
- Traps and Interceptors
- Storm Drainage
- Fuel Gas Piping
- Health Care Facilities — Medical Gas and Medical Vacuum Systems
- Alternate Water Sources and Nonpotable Rainwater Catchment Systems
Ask about the CPC
Get cited, plain-English answers on the California Plumbing Code for your project — any code section, any scenario.
Start Free Trial