CHBC · California Historical Building Code
Means of Egress
The CHBC’s Means of Egress chapter sets life‑safety–focused egress requirements for qualified historical buildings and permits case‑by‑case alternatives to preserve historic character.
Last reviewed: July 6, 2026
Overview
This section of the California Historical Building Code (CHBC) establishes minimum means-of-egress rules tailored for qualified historical buildings and properties, while allowing the enforcing agency to accept reasonably equivalent alternatives to regular-code requirements (§8‑501). The chapter is focused on life-safety outcomes rather than strict replication of contemporary dimensions, so historic features may be retained where they do not create a distinct hazard (§8‑501.1; §8‑502) .
Key provisions cover general application and exceptions (§8‑502), emergency escape and rescue openings (§8‑503), and railings/guardrails (§8‑504); the CHBC’s Chapter 8‑5 collects these means-of-egress rules for qualified historical buildings (Chapter 8‑5 table of contents) . The focus is preserving historic fabric while ensuring adequate exits, allowing existing nonconforming doors, corridors, stairs, and approved fire escapes to remain when the enforcing agency determines they do not present a distinct life‑safety hazard (§8‑502.2–.6) .
In this section
Code references
Grounded in the retrieved California Historical Building Code — click a citation to read the verbatim passage:
CHBC § 8-410.3 High relevance — show source text
Buildings with floors above 75 feet, NFPA 13.
When the building is free standing or with property line separation, two floors and 1500 square feet per floor or less, NFPA 13D.
For exterior wall and opening protection. As required by this chapter.
Exception: When the automatic sprinkler systems are used to reach compliance using this code, in three or more occasions, NFPA 13D standard shall be increased to NFPA 13R standard, or NFPA 13R standard shall be increased to a NFPA 13 standard.
8-410.3 Automatic sprinkler systems shall not be used to substitute for or act as an alternate to the required number of exits from any facility. (See Chapter 8-5 for exiting requirements.)
8-410.4 An automatic sprinkler system shall be provided in all detention facilities.
SECTION 8-411 — OTHER TECHNOLOGIES
Fire alarm systems, smoke and heat detection systems, occupant notification and annunciation systems, smoke control systems and fire modeling, timed egress analysis and modeling, as well as other engineering methods and technologies may be accepted by the enforcing agency to address areas of nonconformance.
SECTION 8-412 — HIGH-RISE BUILDINGS
Qualified historical buildings having floors for human occupancy located more than 75 feet above the lowest floor level having building access shall conform to the provisions of the regular code for existing high-rise buildings as amended by the CHBC.
8 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-5 MEANS OF EGRESS
SECTION 8-501 — PURPOSE, INTENT AND SCOPE
8-501.1 Purpose. The purpose of this chapter is to establish minimum means of egress regulations for qualified historical buildings or properties. The CHBC requires enforcing agencies to accept reasonably equivalent alternatives to the means of egress requirements in the regular code.
8-501.2 Intent. The intent of these regulations is to provide an adequate means of egress.
8-501.3 Scope. Every qualified historical building or portion thereof shall be provided with exits as required by the CHBC when required by the provisions of Section 8-102.
SECTION 8-502 — GENERAL
8-502.1 General. The enforcing agency shall grant reasonable exceptions to the specific provisions of applicable egress regulations where such exceptions will not adversely affect life safety.
8-502.2. Existing door openings and corridor widths of less than dimensions required by regular code shall be permitted where there is sufficient width and height for the occupants to pass through the opening or traverse the exit.
8-502.3 Stairs. Existing stairs having risers and treads or width at variance with the regular code are allowed if determined by the enforcing agency to not constitute a distinct hazard. Handrails with nonconforming grip size or extensions are allowed if determined by the enforcing agency to not constitute a distinct hazard.
8-502.4 Main entry doors. The front or main entry doors need not be rehung to swing in the direction of exit travel, provided other means or conditions of exiting, as necessary to serve the total occupant load, are provided.
CHBC § 8-5 High relevance — show source text
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-5 MEANS OF EGRESS
SECTION 8-501 — PURPOSE, INTENT AND SCOPE
8-501.1 Purpose. The purpose of this chapter is to establish minimum means of egress regulations for qualified historical buildings or properties. The CHBC requires enforcing agencies to accept reasonably equivalent alternatives to the means of egress requirements in the regular code.
8-501.2 Intent. The intent of these regulations is to provide an adequate means of egress.
8-501.3 Scope. Every qualified historical building or portion thereof shall be provided with exits as required by the CHBC when required by the provisions of Section 8-102.
SECTION 8-502 — GENERAL
8-502.1 General. The enforcing agency shall grant reasonable exceptions to the specific provisions of applicable egress regulations where such exceptions will not adversely affect life safety.
8-502.2. Existing door openings and corridor widths of less than dimensions required by regular code shall be permitted where there is sufficient width and height for the occupants to pass through the opening or traverse the exit.
8-502.3 Stairs. Existing stairs having risers and treads or width at variance with the regular code are allowed if determined by the enforcing agency to not constitute a distinct hazard. Handrails with nonconforming grip size or extensions are allowed if determined by the enforcing agency to not constitute a distinct hazard.
8-502.4 Main entry doors. The front or main entry doors need not be rehung to swing in the direction of exit travel, provided other means or conditions of exiting, as necessary to serve the total occupant load, are provided.
8-502.5 Existing fire escapes. Existing previously approved fire escapes and fire escape ladders shall be acceptable as one of the required means of egress, provided they extend to the ground and are easily negotiated, adequately signed and in good working order. Access shall be by an opening having a minimum width of 29 inches (737 mm) when open with a sill no more than 30 inches (762 mm) above the adjacent floor, landing or approved step.
8-502.6 New fire escapes and fire escape ladders. New fire escapes and fire escape ladders which comply with this section shall be acceptable as one of the required means of egress. New fire escapes and new fire escape ladders shall comply with the following:
- Access from a corridor shall not be through an intervening room.
- All openings within 10 feet (3048 mm) shall be protected by three-fourths-hour fire assemblies. When located within a recess or vestibule, adjacent enclosure walls shall be of not less than one-hour fire-resistive construction.
- Egress from the building shall be by a clear opening having a minimum dimension of not less than 29 inches (737 mm). Such openings shall be openable from the inside without the use of a key or special knowledge or effort. The sill of an opening giving access shall not be more than 30 inches (737 mm) above the floor, step or landing of the building or balcony.
- Fire escape stairways and balconies shall support the dead load plus a live load of not less than 100 pounds per square foot (4.79 kN/m [2] ) and shall be provided with a top and intermediate handrail on each side. The pitch of the stairway shall not exceed 72 degrees with a minimum width of 18 inches (457 mm).
CHBC § 33.3 High relevance — show source text
Stairway openings in such balconies shall not be less than 22 inches by 44 inches (559 by 1118 mm). The balustrade of each balcony shall not be less than 36 inches (914 mm) high with not more than 9 inches (287 mm) between balusters. 6. Fire escapes shall extend to the roof or provide an approved gooseneck ladder between the top floor landing and the roof when serving buildings four or more stories in height having roofs with less than 4 units vertical in 12 units horizontal (33.3 percent slope). Fire escape ladders shall be designed and connected to the building to withstand a horizontal force of 100 pounds (445 N) placed anywhere on the rung. All ladders shall be at least 15 inches (381 mm) wide, located within 12 inches (305 mm) of the building. Ladder rungs shall be [3] / 4 inch (19.1 mm) in diameter and shall be located 12 inches (305 mm) on center. Openings for roof access ladders through cornices and similar projections shall have minimum dimensions of 30 inches by 33 inches (762 by 838 mm). The length of fire escapes and exit ladder devices shall be limited to that approved by the building official based on products listed by a recognized testing laboratory. 7. The lowest balcony shall not be more than 18 feet (5486 mm) from the ground. Fire escapes shall extend to the ground or be provided with counterbalanced stairs reaching to the ground. 8. Fire escapes shall not take the place of stairways required by the codes under which the building was constructed. 9. Fire escapes shall be kept clear and unobstructed at all times and maintained in good working order.
2025 CALIFORNIA HISTORICAL BUILDING CODE 9
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
SECTION 8-503 — ESCAPE OR RESCUE WINDOWS AND DOORS
Basements in dwelling units and every sleeping room below the fourth floor shall have at least one openable window or door approved for emergency escape which shall open directly into a public street, public way, yard or exit court. Escape or rescue windows or doors shall have a minimum clear area of 3.3 square feet (0.31 m [2] ) and a minimum width or height dimension of 18 inches (457 mm) and be operable from the inside to provide a full, clear opening without the use of special tools.
SECTION 8-504 — RAILINGS AND GUARDRAILS
The height of railings and guard railings and the spacing of balusters may continue in their historical height and spacing unless a distinct hazard has been identified or created by a change in use or occupancy.
10 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-6 ACCESSIBILITY
SECTION 8-601 — PURPOSE, INTENT AND SCOPE
8-601.1 Purpose. The purpose of the CHBC is to provide alternative regulations to facilitate access and use by persons with disabilities to and throughout facilities designated as qualified historical buildings or properties. These regulations require enforcing agencies to accept alternatives to regular code when dealing with qualified historical buildings or properties.
CHBC § 1001.1 High relevance — show source text
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
10 MEANS OF EGRESS
User notes:
About this chapter: Chapter 10 provides the general criteria for designing the means of egress established as the primary method for protection of people in buildings by allowing timely relocation or evacuation of building occupants. Both prescriptive and performance language is utilized in this chapter to provide for a basic approach in the determination of a safe exiting system for all occupancies. It addresses all portions of the egress system (exit access, exits and exit discharge) and includes design requirements as well as provisions regulating individual components. The requirements detail the size, arrangement, number and protection of means of egress components. Functional and operational characteristics that will permit the safe use of components without special knowledge or effort are specified.
The means of egress protection requirements work in coordination with other sections of the code, such as protection of vertical openings (see Chapter 7), interior finish (see Chapter 8), fire suppression and detection systems (see Chapter 9) and numerous others, all having an impact on life safety. Chapter 10 is subdivided into four main sections: general (Sections 1003–1015), exit access (Sections 1016–1021), exit (Sections 1022–1027) and exit discharge (Sections 1028–1029). Special allowances for the unique requirements for assembly spaces (Section 1030) and emergency escape and rescue openings (Section 1031) complete the chapter. Chapter 10 of this code is duplicated in Chapter 10 the California Fire Code; however, the California Fire Code contains one additional section on maintenance of the means of egress system in existing buildings.
SECTION 1001—ADMINISTRATION
1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this chapter shall control the design, construction and arrangement of means of egress components required to provide an approved means of egress from structures and portions thereof.
1001.2 Minimum requirements. It shall be unlawful to alter a building or structure in a manner that will reduce the number of exits or the minimum width or required capacity of the means of egress to less than required by this code.
SECTION 1002—MAINTENANCE AND PLANS
[F] 1002.1 Maintenance. Means of egress shall be maintained in accordance with the California Fire Code .
[F] 1002.2 Fire safety and evacuation plans. Fire safety and evacuation plans shall be provided for all occupancies and buildings where required by the California Fire Code . Such fire safety and evacuation plans shall comply with the applicable provisions of Sections 401.2 and 404 of the California Fire Code .
SECTION 1003—GENERAL MEANS OF EGRESS
1003.1 Applicability. The general requirements specified in Sections 1003 through 1015 shall apply to all three elements of the means of egress system, in addition to those specific requirements for the exit access, the exit and the exit discharge detailed elsewhere in this chapter.
CHBC § 8-503 High relevance — show source text
2025 CALIFORNIA HISTORICAL BUILDING CODE 9
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
SECTION 8-503 — ESCAPE OR RESCUE WINDOWS AND DOORS
Basements in dwelling units and every sleeping room below the fourth floor shall have at least one openable window or door approved for emergency escape which shall open directly into a public street, public way, yard or exit court. Escape or rescue windows or doors shall have a minimum clear area of 3.3 square feet (0.31 m [2] ) and a minimum width or height dimension of 18 inches (457 mm) and be operable from the inside to provide a full, clear opening without the use of special tools.
SECTION 8-504 — RAILINGS AND GUARDRAILS
The height of railings and guard railings and the spacing of balusters may continue in their historical height and spacing unless a distinct hazard has been identified or created by a change in use or occupancy.
10 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-6 ACCESSIBILITY
SECTION 8-601 — PURPOSE, INTENT AND SCOPE
8-601.1 Purpose. The purpose of the CHBC is to provide alternative regulations to facilitate access and use by persons with disabilities to and throughout facilities designated as qualified historical buildings or properties. These regulations require enforcing agencies to accept alternatives to regular code when dealing with qualified historical buildings or properties.
8-601.2 Intent. The intent of this chapter is to preserve the integrity of qualified historical buildings and properties while providing access to and use by persons with disabilities.
8-601.3 Scope. The CHBC shall apply to every qualified historical building or property that is required to provide access to persons with disabilities.
- Provisions of this chapter do not apply to new construction or reconstruction/replicas of historical buildings.
- Where provisions of this chapter apply to alteration of qualified historical buildings or properties, alteration is defined in California Building Code (CBC), Chapter 2.
8-601.4 General application. The provisions in the CHBC apply to local, state and federal governments (Title II entities); alteration of commercial facilities and places of public accommodation (Title III entities); and barrier removal in commercial facilities and places of public accommodation (Title III entities). Except as noted in this chapter.
SECTION 8-602 — BASIC PROVISIONS
8-602.1 Regular code. The regular code for access for people with disabilities (Title 24, Part 2, Vol. 1, Chapter 11B) shall be applied to qualified historical buildings or properties unless strict compliance with the regular code will threaten or destroy the historical significance or character-defining features of the building or property.
8-602.2 Alternative provisions. If the historical significance or character-defining features are threatened, alternative provisions for access may be applied pursuant to this chapter, provided the following conditions are met:
- These provisions shall be applied only on an item-by-item or a case-by-case basis.
- Documentation is provided, including meeting minutes or letters, stating the reasons for the application of the alternative provisions. Such documentation shall be retained in the permanent file of the enforcing agency.
SECTION 8-603 — ALTERNATIVES
CHBC § 1023.9.1 High relevance — show source text
9
(2nd paragraph only)|||||||X|||||||||||||||||| |1023.9.1|||X|||||||||||||||||||||| |1023.11||||||X||||||||||||||||||| |1024.2|||X|||||||||||||||||||||| |1026.4.1|||X|||||||||||||||||||||| |1026.4.2|||X|||||||||||||||||||||| |1026.6|||X|||||||||||||||||||||| |1028.5|||X|||||||||||||||||||||| |1029.3.1|||X|||||||||||||||||||||| |1029.9.1|||X|||||||||||||||||||||| |1030.2|||X|||||||||||||||||||||| |1030.3|||X|||||||||||||||||||||| |1030.6.3.2|||X|||||||||||||||||||||| |1030.9|||X|||||||||||||||||||||| |1031.2|||X|||||||||||||||||||||| |1031.2.1|||X|||||||||||||||||||||| |1031.2.2|||X|||||||||||||||||||||| |1031.2.3|||X||||||||||||||||||||||The state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
2025 CALIFORNIA BUILDING CODE 10-3
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
10-4 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
10 MEANS OF EGRESS
User notes:
About this chapter: Chapter 10 provides the general criteria for designing the means of egress established as the primary method for protection of people in buildings by allowing timely relocation or evacuation of building occupants. Both prescriptive and performance language is utilized in this chapter to provide for a basic approach in the determination of a safe exiting system for all occupancies. It addresses all portions of the egress system (exit access, exits and exit discharge) and includes design requirements as well as provisions regulating individual components. The requirements detail the size, arrangement, number and protection of means of egress components. Functional and operational characteristics that will permit the safe use of components without special knowledge or effort are specified.
The means of egress protection requirements work in coordination with other sections of the code, such as protection of vertical openings (see Chapter 7), interior finish (see Chapter 8), fire suppression and detection systems (see Chapter 9) and numerous others, all having an impact on life safety. Chapter 10 is subdivided into four main sections: general (Sections 1003–1015), exit access (Sections 1016–1021), exit (Sections 1022–1027) and exit discharge (Sections 1028–1029). Special allowances for the unique requirements for assembly spaces (Section 1030) and emergency escape and rescue openings (Section 1031) complete the chapter. Chapter 10 of this code is duplicated in Chapter 10 the California Fire Code; however, the California Fire Code contains one additional section on maintenance of the means of egress system in existing buildings.
SECTION 1001—ADMINISTRATION
CHBC § 8-104.3 High relevance — show source text
ENFORCING AGENCY, Authority Having Jurisdiction, Local Agency with Jurisdiction. An entity with the responsibility for regulating, enforcing, reviewing or otherwise that exerts control of or administration over the process of granting permits, approvals, decisions, variances, appeals for qualified historical buildings or properties.
EXIT LADDER DEVICE. An exit ladder device is a permanently installed, fixed, folding, retractable or hinged ladder intended for use as a means of emergency egress from areas of the second or third stories. Unless approved specifically for a longer length, the ladder shall be limited to 25 feet (7620 mm) in length. Exit ladders are permitted where the area served by the ladder has an occupant load less than 10 persons.
FIRE HAZARD. Any condition which increases or may contribute to an increase in the hazard or menace of fire to a greater degree than customarily recognized by the authority having jurisdiction, or any condition or act which could obstruct, delay, hinder or interfere with the operations of firefighting personnel or the egress of occupants in the event of fire. Section 8-104.3, SHBC appeals, remains applicable.
HISTORICAL FABRIC OR MATERIALS. Original and later-added historically significant construction materials, architectural finishes or elements in a particular pattern or configuration which form a qualified historical property, as determined by the authority having jurisdiction.
HISTORICAL SIGNIFICANCE. Importance for which a property has been evaluated and found to be historical, as determined by the authority having jurisdiction.
IMMINENT THREAT. Any condition within or affecting a qualified historical building or property which, in the opinion of the authority having jurisdiction, would qualify a building or property as dangerous to the extent that the life, health, property or safety of the public, its occupants or those performing necessary repair, stabilization or shoring work are in immediate peril due to conditions affecting the building or property. Potential hazards to persons using, or improvements within, the right-of-way may not be construed to be “imminent threats” solely for that reason if the hazard can be mitigated by shoring, stabilization, barricades or temporary fences.
INTEGRITY. Authenticity of a building or property’s historical identity, evidenced by the survival of physical characteristics that existed during the property’s historical or prehistorical period of significance.
LIFE SAFETY EVALUATION. An evaluation of the life safety hazards of a qualified historical building or property based on procedures similar to those contained in NFPA 909, Standard for the Protection of Cultural Resources, Appendix B, Fire Risk Assessment in Heritage Premises.
LIFE SAFETY HAZARD. See Distinct Hazard.
PERIOD OF SIGNIFICANCE. The period of time when a qualified historical building or property was associated with important events, activities or persons, or attained the characteristics for its listing or registration.
PRESERVATION. The act or process of applying measures necessary to sustain the existing form, integrity and materials of a qualified historical building or property. Work, including preliminary measures to protect and stabilize the property, generally focuses upon the ongoing maintenance and repair of historic materials and features rather than extensive replacement and new construction. New exterior additions are not within the scope of this treatment; however, the limited and sensitive upgrading of mechanical,
2025 CALIFORNIA HISTORICAL BUILDING CODE 3
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
DEFINITIONS
electrical and plumbing systems and other code-related work to make properties functional is appropriate within a preservation project.
CHBC § 1008.3.2 High relevance — show source text
1008.3.2 Illumination level under emergency power. Emergency lighting facilities shall be arranged to provide initial illumination that is not less than an average of 1 footcandle (11 lux) and a minimum at any point of 0.1 footcandle (1 lux) measured along the path of egress at floor level. Illumination levels shall be permitted to decline to 0.6 footcandle (6 lux) average and a minimum at any point of 0.06 footcandle (0.6 lux) at the end of the emergency lighting time duration. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded. In Group I-2 occupancies, failure of a single lamp in a luminaire shall not reduce the illumination level to less than 0.2 footcandle (2.2 lux).
SECTION 1009—ACCESSIBLE MEANS OF EGRESS
1009.1 Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by Section 1006.2 or 1006.3 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress in at least the same number as required by Sections 1006.2 or 1006.3. In addition to the requirements of this chapter, means of egress, which provide access to, or egress from, buildings for persons with disabilities, shall also comply with the requirements of Chap- ter 11A or 11B as applicable.
Exceptions:
- One accessible means of egress is required from an accessible mezzanine level in accordance with Section 1009.3, 1009.4 or 1009.5, and Chapter 11A or 11B, as applicable.
- In assembly areas with ramped aisles or stepped aisles, one accessible means of egress is permitted where the common path of egress travel is accessible and meets the requirements in Section 1030.8 and Chapter 11A or 11B, as applicable.
2025 CALIFORNIA BUILDING CODE 10-15
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
1009.2 Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components:
- Accessible routes complying with Chapter 11A, Sections 1110A.1 and 1119A, or Chapter 11B, Sections 11B-206 and 11B-402, as applicable.
- Interior exit stairways complying with Sections 1009.3 and 1023, and Chapter 11A, Section 1123A, or Chapter 11B, Sections 11B-210 and 11B-504, as applicable.
- Exit access stairways complying with Sections 1009.3 and 1019.3 or 1019.4, and Chapter 11A, Section 1123A, or Chapter 11B, Sections 11B-210 and 11B-504, as applicable.
CHBC § 8-2 High relevance — show source text
2 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-2 DEFINITIONS
SECTION 8-201 — DEFINITIONS
For the purpose of the CHBC, certain terms and phrases, words and their derivatives shall be construed as specified in this chapter. Additional definitions and/or terms may appear in the various other chapters relative to terms or phrases primarily applicable thereto. Any reference to “authority having jurisdiction” does not necessarily preclude the appellate process of Section 8-104.3.
ADDITION. A nonhistorical extension or increase in floor area or height of a building or property.
ALTERATION. A modification to a qualified historical building or property that affects the usability of the building or property, or part thereof. Alterations include, but are not limited to, remodeling, renovation, rehabilitation, reconstruction, historical restoration, changes or rearrangement of the structural parts or elements, and changes or rearrangements in the plan configuration of walls and full-height partitions.
BUILDING STANDARD. Any guideline, regulation or code that may be applied to a qualified historical building or property.
CHARACTER-DEFINING FEATURE. Those visual aspects and physical elements that comprise the appearance of a historical building or property, and that are significant to its historical, architectural and cultural values, including the overall shape of the historical building or property, its materials, craftsmanship, decorative details, interior spaces and features, as well as the various aspects of its site and environment.
CULTURAL RESOURCE. Building, site, property, object or district evaluated as having significance in prehistory or history.
DISTINCT HAZARD. Any clear and evident condition that exists as an immediate danger to the safety of the occupants or public right of way. Conditions that do not meet the requirements of current regular codes and ordinances do not, of themselves, constitute a distinct hazard. Section 8-104.3, SHBC appeals, remains applicable.
ENFORCING AGENCY, Authority Having Jurisdiction, Local Agency with Jurisdiction. An entity with the responsibility for regulating, enforcing, reviewing or otherwise that exerts control of or administration over the process of granting permits, approvals, decisions, variances, appeals for qualified historical buildings or properties.
EXIT LADDER DEVICE. An exit ladder device is a permanently installed, fixed, folding, retractable or hinged ladder intended for use as a means of emergency egress from areas of the second or third stories. Unless approved specifically for a longer length, the ladder shall be limited to 25 feet (7620 mm) in length. Exit ladders are permitted where the area served by the ladder has an occupant load less than 10 persons.
FIRE HAZARD. Any condition which increases or may contribute to an increase in the hazard or menace of fire to a greater degree than customarily recognized by the authority having jurisdiction, or any condition or act which could obstruct, delay, hinder or interfere with the operations of firefighting personnel or the egress of occupants in the event of fire. Section 8-104.3, SHBC appeals, remains applicable.
HISTORICAL FABRIC OR MATERIALS. Original and later-added historically significant construction materials, architectural finishes or elements in a particular pattern or configuration which form a qualified historical property, as determined by the authority having jurisdiction.
HISTORICAL SIGNIFICANCE. Importance for which a property has been evaluated and found to be historical, as determined by the authority having jurisdiction.
CHBC § 1004.9 High relevance — show source text
[BE] 1004.9 Posting of occupant load. Every room or space which is used for assembly, classroom, dining, drinking or similar purposes having an occupant load of 50 or more that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space, for the intended configurations. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or the owner’s authorized agent.
SECTION 1005—MEANS OF EGRESS SIZING
[BE] 1005.1 General. All portions of the means of egress system shall be sized in accordance with this section.
Exception: Aisles and aisle accessways in rooms or spaces used for assembly purposes complying with Section 1030.
[BE] 1005.2 Minimum width based on component. The minimum width, in inches (mm), of any means of egress components shall be not less than that specified for such component, elsewhere in this code.
[BE] 1005.3 Required capacity based on occupant load. The required capacity, in inches (mm), of the means of egress for any room, area, space or story shall be not less than that determined in accordance with Sections 1005.3.1 and 1005.3.2.
[BE] 1005.3.1 Stairways. The capacity, in inches, of means of egress stairways shall be calculated by multiplying the occupant load served by such stairways by a means of egress capacity factor of 0.3 inch (7.6 mm) per occupant. Where stairways serve more than one story, only the occupant load of each story considered individually shall be used in calculating the required capacity of the stairways serving that story. Exceptions:
For other than Group H and I-2 occupancies, the capacity, in inches, of means of egress stairways shall be calculated by multiplying the occupant load served by such stairways by a means of egress capacity factor of 0.2 inch (5.1 mm) per occupant in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 and an emergency voice/alarm communication system in accordance with Section 907.5.2.2.
Facilities with smoke-protected assembly seating shall be permitted to use the capacity factors in Table 1030.6.2 indicated for stepped aisles for exit access or exit stairways where the entire path for means of egress from the seating to the exit discharge is provided with a smoke control system complying with Section 909.
10-10 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
- Facilities with open-air assembly seating shall be permitted to the capacity factors in Section 1030.6.3 indicated for stepped aisles for exit access or exit stairways where the entire path for means of egress from the seating to the exit discharge is open to the outdoors.
4. For Group H-1, H-2, H-3 and H-4 occupancies, the total width of means of egress in inches (mm) shall not be less than the total occupant load served by the means of egress multiplied by 0.7 inches (7.62 mm) per occupant.
CHBC § 2.25 High relevance — show source text
00|2.25|0.70|DR|3.70|1.05|DR|DR| |Minimum 33
mil steel
furring or
minimum
1x wood
furringc|33 mil cold-
formed steel
stud|#10 screw|Steel thick-
ness plus 3
threads|16|3.85|1.45|DR|DR|3.40|DR|DR|DR| |Minimum 33
mil steel
furring or
minimum
1x wood
furringc|33 mil cold-
formed steel
stud|#10 screw|Steel thick-
ness plus 3
threads|24|3.40|DR|DR|DR|2.70|DR|DR|DR| |Minimum 33
mil steel
furring or
minimum
1x wood
furringc|43 mil or
thicker cold-
formed steel
stud|#8 Screw|Steel thick-
ness plus 3
threads|12|3.00|1.80|DR|DR|3.00|0.65|DR|DR| |Minimum 33
mil steel
furring or
minimum
1x wood
furringc|43 mil or
thicker cold-
formed steel
stud|#8 Screw|Steel thick-
ness plus 3
threads|16|3.00|1.00|DR|DR|2.85|DR|DR|DR| |Minimum 33
mil steel
furring or
minimum
1x wood
furringc|43 mil or
thicker cold-
formed steel
stud|#8 Screw|Steel thick-
ness plus 3
threads|24|2.85|DR|DR|DR|2.20|DR|DR|DR| |Minimum 33
mil steel
furring or
minimum
1x wood
furringc|43 mil or
thicker cold-
formed steel
stud|#10 screw|Steel thick-
ness plus 3
threads|12|4.00|3.85|2.80|1.80|4.00|3.05|1.50|DR| |Minimum 33
mil steel
furring or
minimum
1x wood
furringc|43 mil or
thicker cold-
formed steel
stud|#10 screw|Steel thick-
ness plus 3
threads|16|4.00|3.30|1.95|0.60|4.00|2.25|DR|DR| |Minimum 33
mil steel
furring or
minimum
1x wood
furringc|43 mil or
thicker cold-
formed steel
stud|#10 screw|Steel thick-
ness plus 3
threads|24|4.00|2.25|DR|DR|4.00|0.65|DR|DR| |For SI: 1 inch = 25.4 mm, 1 pound per square foot (psf) = 0.0479 kPa, 1 pound per square inch = 0.00689 MPa.
DR = Design Required, o.c. = on center.
a. Wood furring shall be spruce-pine-fir or any softwood species with a specific gravity of 0.42 or greater.CHBC § 8-408 High relevance — show source text
8-408 Roof Covering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 8-409 Fire Alarm Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 8-410 Automatic Sprinkler Systems. . . . . . . . . . . . . . . . . . . . . 8 8-411 Other Technologies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 8-412 High-rise Buildings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
CHAPTER 8-5 MEANS OF EGRESS . . . . . . . . . . . . . . . . . . . . . . 9
Section
8-501 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . . 9 8-502 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
8-503 Escape or Rescue Windows and Doors. . . . . . . . . . . . 10 8-504 Railings and Guardrails . . . . . . . . . . . . . . . . . . . . . . . . . 10
CHAPTER 8-6 ACCESSIBILITY . . . . . . . . . . . . . . . . . . . . . . . . 11
Section
8-601 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 11
8-602 Basic Provisions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8-603 Alternatives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8-604 Equivalent Facilitation. . . . . . . . . . . . . . . . . . . . . . . . . . 12
CHAPTER 8-7 STRUCTURAL REGULATIONS. . . . . . . . . . . . . 13
Section
8-701 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 13 8-702 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8-703 Structural Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8-704 Nonhistorical Additions and
Nonhistorical Alterations . . . . . . . . . . . . . . . . . . . . . . . 13
Frequently asked questions
Can the CHBC waive modern egress dimensions for historic stairs and doors?
Yes. The CHBC permits existing door openings, corridor widths and stairs that differ from regular‑code dimensions to remain when the enforcing agency determines they do not constitute a distinct hazard (§8‑502.2–.3) .
Are existing fire escapes acceptable as means of egress under the CHBC?
Existing, previously approved fire escapes and ladders may be accepted as one required means of egress provided they extend to the ground, are accessible, in good working order and meet the access/opening requirements in §8‑502.5; new fire escapes have additional criteria in §8‑502.6 .
Where do I look in the CHBC for escape windows and guardrail rules?
Emergency escape/rescue openings are addressed at §8‑503; railing and guardrail historic‑feature allowances are at §8‑504 — both are part of CHBC Chapter 8‑5 Means of Egress (see the chapter index) .