CHBC · California Historical Building Code
When can existing mechanical systems remain in place?
In plain English: historic heating/venting/duct systems can stay in a qualified historic building only if the local enforcing agency finds they are safe to operate. If they would be dangerous, they can remain only if they are permanently and completely taken out of service so they cannot be used. The authority can also approve performance-based alternatives to protect life safety while preserving historic features.
Last reviewed: July 6, 2026
What the code requires — 2–4 sentences
Existing mechanical systems may be left in place or continue in use in a qualified historical building only when they do not constitute a safety hazard, as judged by the enforcing agency (§ 8-902.1.2). If an existing system does constitute a safety hazard when operational, it may remain in the building only if it is completely and permanently rendered inoperative; otherwise it must be corrected to remove the hazard (§ 8-901.4). The CHBC also allows the enforcing agency to accept alternative solutions that achieve equivalent life safety (§ 8-902.1.3).
The single most important rule: an existing mechanical system is permitted to stay only if it is safe to operate — or, if unsafe, it must be permanently deactivated so it cannot create a hazard. § 8-902.1.2 and § 8-901.4 control this decision.
Requirements in detail
Key defined terms and first-use emphasis
- safety hazard — any condition threatening fire, health or life safety (CHBC intent and scope; used in §§ cited below).
- enforcing agency — the authority that evaluates whether a system is a safety hazard and approves alternatives.
- completely and permanently rendered inoperative — the required state for systems that are unsafe but are permitted to remain physically in the building per § 8-901.4.
Decision table — when a mechanical system may remain
| Decision factor | When permitted | Required action / limitation | Code reference |
|---|---|---|---|
| System does not constitute a safety hazard (operational) | May remain in use | Enforcing agency opinion governs; regular-code compliance normally required unless modified by CHBC | § 8-902.1.2 |
| System does constitute a safety hazard when operational | May remain only if completely and permanently rendered inoperative | Permanently deactivate/removal so it cannot be operated; inoperative systems must not create hazards | § 8-901.4 |
| Existing system noncompliant but not hazardous (e.g., old ducts) | May remain in use | Enforcing agency may allow continued use if no safety/health hazard is created | § 8-902.7.2 |
| Historic feature used as vent/chimney (masonry chimneys) | May remain for fuel-burning appliances if structurally sound and flue documented | Flue evaluation and documentation required; some materials (terra cotta, concealed Type C vents) need case-by-case mitigation/approval | § 8-902.6.2 |
| Alternatives to CHBC or regular code needed | Enforcing agency may approve if equivalent life safety achieved | Use performance-based/alternative solutions accepted by authority having jurisdiction | § 8-902.1.3 |
What "opinion of the enforcing agency" means in practice
- The CHBC repeatedly gives the enforcing agency discretion to judge whether a system is a safety hazard (see § 8-902.1.2, § 8-901.4, and other system-specific subsections). That opinion is the controlling determination for whether the system may remain in use or must be rendered inoperative.
Operational testing and documentation
- The CHBC allows the enforcing agency to require operational tests or evaluations for combustion air systems, venting systems, chimneys and ducts before permitting continued use. Plan to provide evaluation reports or test results when requesting to keep an older system in service. See, for example, § 8-902.5.2, § 8-902.6.3, and § 8-902.7.2.
Interaction with other CHBC allowances
- The CHBC is written to permit preservation of historic materials/methods so long as life safety is protected; enforcement decisions and allowed exceptions (e.g., masonry chimneys, archaic wiring) appear throughout Part 8 and are applied case-by-case by the enforcing agency.
Exceptions & special cases
- Masonry chimneys in structurally sound condition may remain in use for fuel-burning appliances, but the flue must be evaluated and documented; terra cotta chimneys and Type C metallic vents installed in concealed spaces shall not remain in use unless mitigated and approved on a case-by-case basis (§ 8-902.6.2).
- Existing ducts that do not meet regular-code requirements may still be permitted to remain if they do not constitute a safety or health hazard, per § 8-902.7.2; expect the enforcing agency to require testing or mitigation for obvious hazards (e.g., contaminated ducts).
- The enforcing agency may accept alternatives that achieve equivalent life safety (performance-based fixes rather than strict retrofits) — request these alternatives formally if historic integrity would be harmed by full regular-code compliance (§ 8-902.1.3).
Common mistakes
- Thinking "historic = always allowed": The CHBC permits retention of historic systems only when they are not safety hazards or are permanently rendered inoperative; historic status does not override life-safety concerns (§ 8-902.1.2, § 8-901.4).
- Treating the CHBC as a blanket exemption from the regular code: CHBC modifies application but still requires compliance where necessary and accepts alternatives only when they do not create a safety hazard (§ 8-902.1 General, § 8-901.3).
- Not documenting evaluations: For chimneys, vents and other fuel-burning systems, inspectors commonly require flue/combustion-air evaluations — lack of documentation can lead to an order to remove or permanently deactivate the system (§ 8-902.6.2, § 8-902.5.2).
- Confusing "may remain in use" with "no further work allowed": Even when a system may remain, the enforcing agency can still require testing, mitigation, or conditions of continued use. See duct and venting provisions for examples (§ 8-902.7.2, § 8-902.6.3).
Worked example — concrete scenario
Scenario: A 1908 historic hotel has its original gravity-fed gas-fired boiler and low-pressure steam distribution. The boiler shows corrosion but is currently operating.
Step 1 — Enforcing-agency evaluation: The local enforcing agency inspects and determines that continued operation is likely to produce carbon monoxide or a fire hazard (i.e., it constitutes a safety hazard). This determination is the CHBC trigger. § 8-901.4 controls.
Step 2 — Options under CHBC:
- If the owner can repair the boiler to meet the regular code (and the enforcing agency agrees), the owner may be required to bring that equipment into safe condition per the regular code. § 8-902.1 requires mechanical systems to comply with the regular code unless modified by this chapter.
- If repair would destroy historic character, the owner may propose an alternative solution demonstrating equivalent life safety (performance-based), which the enforcing agency may accept (§ 8-902.1.3).
- If neither repair nor an acceptable alternative is approved, the boiler may remain only if completely and permanently rendered inoperative (removed from service and decommissioned so it cannot be operated) per § 8-901.4. The owner must ensure that the inoperative boiler does not itself create a hazard (e.g., fuel left in place).
Numbers/thresholds in this example:
- No numeric “age” threshold matters — CHBC uses the enforcing agency’s safety-hazard judgment (qualitative). The decisive factors are documented hazard (e.g., CO emission measurements, visible corrosion causing leakage) and whether a safe, acceptably historic-preserving fix exists.
Related provisions
- § 8-902.6.2 — Chimney/vent reuse conditions and documentation requirements (masonry chimneys, terra cotta limits).
- § 8-902.7.2 — Existing duct systems that don’t comply may remain if not safety/health hazards.
- § 8-902.1.3 — Enforcing agency may approve alternatives that achieve equivalent life safety.
- § 8-903.1.2 — Parallel plumbing allowance: existing plumbing systems that don’t constitute a safety hazard may remain. (Plumbing counterpart to the mechanical rules.)
- § 8-904.1.2 — Electrical counterpart: existing electrical systems that do not constitute a safety hazard may remain in use.
- § 8-901.5 — Energy conservation exemptions for qualified historical buildings (relevant when replacing mechanical equipment).
Code references
Grounded in the retrieved California Historical Building Code — click a citation to read the verbatim passage:
CHBC § 8-9 High relevance — show source text
Bolt spacing shall not
exceed 6 feet (1830 mm) on center and shall not be less than 12 inches (305 mm) on center.
6. Other masonry based on tests or other substantiated data.
7. Embedded bolts to be tested as specified in regular code standards.
8. Stresses given may be increased for combinations of loads as specified in the regular code.
9. Adhesives shall be approved by the enforcing agency and installed in accordance with the manufacturer’s recommendations. All drilling dust shall be removed from drilled
holes prior to installation.|18 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-9 MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
SECTION 8-901 — PURPOSE, INTENT AND SCOPE
8-901.1 Purpose. The purpose of the CHBC is to provide regulations for the mechanical, plumbing and electrical systems of buildings designated as qualified historical buildings or properties. The CHBC requires enforcing agencies to accept any reasonable equivalent solutions to the regular code when dealing with qualified historical buildings or properties.
8-901.2 Intent. The intent of the CHBC is to preserve the integrity of qualified historical buildings or properties while providing a reasonable level of protection from fire, health and life safety hazards (hereinafter referred to as safety hazards) for the building occupants.
8-901.3 Scope. The CHBC shall be applied in conjunction with the regular code whenever compliance with the regular code is required for qualified historical buildings or properties.
8-901.4 Safety hazard. No person shall permit any safety hazard to exist on premises under their control, or fail to take immediate action to abate such hazard. Existing systems which constitute a safety hazard when operational may remain in place, provided they are completely and permanently rendered inoperative. Safety hazards created by inoperative systems shall not be permitted to exist. Requirements of the regular code concerning general regulations shall be complied with, except that the enforcing agency shall accept solutions which do not cause a safety hazard.
8-901.5 Energy conservation. Qualified historical buildings or properties covered by this part are exempted from compliance with energy conservation standards. When new nonhistorical lighting and space conditioning system components, devices, appliances and equipment are installed, they shall comply with the requirements of Title 24, Part 6, The California Energy Code, except where the historical significance or character-defining features are threatened.
SECTION 8-902 — MECHANICAL
8-902.1 General. Mechanical systems shall comply with the regular code unless otherwise modified by this chapter.
8-902.1.1 The provisions of the CHBC shall apply to the acceptance, location, installation, alteration, repair, relocation, replacement or addition of any heating, ventilating, air conditioning, domestic incinerators, kilns or miscellaneous heat-producing appliances or equipment within or attached to a historical building.
8-902.1.2 Existing systems which do not, in the opinion of the enforcing agency, constitute a safety hazard may remain in use.
8-902.1.3 The enforcing agency may approve any alternative to the CHBC which would achieve equivalent life safety.
8-902.2 Heating facilities. All dwelling-type occupancies covered under this chapter shall be provided with heating facilities. Woodburning or pellet stoves or fireplaces may be acceptable as heating facilities.
CHBC § 8-901.5 High relevance — show source text
8-901.5 Energy conservation. Qualified historical buildings or properties covered by this part are exempted from compliance with energy conservation standards. When new nonhistorical lighting and space conditioning system components, devices, appliances and equipment are installed, they shall comply with the requirements of Title 24, Part 6, The California Energy Code, except where the historical significance or character-defining features are threatened.
SECTION 8-902 — MECHANICAL
8-902.1 General. Mechanical systems shall comply with the regular code unless otherwise modified by this chapter.
8-902.1.1 The provisions of the CHBC shall apply to the acceptance, location, installation, alteration, repair, relocation, replacement or addition of any heating, ventilating, air conditioning, domestic incinerators, kilns or miscellaneous heat-producing appliances or equipment within or attached to a historical building.
8-902.1.2 Existing systems which do not, in the opinion of the enforcing agency, constitute a safety hazard may remain in use.
8-902.1.3 The enforcing agency may approve any alternative to the CHBC which would achieve equivalent life safety.
8-902.2 Heating facilities. All dwelling-type occupancies covered under this chapter shall be provided with heating facilities. Woodburning or pellet stoves or fireplaces may be acceptable as heating facilities.
8-902.3 Fuel oil piping and tanks. Fuel oil piping and tanks shall comply with regular code requirements except that the enforcing agency may waive such requirements where the lack of compliance does not create a safety or environmental hazard.
8-902.4 Heat-producing and cooling equipment. Heat-producing and cooling equipment shall comply with the regular code requirements governing equipment safety, except that the enforcing agency may accept alternatives which do not create a safety hazard.
8-902.5 Combustion air.
8-902.5.1 All fuel-burning appliances and equipment shall be provided a sufficient supply of air for proper fuel combustion, ventilation and draft hood dilution.
8-902.5.2 The enforcing agency may require operational tests for combustion air systems which do not comply with applicable requirements of the regular code.
8-902.6 Venting of appliances.
8-902.6.1 Every appliance required to be vented shall be connected to an approved venting system. Venting systems shall develop a positive flow adequate to convey all combustion products to the outside atmosphere.
8-902.6.2 Masonry chimneys in structurally sound condition may remain in use for all fuel-burning appliances, provided the flue is evaluated and documentation provided that the masonry and grout are in good condition. Terra cotta chimneys and Type C metallic vents installed in concealed spaces shall not remain in use unless otherwise mitigated and approved on a case-by-case basis.
8-902.6.3 The enforcing agency may require operational tests for venting systems which do not comply with applicable requirements of the regular code.
8-902.7 Ducts.
8-902.7.1 New ducts shall be constructed and installed in accordance with applicable requirements of the regular code.
8-902.7.2 Existing duct systems which do not comply with applicable requirements of the regular code and do not, in the opinion of the enforcing agency, constitute a safety or health hazard may remain in use.
8-902.8 Ventilating systems.
2025 CALIFORNIA HISTORICAL BUILDING CODE 19
CHBC § 8-903.3 High relevance — show source text
8-903.3 Materials. New nonhistorical materials shall comply with the regular code requirements. The enforcing agency shall accept alternative materials which do not create a safety hazard where their use is necessary to maintain the historical integrity of the building.
8-903.4 Drainage and vent systems. Plumbing fixtures shall be connected to an adequate drainage and vent system. The enforcing agency may require operational tests for drainage and vent systems which do not comply with applicable requirements of the regular code. Vent terminations may be installed in any location which, in the opinion of the enforcing agency, does not create a safety hazard.
8-903.5 Indirect and special wastes. Indirect and special waste systems shall be installed so that no safety hazard is created. Chemical or industrial liquid wastes which may detrimentally affect the sanitary sewer system shall be pretreated to render them safe prior to discharge.
8-903.6 Traps and interceptors. Traps and interceptors shall comply with the regular code requirements except that the enforcing agency shall accept solutions which do not increase the safety hazard. Properly maintained “S” and drum traps may remain in use.
8-903.7 Joints and connections.
8-903.7.1 Joints and connections in new plumbing systems shall comply with applicable requirements of the regular code.
8-903.7.2 Joints and connections in existing or restored systems may be of any type that does not create a safety hazard.
8-903.8 Water distribution. Plumbing fixtures shall be connected to an adequate water distribution system. The enforcing agency may require operational tests for water distribution systems which do not comply with applicable requirements of the regular code. Prohibited (unlawful) connections and cross connections shall not be permitted.
8-903.9 Building sewers and private sewage disposal systems. New building sewers and new private sewage disposal systems shall comply with applicable requirements of the regular code.
20 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
8-903.10 Fuel-gas piping. Fuel-gas piping shall comply with the regular code requirements except that the enforcing agency shall accept solutions which do not increase the safety hazard.
SECTION 8-904 — ELECTRICAL
8-904.1 General. Electrical systems shall comply with the regular code unless otherwise permitted by this code, or approved by the authority having jurisdiction.
8-904.1.1 The provisions of the CHBC shall apply to the acceptance, location, installation, alteration, repair, relocation, replacement or addition of any electrical system or portion thereof, the premise wiring, or equipment fixed in place as related to restoration within or attached to a qualified historical building or property.
8-904.1.2 Existing systems, wiring methods and electrical equipment which do not, in the opinion of the enforcing agency, constitute a safety hazard may remain in use.
8-904.1.3 The enforcing agency may approve any alternative to the CHBC which achieves equivalent safety.
8-904.1.4 Archaic methods that do not appear in present codes may remain and may be extended if, in the opinion of the enforcing agency, they constitute a safe installation.
8-904.2 Wiring methods.
CHBC § 8-902.8.1 Medium relevance — show source text
MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
8-902.8.1 Ventilating systems shall be installed so that no safety hazard is created.
8-902.8.2 Grease hoods and grease hood exhaust systems shall be furnished and installed in accordance with applicable requirements of the regular code. Existing systems which are altered shall comply with the regular code.
8-902.9 Miscellaneous equipment requirements.
8-902.9.1 The following appliances and equipment shall be installed so that no safety hazard is created: warm air furnaces, space heating equipment, vented decorative appliances, floor furnaces, vented wall furnaces, unit heaters, room heaters, absorption units, refrigeration equipment, duct furnaces, infrared radiant heaters, domestic incinerators, miscellaneous heat-producing appliances and water heaters.
8-902.9.2 Storage-type water heaters shall be equipped with a temperature- and pressure-relief valve in accordance with applicable requirements of the regular code.
SECTION 8-903 — PLUMBING
8-903.1 General. Plumbing systems shall comply with the regular code unless otherwise noted.
8-903.1.1 The provisions of the CHBC shall apply to the acceptance, location, installation, alteration, repair, relocation, replacement or addition of any plumbing system or equipment within or attached to a historical building.
8-903.1.2 Existing systems which do not, in the opinion of the enforcing agency, constitute a safety hazard may remain in use.
8-903.1.3 The enforcing agency may approve any alternative to these regulations which achieves reasonably equivalent life safety.
8-903.2 Residential occupancies.
8-903.2.1 Where toilet facilities are provided, alternative sewage disposal methods may be acceptable if approved by the local health department. In hotels, where private facilities are not provided, water closets at the ratio of one for each 15 rooms may be acceptable.
8-903.2.2 Toilet facilities are not required to be on the same floor or in the same building as sleeping rooms. Water-flush toilets may be located in a building immediately adjacent to the sleeping rooms. When alternative sewage disposal methods are utilized, they shall be located a minimum distance from the sleeping rooms or other locations as approved by the local health department.
8-903.2.3 Kitchen sinks shall be provided in all kitchens. The sink and countertop may be of any smooth nonabsorbent finish which can be maintained in a sanitary condition.
8-903.2.4 Hand washing facilities shall be provided for each dwelling unit and each hotel guest room. A basin and pitcher may be acceptable as adequate hand washing facilities.
8-903.2.5 Hot or cold running water is not required for each plumbing fixture, provided a sufficient amount of water is supplied to permit the fixture’s normal operation.
8-903.2.6 Bathtubs and lavatories with filler spouts less than 1 inch (25.4 mm) above the fixture rim may remain in use, provided there is an acceptable overflow below the rim.
8-903.2.7 Original or salvage water closets, urinals and flushometer valves shall be permitted in qualified historical buildings or properties. Historically accurate reproduction, nonlow-consumption water closets, urinals and flushometer valves shall be permitted except where historically accurate fixtures that comply with the regular code are available.
CHBC § 8-706.3 Medium relevance — show source text
8-706.3 Load path. A complete and continuous load path, including connections, from every part or portion of the structure to the ground shall be provided for the required forces. It shall be verified that the structure is adequately tied together to perform as a unit when subjected to earthquake forces.
8-706.4 Parapets. Parapets and exterior decoration shall be investigated for conformance with regular code requirements for anchorage and ability to resist prescribed seismic forces.
An exception to regular code requirements shall be permitted for those parapets and decorations which are judged not to be a hazard to life safety.
8-706.5 Nonstructural features. Nonstructural features of historical structure, such as exterior veneer, cornices and decorations, which might fall and create a life safety hazard in an earthquake, shall be evaluated. Their ability to resist seismic forces shall be verified, or the feature shall be strengthened with improved anchorage when appropriate.
8-706.5.1 Partitions and ceilings of corridors and stairways serving an occupant load of 30 or more shall be investigated to determine their ability to remain in place when the building is subjected to earthquake forces.
8-706.5.2 Seismic forces used to evaluate and improve nonstructural components and their anchorage, where required, shall comply with ASCE 41 or need not exceed 0.75 times the seismic forces prescribed by the requirements of the regular code.
14 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-8 ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
SECTION 8-801 — PURPOSE, INTENT AND SCOPE
8-801.1 Purpose. The purpose of the CHBC is to provide regulations for the use of historical methods and materials of construction that are at variance with regular code requirements or are not otherwise codified, in buildings or structures designated as qualified historical buildings or properties. The CHBC require enforcing agencies to accept any reasonably equivalent alternatives to the regular code when dealing with qualified historical buildings or properties.
8-801.2 Intent. It is the intent of the CHBC to provide for the use of historical methods and materials of construction that are at variance with specific code requirements or are not otherwise codified.
8-801.3 Scope. Any construction type or material that is, or was, part of the historical fabric of a structure is covered by this chapter. Archaic materials and methods of construction present in a historical structure may remain or be reinstalled or be installed with new materials of the same class to match existing conditions.
SECTION 8-802 — GENERAL ENGINEERING APPROACHES
Strength values for archaic materials shall be assigned based upon similar conventional codified materials, or on tests as hereinafter indicated. The archaic materials and methods of construction shall be thoroughly investigated for their details of construction in accordance with Section 8-703. Testing shall be performed when applicable to evaluate existing conditions. The architect or structural engineer in responsible charge of the project shall assign allowable stresses or strength levels to archaic materials. Such assigned strength values shall not be greater than those provided for in the following sections without adequate testing, and shall be subject to the concurrence of the enforcing agency.
SECTION 8-803 — NONSTRUCTURAL ARCHAIC MATERIALS
CHBC § 8-902.5 Medium relevance — show source text
8-902.5 Combustion air.
8-902.5.1 All fuel-burning appliances and equipment shall be provided a sufficient supply of air for proper fuel combustion, ventilation and draft hood dilution.
8-902.5.2 The enforcing agency may require operational tests for combustion air systems which do not comply with applicable requirements of the regular code.
8-902.6 Venting of appliances.
8-902.6.1 Every appliance required to be vented shall be connected to an approved venting system. Venting systems shall develop a positive flow adequate to convey all combustion products to the outside atmosphere.
8-902.6.2 Masonry chimneys in structurally sound condition may remain in use for all fuel-burning appliances, provided the flue is evaluated and documentation provided that the masonry and grout are in good condition. Terra cotta chimneys and Type C metallic vents installed in concealed spaces shall not remain in use unless otherwise mitigated and approved on a case-by-case basis.
8-902.6.3 The enforcing agency may require operational tests for venting systems which do not comply with applicable requirements of the regular code.
8-902.7 Ducts.
8-902.7.1 New ducts shall be constructed and installed in accordance with applicable requirements of the regular code.
8-902.7.2 Existing duct systems which do not comply with applicable requirements of the regular code and do not, in the opinion of the enforcing agency, constitute a safety or health hazard may remain in use.
8-902.8 Ventilating systems.
2025 CALIFORNIA HISTORICAL BUILDING CODE 19
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
8-902.8.1 Ventilating systems shall be installed so that no safety hazard is created.
8-902.8.2 Grease hoods and grease hood exhaust systems shall be furnished and installed in accordance with applicable requirements of the regular code. Existing systems which are altered shall comply with the regular code.
8-902.9 Miscellaneous equipment requirements.
8-902.9.1 The following appliances and equipment shall be installed so that no safety hazard is created: warm air furnaces, space heating equipment, vented decorative appliances, floor furnaces, vented wall furnaces, unit heaters, room heaters, absorption units, refrigeration equipment, duct furnaces, infrared radiant heaters, domestic incinerators, miscellaneous heat-producing appliances and water heaters.
8-902.9.2 Storage-type water heaters shall be equipped with a temperature- and pressure-relief valve in accordance with applicable requirements of the regular code.
SECTION 8-903 — PLUMBING
8-903.1 General. Plumbing systems shall comply with the regular code unless otherwise noted.
8-903.1.1 The provisions of the CHBC shall apply to the acceptance, location, installation, alteration, repair, relocation, replacement or addition of any plumbing system or equipment within or attached to a historical building.
8-903.1.2 Existing systems which do not, in the opinion of the enforcing agency, constitute a safety hazard may remain in use.
8-903.1.3 The enforcing agency may approve any alternative to these regulations which achieves reasonably equivalent life safety.
8-903.2 Residential occupancies.
CHBC § 8-903.9 Medium relevance — show source text
8-903.9 Building sewers and private sewage disposal systems. New building sewers and new private sewage disposal systems shall comply with applicable requirements of the regular code.
20 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
8-903.10 Fuel-gas piping. Fuel-gas piping shall comply with the regular code requirements except that the enforcing agency shall accept solutions which do not increase the safety hazard.
SECTION 8-904 — ELECTRICAL
8-904.1 General. Electrical systems shall comply with the regular code unless otherwise permitted by this code, or approved by the authority having jurisdiction.
8-904.1.1 The provisions of the CHBC shall apply to the acceptance, location, installation, alteration, repair, relocation, replacement or addition of any electrical system or portion thereof, the premise wiring, or equipment fixed in place as related to restoration within or attached to a qualified historical building or property.
8-904.1.2 Existing systems, wiring methods and electrical equipment which do not, in the opinion of the enforcing agency, constitute a safety hazard may remain in use.
8-904.1.3 The enforcing agency may approve any alternative to the CHBC which achieves equivalent safety.
8-904.1.4 Archaic methods that do not appear in present codes may remain and may be extended if, in the opinion of the enforcing agency, they constitute a safe installation.
8-904.2 Wiring methods.
8-904.2.1 Where existing branch circuits do not include an equipment grounding conductor and, in the opinion of the enforcing agency, it is impracticable to connect an equipment grounding conductor to the grounding electrode system, receptacle convenience outlets may remain the nongrounding type.
8-904.2.2 Ground fault circuit interrupter (GFCI) protected receptacles shall be installed where replacements are made at receptacle outlets that are required to be so protected by the regular code in effect at the time of replacement. Metallic face plates shall either be grounded to the grounded metal outlet box or be grounded to the grounding-type device when used with devices supplied by branch circuits without equipment grounding conductors.
8-904.2.3 Grounding-type receptacles shall not be used without a grounding means in an existing receptacle outlet unless GFCI protected. Existing nongrounding receptacles shall be permitted to be replaced with nongrounding or grounding-type receptacles where supplied through a ground fault circuit interrupter.
8-904.2.4 Extensions of existing branch circuits without equipment-grounding conductors shall be permitted to supply grounding-type devices only when the equipment grounding conductor of the new extension is grounded to any accessible point on the grounding electrode system.
8-904.2.5 Receptacle outlet spacing and other related distance requirements shall be waived or modified if determined to be impracticable by the enforcing agency.
CHBC § 8-706.1.3 Medium relevance — show source text
Exceptions:
- Alternative standards may be used on a case-by-case basis when approved by the authority having jurisdiction. It shall be permitted to exceed the strength limitation of 100 psi in Section A108.2 of the CEBC when test data and building configuration supports higher values subject to the approval of the authority having jurisdiction.
- CEBC Section A102.2 shall not apply to Qualified Historical Buildings in Risk Category III buildings and other structures whose primary occupancies are public assembly with an occupancy load greater than 300.
8-706.1.3 All deviations from the detailing provisions of the lateral-force-resisting systems shall be evaluated for stability and the ability to maintain load-carrying capacity at the expected inelastic deformations.
8-706.2 Existing building performance. The seismic resistance may be based upon the ultimate capacity of the structure to perform, giving due consideration to ductility and reserve strength of the lateral-force-resisting system and materials while maintaining a reasonable factor of safety. Broad judgment may be exercised regarding the strength and performance of materials not recognized by regular code requirements. (See Chapter 8-8, Archaic Materials and Methods of Construction.)
8-706.2.1 All structural materials or members that do not comply with detailing and proportioning requirements of the regular code shall be evaluated for potential seismic performance and the consequence of non-compliance. All members that would be reasonably expected to fail and lead to collapse or life threatening injury when subjected to seismic demands shall be judged unacceptable, and appropriate structural strengthening shall be developed.
8-706.3 Load path. A complete and continuous load path, including connections, from every part or portion of the structure to the ground shall be provided for the required forces. It shall be verified that the structure is adequately tied together to perform as a unit when subjected to earthquake forces.
8-706.4 Parapets. Parapets and exterior decoration shall be investigated for conformance with regular code requirements for anchorage and ability to resist prescribed seismic forces.
An exception to regular code requirements shall be permitted for those parapets and decorations which are judged not to be a hazard to life safety.
8-706.5 Nonstructural features. Nonstructural features of historical structure, such as exterior veneer, cornices and decorations, which might fall and create a life safety hazard in an earthquake, shall be evaluated. Their ability to resist seismic forces shall be verified, or the feature shall be strengthened with improved anchorage when appropriate.
8-706.5.1 Partitions and ceilings of corridors and stairways serving an occupant load of 30 or more shall be investigated to determine their ability to remain in place when the building is subjected to earthquake forces.
8-706.5.2 Seismic forces used to evaluate and improve nonstructural components and their anchorage, where required, shall comply with ASCE 41 or need not exceed 0.75 times the seismic forces prescribed by the requirements of the regular code.
14 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-8 ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
SECTION 8-801 — PURPOSE, INTENT AND SCOPE
CHBC § 8-807.3 Medium relevance — show source text
8-807.3 Existing wood framing. Existing wood framing members may be assigned allowable stresses consistent with codes in effect at the time of construction. Existing or new replacement wood framing may be of archaic types originally used if properly researched, such as balloon and single wall. Wood joints such as dovetail and mortise and tenon types may be used structurally, provided they are well made. Lumber selected for use and type need not bear grade marks, and greater or lesser species such as low-level pine and fir, boxwood and indigenous hardwoods and other variations may be used for specific conditions where they were or would have been used.
Wood fasteners such as square or cut nails may be used with a maximum increase of 50 percent over wire nails for shear.
SECTION 8-808 — CONCRETE
8-808.1 Materials. Natural cement concrete, unreinforced rubble concrete and similar materials may be utilized wherever that material is used historically. Concrete of low strength and with less reinforcement than required by the regular code may remain in place. The architect or engineer shall assign appropriate values of strength based on testing of samples of the materials. Bond and development lengths shall be determined based on historical information or tests.
8-808.2 Detailing. The architect or engineer shall carefully evaluate all detailing provisions of the regular code which are not met and shall consider the implications of these variations on the ultimate performance of the structure, giving due consideration to ductility and reserve strength.
16 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
SECTION 8-809 — STEEL AND IRON
The hand-built, untested use of wrought or black iron, the use of cast iron or grey iron, and the myriad of joining methods that are not specifically allowed by code may be used wherever applicable and wherever they have proven their worth under the considerable span of years involved with most qualified historical buildings or structures. Uplift capacity should be evaluated and strengthened where necessary. Fixed conditions or midheight lateral loads on cast iron columns that could cause failure should be taken into account. Existing structural wrought, forged steel or grey iron may be assigned the maximum working stress prevalent at the time of original construction.
SECTION 8-810 — HOLLOW CLAY TILE
The historical performance of hollow clay tile in past earthquakes shall be carefully considered in evaluating walls of hollow clay tile construction. Hollow clay tile bearing walls shall be evaluated and strengthened as appropriate for lateral loads and their ability to maintain support of gravity loads. Suitable protective measures shall be provided to prevent blockage of exit stairways, stairway enclosures, exit ways and public ways as a result of an earthquake.
SECTION 8-811 — VENEERS
8-811.1 Terra cotta and stone. Terra cotta, cast stone and natural stone veneers shall be investigated for the presence of suitable anchorage. Steel anchors shall be investigated for deterioration or corrosion. New or supplemental anchorage shall be provided as appropriate.
8-811.2 Anchorage. Brick veneer with mechanical anchorage at spacings greater than required by the regular code may remain, provided the anchorages have not corroded. Nail strength in withdrawal in wood sheathing may be utilized to its capacity in accordance with code values.
SECTION 8-812 — GLASS AND GLAZING
CHBC § 8-810 Medium relevance — show source text
The hand-built, untested use of wrought or black iron, the use of cast iron or grey iron, and the myriad of joining methods that are not specifically allowed by code may be used wherever applicable and wherever they have proven their worth under the considerable span of years involved with most qualified historical buildings or structures. Uplift capacity should be evaluated and strengthened where necessary. Fixed conditions or midheight lateral loads on cast iron columns that could cause failure should be taken into account. Existing structural wrought, forged steel or grey iron may be assigned the maximum working stress prevalent at the time of original construction.
SECTION 8-810 — HOLLOW CLAY TILE
The historical performance of hollow clay tile in past earthquakes shall be carefully considered in evaluating walls of hollow clay tile construction. Hollow clay tile bearing walls shall be evaluated and strengthened as appropriate for lateral loads and their ability to maintain support of gravity loads. Suitable protective measures shall be provided to prevent blockage of exit stairways, stairway enclosures, exit ways and public ways as a result of an earthquake.
SECTION 8-811 — VENEERS
8-811.1 Terra cotta and stone. Terra cotta, cast stone and natural stone veneers shall be investigated for the presence of suitable anchorage. Steel anchors shall be investigated for deterioration or corrosion. New or supplemental anchorage shall be provided as appropriate.
8-811.2 Anchorage. Brick veneer with mechanical anchorage at spacings greater than required by the regular code may remain, provided the anchorages have not corroded. Nail strength in withdrawal in wood sheathing may be utilized to its capacity in accordance with code values.
SECTION 8-812 — GLASS AND GLAZING
8-812.1 Glazing subject to human impact. Historical glazing material located in areas subject to human impact may be approved subject to the concurrence of the enforcing agency when alternative protective measures are provided. These measures may include, but not be limited to, additional glazing panels, protective film, protective guards or systems, and devices or signs which would provide adequate public safety.
8-812.2 Glazing in fire-rated systems. See Section 8-402.3.
TABLE8-8A—STRENGTH VALUES FOR EXISTING MATERIALS Col2 EXISTING MATERIALS OR CONFIGURATIONS OF MATERIALS1 STRENGTH LEVEL CAPACITY
x14.594 for N/m1. Horizontal diaphragms2
1.1. Roofs with straight sheathing and roofing applied directly to the sheathing
1.2. Roofs with diagonal sheathing and roofing applied directly to the sheathing
1.3. Floors with straight tongue-and-groove sheathing
1.4. Floors with straight sheathing and finished wood flooring with board edges
offset or perpendicular
1.5. Floors with diagonal sheathing and finished300 lbs per foot for seismic shear
750 lbs per foot for seismic shear
300 lbs per foot for seismic shear
1,500 lbs per foot for seismic shear
1,800 lbs per foot for seismic shear2. Crosswalls2,3
2.1. Plaster on wood or metal lath
2.2. Plaster on gypsum lath
2.3. Gypsum wallboard, unblocked edges
2.4.CHBC § 8-102.1.1 Medium relevance — show source text
- State agencies. All state agencies shall apply the provisions of the CHBC in permitting repairs, alterations and additions necessary for the preservation, restoration, rehabilitation, safety, relocation, reconstruction or continued use of qualified historical buildings or properties.
8-102.1.1 Additions, alterations and repairs. It is the intent of the CHBC to allow nonhistorical expansion or addition to a qualified historical building or property, provided nonhistorical additions shall conform to the requirements of the regular code (as defined in Chapter 8-2).
8-102.1.2 Relocation. Relocated qualified historical buildings or properties shall be sited to comply with the regular code or with the solutions listed in the CHBC. Nonhistorical new construction related to relocation shall comply with the regular code. Reconstruction and restoration related to relocation is permitted to comply with the provisions in the CHBC.
8-102.1.3 Change of occupancy. For change of use or occupancy, see Chapter 8-3, Use and Occupancy.
8-102.1.4 Continued use. Qualified historical buildings or properties may have their existing use or occupancy continued if such use or occupancy conformed to the code or to the standards of construction in effect at the time of construction, and such use or occupancy does not constitute a distinct hazard to life safety as defined in the CHBC.
8-102.1.5 Unsafe buildings or properties. When a qualified historical building or property is determined to be unsafe as defined in the regular code, the requirements of the CHBC are applicable to the work necessary to correct the unsafe conditions. Work to remediate the buildings or properties need only address the correction of the unsafe conditions, and it shall not be required to bring the entire qualified historical building or property into compliance with regular code.
8-102.1.6 Additional work. Qualified historical buildings or properties shall not be subject to additional work required by the regular code, regulation or ordinance beyond that required to complete the work undertaken. Certain exceptions for accessibility and for distinct hazards exist by mandate and may require specific action, within the parameters of the CHBC.
SECTION 8-103 — ORGANIZATION AND ENFORCEMENT
8-103.1 Authority. The state or local enforcing agency, pursuant to authority provided under Section 18954 of the Health and Safety Code, shall administer and enforce the provisions of the CHBC in permitting repairs, alterations and additions necessary for the preservation, restoration, reconstruction, rehabilitation, relocation or continued use of a qualified historical building or property.
8-103.2 State enforcement. All state agencies pursuant to authority provided under Section 18954 and Section 18961 of the Health and Safety Code shall administer and enforce the CHBC with respect to qualified historical buildings or properties under their respective jurisdiction.
8-103.3 Liability. Prevailing law regarding immunity of building officials is unaffected by the use and enforcement of the CHBC.
2025 CALIFORNIA HISTORICAL BUILDING CODE 1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ADMINISTRATION
SECTION 8-104 — REVIEW AND APPEALS
8-104.1 State Historical Building Safety Board (SHBSB or Board). In order to provide for interpretation of the provisions of the CHBC and to hear appeals, the SHBSB shall act as an appeal and review body to state and local agencies or any affected party.
**8-104.2 SHBSB review.
CHBC § 1.11. Medium relevance — show source text
Adopting Agency BSC BSC-
CGSFM HCD Col6 Col7 DSA Col9 Col10 OSHPD Col12 Col13 Col14 Col15 Col16 Col17 BSCC DPH AGR DWR CEC CA SL SLC Adopting Agency BSC BSC-
CGSFM 1 2 1/AC AC SS SS/CC 1 1R 2 3 4 5 6 6 6 6 6 6 6 6 6 Adopt Entire Chapter Adopt Entire Chapter as
amended (amended
sections listed below)Adopt only those sections
that are listed belowChapter / Section The state agency does not adopt sections identified with the following symbol: † The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
2025 CALIFORNIA EXISTING BUILDING CODE APPENDIX C-25
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX C-26 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX C—GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUILDINGS
CHAPTER C2 ROOF DECK FASTENING FOR HIGH-WIND AREAS
SECTION C201—GENERAL
[BS] C201.1 Purpose. This chapter provides prescriptive methods for partial structural retrofit of an existing building to increase its resistance to wind loads. It is intended for voluntary use where the basic wind speed, V, is greater than 130 mph (58 m/s) in accordance with Figure 1609.3(2) of the California Building Code and for reference by mitigation programs. The provisions of this chapter do not necessarily satisfy requirements for new construction. Unless specifically cited, the provisions of this chapter do not necessarily satisfy requirements for structural improvements triggered by addition, alteration, repair, change of occupancy, building relocation or other circumstances.
[BS] C201.2 Eligible conditions. The provisions of this chapter are applicable only to buildings that meet either of the following eligibility requirements:
- Buildings assigned to Risk Category I or II in accordance with Table 1604.5 of the California Building Code .
- Buildings within the scope of the California Residential Code .
SECTION C202—ROOF DECK ATTACHMENT FOR WOOD ROOFS
Frequently asked questions
Who decides whether an existing mechanical system is a safety hazard?
The local or state enforcing agency makes that determination under the CHBC; their opinion controls whether a system may remain in use or must be rendered inoperative. § 8-902.1.2, § 8-901.4.
Can an unsafe historic boiler stay in the building if I decommission it?
Yes — an existing system that would be a safety hazard when operational may remain only if it is completely and permanently rendered inoperative, and the inoperative condition itself must not create a hazard. § 8-901.4.
If my ducts don’t meet modern code, do I have to replace them?
Not necessarily. Existing duct systems that do not comply but do not constitute a safety or health hazard may remain in use at the enforcing agency’s discretion (§ 8-902.7.2). Expect required testing or mitigation if needed.
Are there special rules for historic chimneys and vents?
Yes. Masonry chimneys may remain for fuel-burning appliances if structurally sound and the flue is evaluated and documented. Terra cotta chimneys and Type C metallic vents in concealed spaces are restricted and typically require case-by-case mitigation and approval (§ 8-902.6.2).
Can the enforcing agency accept a performance-based alternative instead of bringing equipment to modern code?
Yes. The CHBC explicitly allows the enforcing agency to approve alternatives that achieve equivalent life safety, which is the usual path when historic integrity would be harmed by strict compliance (§ 8-902.1.3).