CHBC · California Historical Building Code
Archaic Materials and Methods of Construction
The CHBC chapter on Archaic Materials and Methods of Construction lets qualified historical buildings retain or use historic materials and techniques by applying a documented, engineering‑based approach (structural survey, assigned strengths, testing, and material‑specific rules) to balance preservation and safety.
Last reviewed: July 6, 2026
Overview
This part of the California Historical Building Code (CHBC) provides rules for using, retaining, repairing, or reinstituting historical (archaic) materials and construction methods in qualified historical buildings and properties. It exists so that preservation-compatible materials and techniques—even when they differ from the regular code—can be accepted when reasonably equivalent alternatives are shown, and to allow in-kind repairs subject to conditions in the CHBC (see §8‑801 and §8‑105.1) .
The CHBC treats archaic materials with an engineering approach: existing conditions must be documented by a structural survey, allowable strengths are assigned by the project architect or engineer, and testing is used where appropriate to set design values and mitigation measures (see §8‑802 and the structural survey requirements of §8‑703) . That approach lets historic fabric—masonry, adobe, wood lath and plaster, early concretes, ironwork, hollow clay tile, veneers, glazing and the like—remain or be repaired in a way that balances safety and preservation.
Key sections cover purpose and scope (§8‑801), general engineering approaches (§8‑802), and material‑specific provisions grouped in §8‑804 through §8‑812; for example, masonry rules and testing are in §8‑805, adobe requirements (including height‑to‑thickness, bond beams and shear values) are in §8‑806, and wood/lath/plaster provisions appear in §8‑807 .
In this section
Code references
Grounded in the retrieved California Historical Building Code — click a citation to read the verbatim passage:
CHBC § 8-706.3 High relevance — show source text
8-706.3 Load path. A complete and continuous load path, including connections, from every part or portion of the structure to the ground shall be provided for the required forces. It shall be verified that the structure is adequately tied together to perform as a unit when subjected to earthquake forces.
8-706.4 Parapets. Parapets and exterior decoration shall be investigated for conformance with regular code requirements for anchorage and ability to resist prescribed seismic forces.
An exception to regular code requirements shall be permitted for those parapets and decorations which are judged not to be a hazard to life safety.
8-706.5 Nonstructural features. Nonstructural features of historical structure, such as exterior veneer, cornices and decorations, which might fall and create a life safety hazard in an earthquake, shall be evaluated. Their ability to resist seismic forces shall be verified, or the feature shall be strengthened with improved anchorage when appropriate.
8-706.5.1 Partitions and ceilings of corridors and stairways serving an occupant load of 30 or more shall be investigated to determine their ability to remain in place when the building is subjected to earthquake forces.
8-706.5.2 Seismic forces used to evaluate and improve nonstructural components and their anchorage, where required, shall comply with ASCE 41 or need not exceed 0.75 times the seismic forces prescribed by the requirements of the regular code.
14 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-8 ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
SECTION 8-801 — PURPOSE, INTENT AND SCOPE
8-801.1 Purpose. The purpose of the CHBC is to provide regulations for the use of historical methods and materials of construction that are at variance with regular code requirements or are not otherwise codified, in buildings or structures designated as qualified historical buildings or properties. The CHBC require enforcing agencies to accept any reasonably equivalent alternatives to the regular code when dealing with qualified historical buildings or properties.
8-801.2 Intent. It is the intent of the CHBC to provide for the use of historical methods and materials of construction that are at variance with specific code requirements or are not otherwise codified.
8-801.3 Scope. Any construction type or material that is, or was, part of the historical fabric of a structure is covered by this chapter. Archaic materials and methods of construction present in a historical structure may remain or be reinstalled or be installed with new materials of the same class to match existing conditions.
SECTION 8-802 — GENERAL ENGINEERING APPROACHES
Strength values for archaic materials shall be assigned based upon similar conventional codified materials, or on tests as hereinafter indicated. The archaic materials and methods of construction shall be thoroughly investigated for their details of construction in accordance with Section 8-703. Testing shall be performed when applicable to evaluate existing conditions. The architect or structural engineer in responsible charge of the project shall assign allowable stresses or strength levels to archaic materials. Such assigned strength values shall not be greater than those provided for in the following sections without adequate testing, and shall be subject to the concurrence of the enforcing agency.
SECTION 8-803 — NONSTRUCTURAL ARCHAIC MATERIALS
CHBC § 8-8 High relevance — show source text
CHAPTER 8-8 ARCHAIC MATERIALS AND METHODS OF
CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . 15
Section
8-801 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 15 8-802 General Engineering Approaches. . . . . . . . . . . . . . . . . 15 8-803 Nonstructural Archaic Materials. . . . . . . . . . . . . . . . . . 15
8-804 Allowable Conditions for Specific Materials . . . . . . . 15 8-805 Masonry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 8-806 Adobe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8-807 Wood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8-808 Concrete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8-809 Steel and Iron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8-810 Hollow Clay Tile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8-811 Veneers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8-812 Glass and Glazing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
CHAPTER 8-9 MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . 19
Section
8-901 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 19 8-902 Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8-903 Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 8-904 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
CHAPTER 8-10 QUALIFIED HISTORICAL DISTRICTS,
SITES AND OPEN SPACES . . . . . . . . . . . . . . . 23
Section
CHBC § 8-801 High relevance — show source text
SECTION 8-801 — PURPOSE, INTENT AND SCOPE
8-801.1 Purpose. The purpose of the CHBC is to provide regulations for the use of historical methods and materials of construction that are at variance with regular code requirements or are not otherwise codified, in buildings or structures designated as qualified historical buildings or properties. The CHBC require enforcing agencies to accept any reasonably equivalent alternatives to the regular code when dealing with qualified historical buildings or properties.
8-801.2 Intent. It is the intent of the CHBC to provide for the use of historical methods and materials of construction that are at variance with specific code requirements or are not otherwise codified.
8-801.3 Scope. Any construction type or material that is, or was, part of the historical fabric of a structure is covered by this chapter. Archaic materials and methods of construction present in a historical structure may remain or be reinstalled or be installed with new materials of the same class to match existing conditions.
SECTION 8-802 — GENERAL ENGINEERING APPROACHES
Strength values for archaic materials shall be assigned based upon similar conventional codified materials, or on tests as hereinafter indicated. The archaic materials and methods of construction shall be thoroughly investigated for their details of construction in accordance with Section 8-703. Testing shall be performed when applicable to evaluate existing conditions. The architect or structural engineer in responsible charge of the project shall assign allowable stresses or strength levels to archaic materials. Such assigned strength values shall not be greater than those provided for in the following sections without adequate testing, and shall be subject to the concurrence of the enforcing agency.
SECTION 8-803 — NONSTRUCTURAL ARCHAIC MATERIALS
Where nonstructural historical materials exist in uses which do not meet the requirements of the regular code, their continued use is allowed by this code, provided that any public health and life safety hazards are mitigated subject to the concurrence of the enforcing agency.
SECTION 8-804 — ALLOWABLE CONDITIONS FOR SPECIFIC MATERIALS
Archaic materials which exist and are to remain in qualified historical buildings or structures shall be evaluated for their condition and for loads required by this code. The structural survey required in Section 8-703 of the CHBC shall document existing conditions, reinforcement, anchorage, deterioration and other factors pertinent to establishing allowable stresses, strength levels and adequacy of the archaic materials. The remaining portion of this chapter provides additional specific requirements for commonly encountered archaic materials.
SECTION 8-805 — MASONRY
For adobe, see Section 8-806.
8-805.1 Existing solid masonry. Existing solid masonry walls of any type, except adobe, may be allowed, without testing, a maximum ultimate strength of 9 pounds per square inch (62.1 kPa) in shear where there is a qualifying statement by the architect or engineer that an inspection has been made, that mortar joints are filled and that both brick and mortar are reasonably good. The shear stress above applies to unreinforced masonry, except adobe, where the maximum ratio of unsupported height or length to thickness does not exceed 13, and where minimum quality mortar is used or exists. Wall height or length is measured to supporting or resisting elements that are at least twice as stiff as the tributary wall. Stiffness is based on the gross section. Shear stress may be increased by the addition of 10 percent of the axial direct stress due to the weight of the wall directly above.
CHBC § 8-6 High relevance — show source text
CHAPTER 8-6 ACCESSIBILITY . . . . . . . . . . . . . . . . . . . . . . . . 11
Section
8-601 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 11
8-602 Basic Provisions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8-603 Alternatives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8-604 Equivalent Facilitation. . . . . . . . . . . . . . . . . . . . . . . . . . 12
CHAPTER 8-7 STRUCTURAL REGULATIONS. . . . . . . . . . . . . 13
Section
8-701 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 13 8-702 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8-703 Structural Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8-704 Nonhistorical Additions and
Nonhistorical Alterations . . . . . . . . . . . . . . . . . . . . . . . 13
8-705 Structural Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8-706 Lateral Load Regulations. . . . . . . . . . . . . . . . . . . . . . . . 14
CHAPTER 8-8 ARCHAIC MATERIALS AND METHODS OF
CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . 15
Section
8-801 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 15 8-802 General Engineering Approaches. . . . . . . . . . . . . . . . . 15 8-803 Nonstructural Archaic Materials. . . . . . . . . . . . . . . . . . 15
8-804 Allowable Conditions for Specific Materials . . . . . . . 15 8-805 Masonry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 8-806 Adobe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8-807 Wood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8-808 Concrete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
CHBC § 8-804 High relevance — show source text
SECTION 8-804 — ALLOWABLE CONDITIONS FOR SPECIFIC MATERIALS
Archaic materials which exist and are to remain in qualified historical buildings or structures shall be evaluated for their condition and for loads required by this code. The structural survey required in Section 8-703 of the CHBC shall document existing conditions, reinforcement, anchorage, deterioration and other factors pertinent to establishing allowable stresses, strength levels and adequacy of the archaic materials. The remaining portion of this chapter provides additional specific requirements for commonly encountered archaic materials.
SECTION 8-805 — MASONRY
For adobe, see Section 8-806.
8-805.1 Existing solid masonry. Existing solid masonry walls of any type, except adobe, may be allowed, without testing, a maximum ultimate strength of 9 pounds per square inch (62.1 kPa) in shear where there is a qualifying statement by the architect or engineer that an inspection has been made, that mortar joints are filled and that both brick and mortar are reasonably good. The shear stress above applies to unreinforced masonry, except adobe, where the maximum ratio of unsupported height or length to thickness does not exceed 13, and where minimum quality mortar is used or exists. Wall height or length is measured to supporting or resisting elements that are at least twice as stiff as the tributary wall. Stiffness is based on the gross section. Shear stress may be increased by the addition of 10 percent of the axial direct stress due to the weight of the wall directly above. Higher-quality mortar may provide a greater shear value and shall be tested in accordance with Appendix A, Chapter A1 of the California Existing Building Code (CEBC) 2010 edition, and as modified by the CHBC.
8-805.2 Stone masonry.
8-805.2.1 Solid-backed stone masonry. Stone masonry solidly backed with brick masonry shall be treated as solid brick masonry as described in Section 8-805.1 and in the 2009 International Existing Building Code [®] (IEBC [®] ), provided representative testing and inspection verifies solid collar joints between stone and brick and that a reasonable number of stones lap with the brick wythes as headers or that steel anchors are present. Solid stone masonry where the wythes of stone effectively overlap to provide the equivalent header courses may also be treated as solid brick masonry.
8-805.2.2 Independent wythe stone masonry. Stone masonry with independent face wythes may be treated as solid brick masonry as described in Section 8-805.1 and the CEBC, provided representative testing and inspection verify that the core is essentially solid in the masonry wall and that steel ties are epoxied in drilled holes between outer stone wythes at floors, roof and not to exceed 4 feet (1219 mm) on center in each direction, between floors and roof. A reinforcing element shall exist or be provided at or near the top of all stone masonry walls.
2025 CALIFORNIA HISTORICAL BUILDING CODE 15
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
8-805.2.3 Testing of stone masonry. Testing of stone masonry shall be similar to the 2010 CEBC requirements for brick masonry, except that representative stones which are not interlocked shall be pulled outward from the wall and shear area appropriately calculated after the test.
CHBC § 8-806.4 High relevance — show source text
8-806.4 Nonload-bearing adobe. Nonload-bearing adobe partitions and gable end walls shall be evaluated for stability and anchored against out-of-plane failure if necessary.
8-806.5 Bond beam. Where provided, a bond beam or equivalent structural element shall be located at the top of all adobe walls, and at the second floor for two-story buildings or structures. The size and configuration of the structural element shall be sufficient to provide an effective brace for the wall, to tie the building together and to connect the wall to the floor or roof.
8-806.6 Repair or reconstruction. Repair or reconstruction of wall area may utilize unstabilized brick or adobe masonry designed to be compatible with the constituents of the existing adobe materials.
8-806.7 Shear values. Existing adobe may be allowed a maximum strength level of 12 pounds per square inch (82.7 kPa) for shear.
8-806.8 Mortar. Mortar may be of the same soil composition as that used in the existing wall, or in new walls as necessary to be compatible with the adobe brick.
SECTION 8-807 — WOOD
8-807.1 Existing wood diaphragms or walls. Existing wood diaphragms or walls of straight or diagonal sheathing shall be assigned shear resistance values appropriate with the fasteners and materials functioning in conjunction with the sheathing. The structural survey shall determine fastener details and spacings and verify a load path through floor construction. Shear values of Tables 8-8-A and 8-8-B.
8-807.2 Wood lath and plaster. Wood lath and plaster walls and ceilings may be utilized using the shear values referenced in Section 8-807.1.
8-807.3 Existing wood framing. Existing wood framing members may be assigned allowable stresses consistent with codes in effect at the time of construction. Existing or new replacement wood framing may be of archaic types originally used if properly researched, such as balloon and single wall. Wood joints such as dovetail and mortise and tenon types may be used structurally, provided they are well made. Lumber selected for use and type need not bear grade marks, and greater or lesser species such as low-level pine and fir, boxwood and indigenous hardwoods and other variations may be used for specific conditions where they were or would have been used.
Wood fasteners such as square or cut nails may be used with a maximum increase of 50 percent over wire nails for shear.
SECTION 8-808 — CONCRETE
8-808.1 Materials. Natural cement concrete, unreinforced rubble concrete and similar materials may be utilized wherever that material is used historically. Concrete of low strength and with less reinforcement than required by the regular code may remain in place. The architect or engineer shall assign appropriate values of strength based on testing of samples of the materials. Bond and development lengths shall be determined based on historical information or tests.
8-808.2 Detailing. The architect or engineer shall carefully evaluate all detailing provisions of the regular code which are not met and shall consider the implications of these variations on the ultimate performance of the structure, giving due consideration to ductility and reserve strength.
16 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
SECTION 8-809 — STEEL AND IRON
CHBC § 8-807.3 High relevance — show source text
8-807.3 Existing wood framing. Existing wood framing members may be assigned allowable stresses consistent with codes in effect at the time of construction. Existing or new replacement wood framing may be of archaic types originally used if properly researched, such as balloon and single wall. Wood joints such as dovetail and mortise and tenon types may be used structurally, provided they are well made. Lumber selected for use and type need not bear grade marks, and greater or lesser species such as low-level pine and fir, boxwood and indigenous hardwoods and other variations may be used for specific conditions where they were or would have been used.
Wood fasteners such as square or cut nails may be used with a maximum increase of 50 percent over wire nails for shear.
SECTION 8-808 — CONCRETE
8-808.1 Materials. Natural cement concrete, unreinforced rubble concrete and similar materials may be utilized wherever that material is used historically. Concrete of low strength and with less reinforcement than required by the regular code may remain in place. The architect or engineer shall assign appropriate values of strength based on testing of samples of the materials. Bond and development lengths shall be determined based on historical information or tests.
8-808.2 Detailing. The architect or engineer shall carefully evaluate all detailing provisions of the regular code which are not met and shall consider the implications of these variations on the ultimate performance of the structure, giving due consideration to ductility and reserve strength.
16 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
SECTION 8-809 — STEEL AND IRON
The hand-built, untested use of wrought or black iron, the use of cast iron or grey iron, and the myriad of joining methods that are not specifically allowed by code may be used wherever applicable and wherever they have proven their worth under the considerable span of years involved with most qualified historical buildings or structures. Uplift capacity should be evaluated and strengthened where necessary. Fixed conditions or midheight lateral loads on cast iron columns that could cause failure should be taken into account. Existing structural wrought, forged steel or grey iron may be assigned the maximum working stress prevalent at the time of original construction.
SECTION 8-810 — HOLLOW CLAY TILE
The historical performance of hollow clay tile in past earthquakes shall be carefully considered in evaluating walls of hollow clay tile construction. Hollow clay tile bearing walls shall be evaluated and strengthened as appropriate for lateral loads and their ability to maintain support of gravity loads. Suitable protective measures shall be provided to prevent blockage of exit stairways, stairway enclosures, exit ways and public ways as a result of an earthquake.
SECTION 8-811 — VENEERS
8-811.1 Terra cotta and stone. Terra cotta, cast stone and natural stone veneers shall be investigated for the presence of suitable anchorage. Steel anchors shall be investigated for deterioration or corrosion. New or supplemental anchorage shall be provided as appropriate.
8-811.2 Anchorage. Brick veneer with mechanical anchorage at spacings greater than required by the regular code may remain, provided the anchorages have not corroded. Nail strength in withdrawal in wood sheathing may be utilized to its capacity in accordance with code values.
SECTION 8-812 — GLASS AND GLAZING
CHBC § 8-104.4 High relevance — show source text
8-104.4 Local agency fees. Local agencies, when actively involved in the appeal, may also charge affected persons reasonable fees not to exceed the cost of obtaining reviews and appeals from the Board.
SECTION 8-105 — CONSTRUCTION METHODS AND MATERIALS
8-105.1 Repairs. Repairs to any portion of a qualified historical building or property may be made in-kind with historical materials and the use of original or existing historical methods of construction, subject to conditions of the CHBC. (See Chapter 8-8.)
8-105.2 Solutions to the California Historical Building Code . Solutions provided in the CHBC, or any other acceptable regulation or methodology of design or construction and used in whole or in part, with the regular code, or with any combination of the regular code and the CHBC, shall be allowed. The CHBC does not preclude the use of any proposed alternative or method of design or construction not specifically prescribed or otherwise allowed by these regulations. Any alternative may be submitted for evaluation to the appropriate enforcing agency for review and acceptance. The enforcing agency may request that sufficient evidence or proof be submitted to substantiate any claims that may be made regarding such solutions. Any alternative offered in lieu of that prescribed or allowed in the CHBC shall be reasonably equivalent in quality, strength, effectiveness, durability and safety to that of the CHBC.
SECTION 8-106 — SHBSB RULINGS
8-106.1 General. Rulings of the SHBSB (i.e., formal appeals, case decisions, code interpretations and administrative resolutions, etc.) that are issues of statewide application are required to be submitted to the California Building Standards Commission in printed form. These rulings may be used to provide guidance for similar cases or issues.
2 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-2 DEFINITIONS
SECTION 8-201 — DEFINITIONS
For the purpose of the CHBC, certain terms and phrases, words and their derivatives shall be construed as specified in this chapter. Additional definitions and/or terms may appear in the various other chapters relative to terms or phrases primarily applicable thereto. Any reference to “authority having jurisdiction” does not necessarily preclude the appellate process of Section 8-104.3.
ADDITION. A nonhistorical extension or increase in floor area or height of a building or property.
ALTERATION. A modification to a qualified historical building or property that affects the usability of the building or property, or part thereof. Alterations include, but are not limited to, remodeling, renovation, rehabilitation, reconstruction, historical restoration, changes or rearrangement of the structural parts or elements, and changes or rearrangements in the plan configuration of walls and full-height partitions.
BUILDING STANDARD. Any guideline, regulation or code that may be applied to a qualified historical building or property.
CHARACTER-DEFINING FEATURE. Those visual aspects and physical elements that comprise the appearance of a historical building or property, and that are significant to its historical, architectural and cultural values, including the overall shape of the historical building or property, its materials, craftsmanship, decorative details, interior spaces and features, as well as the various aspects of its site and environment.
CULTURAL RESOURCE. Building, site, property, object or district evaluated as having significance in prehistory or history.
CHBC § 8-1 High relevance — show source text
CONTENTS
CHAPTER 8-1 ADMINISTRATION . . . . . . . . . . . . . . . . . . . . . . . 1
Section
8-101 Title, Purpose and Intent. . . . . . . . . . . . . . . . . . . . . . . . . 1 8-102 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 8-103 Organization and Enforcement . . . . . . . . . . . . . . . . . . . 1 8-104 Review and Appeals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 8-105 Construction Methods and Materials . . . . . . . . . . . . . . 2
8-106 SHBSB Rulings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
CHAPTER 8-2 DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Section
8-201 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
CHAPTER 8-3 USE AND OCCUPANCY . . . . . . . . . . . . . . . . . . . 5
Section
8-301 Purpose and Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 8-302 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
8-303 Residential Occupancies. . . . . . . . . . . . . . . . . . . . . . . . . 5
CHAPTER 8-4 FIRE PROTECTION. . . . . . . . . . . . . . . . . . . . . . . 7
Section
8-401 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . . 7
8-402 Fire-resistive Construction . . . . . . . . . . . . . . . . . . . . . . . 7
8-403 Interior Finish Materials. . . . . . . . . . . . . . . . . . . . . . . . . . 7
8-404 Wood Lath and Plaster. . . . . . . . . . . . . . . . . . . . . . . . . . . 7
8-405 Occupancy Separation . . . . . . . . . . . . . . . . . . . . . . . . . . 7 8-406 Maximum Floor Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
CHBC § 8-706.1.3 High relevance — show source text
Exceptions:
- Alternative standards may be used on a case-by-case basis when approved by the authority having jurisdiction. It shall be permitted to exceed the strength limitation of 100 psi in Section A108.2 of the CEBC when test data and building configuration supports higher values subject to the approval of the authority having jurisdiction.
- CEBC Section A102.2 shall not apply to Qualified Historical Buildings in Risk Category III buildings and other structures whose primary occupancies are public assembly with an occupancy load greater than 300.
8-706.1.3 All deviations from the detailing provisions of the lateral-force-resisting systems shall be evaluated for stability and the ability to maintain load-carrying capacity at the expected inelastic deformations.
8-706.2 Existing building performance. The seismic resistance may be based upon the ultimate capacity of the structure to perform, giving due consideration to ductility and reserve strength of the lateral-force-resisting system and materials while maintaining a reasonable factor of safety. Broad judgment may be exercised regarding the strength and performance of materials not recognized by regular code requirements. (See Chapter 8-8, Archaic Materials and Methods of Construction.)
8-706.2.1 All structural materials or members that do not comply with detailing and proportioning requirements of the regular code shall be evaluated for potential seismic performance and the consequence of non-compliance. All members that would be reasonably expected to fail and lead to collapse or life threatening injury when subjected to seismic demands shall be judged unacceptable, and appropriate structural strengthening shall be developed.
8-706.3 Load path. A complete and continuous load path, including connections, from every part or portion of the structure to the ground shall be provided for the required forces. It shall be verified that the structure is adequately tied together to perform as a unit when subjected to earthquake forces.
8-706.4 Parapets. Parapets and exterior decoration shall be investigated for conformance with regular code requirements for anchorage and ability to resist prescribed seismic forces.
An exception to regular code requirements shall be permitted for those parapets and decorations which are judged not to be a hazard to life safety.
8-706.5 Nonstructural features. Nonstructural features of historical structure, such as exterior veneer, cornices and decorations, which might fall and create a life safety hazard in an earthquake, shall be evaluated. Their ability to resist seismic forces shall be verified, or the feature shall be strengthened with improved anchorage when appropriate.
8-706.5.1 Partitions and ceilings of corridors and stairways serving an occupant load of 30 or more shall be investigated to determine their ability to remain in place when the building is subjected to earthquake forces.
8-706.5.2 Seismic forces used to evaluate and improve nonstructural components and their anchorage, where required, shall comply with ASCE 41 or need not exceed 0.75 times the seismic forces prescribed by the requirements of the regular code.
14 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-8 ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
SECTION 8-801 — PURPOSE, INTENT AND SCOPE
CHBC § 8-805.3 Medium relevance — show source text
8-805.3 Reconstructed walls. Totally reconstructed walls utilizing original brick or masonry, constructed similar to original, shall be constructed in accordance with the regular code. Repairs or infills may be constructed in a similar manner to the original walls without conforming to the regular code.
SECTION 8-806 — ADOBE
8-806.1 General. Unburned clay masonry may be constructed, reconstructed, stabilized or rehabilitated subject to this chapter. Alternative approaches which provide an equivalent or greater level of safety may be used, subject to the concurrence of the enforcing agency.
8-806.2 Moisture protection. Provisions shall be in place to protect adobe structures from deterioration due to moisture penetration. Adobe shall be maintained in reasonably good condition. Particular attention shall be given to moisture content of adobe walls. Unmaintained walls or ruins shall be evaluated for safety based on their condition and stability. Additional protection measures may be appropriate subject to the concurrence of the enforcing agency.
8-806.3 Height to thickness ratio. Unreinforced new or existing adobe walls meeting these criteria need not be evaluated for out of plane failure. Where existing dimensions do not meet these conditions, additional strengthening measures, such as a bond beam, may be appropriate. Existing sod or rammed earth walls shall be considered similar to the extent these provisions apply.
- One-story adobe load-bearing walls shall not exceed a height-to-thickness ratio of 6.
- Two-story adobe buildings or structures’ height- to-thickness wall ratio shall not exceed 6 at the ground floor and 5 at the second floor, and shall be measured at floor-to-floor height when the second floor and attic ceiling/roof are connected to the wall as described below.
8-806.4 Nonload-bearing adobe. Nonload-bearing adobe partitions and gable end walls shall be evaluated for stability and anchored against out-of-plane failure if necessary.
8-806.5 Bond beam. Where provided, a bond beam or equivalent structural element shall be located at the top of all adobe walls, and at the second floor for two-story buildings or structures. The size and configuration of the structural element shall be sufficient to provide an effective brace for the wall, to tie the building together and to connect the wall to the floor or roof.
8-806.6 Repair or reconstruction. Repair or reconstruction of wall area may utilize unstabilized brick or adobe masonry designed to be compatible with the constituents of the existing adobe materials.
8-806.7 Shear values. Existing adobe may be allowed a maximum strength level of 12 pounds per square inch (82.7 kPa) for shear.
8-806.8 Mortar. Mortar may be of the same soil composition as that used in the existing wall, or in new walls as necessary to be compatible with the adobe brick.
SECTION 8-807 — WOOD
8-807.1 Existing wood diaphragms or walls. Existing wood diaphragms or walls of straight or diagonal sheathing shall be assigned shear resistance values appropriate with the fasteners and materials functioning in conjunction with the sheathing. The structural survey shall determine fastener details and spacings and verify a load path through floor construction. Shear values of Tables 8-8-A and 8-8-B.
8-807.2 Wood lath and plaster. Wood lath and plaster walls and ceilings may be utilized using the shear values referenced in Section 8-807.1.
CHBC § 3106.3 Medium relevance — show source text
Roof construction 3106.3 Masonry Chapter 21A Adhered veneer 1404.11
Adobe 2109 Anchorage 1604.8.2 Anchored veneer 1404.7
Architectural cast stone 2103.1
Calculated fire resistance 722.4 Chimneys 2113 Construction 2104 Dampproofing 1805.2.2 Design, methods 2101.2, 2107, 2108, 2109
Fire resistance, calculated 722.3.2,
722.3.4
Fireplaces 2111 Floor anchorage 1604.8.2 Foundation walls 1807.1.5
Foundations, adobe 2109.2.4.5 Glass unit 2110
Heaters 2112
Inspection, special 1705.4 Joint reinforcement 2103.4
Materials 603.1, 2103 Penetrations 714 Quality assurance 2105 Rodentproofing Appendix F Roof anchorage 1604.8.1 Seismic provisions 2106 Serviceability 1604.3.4 Supported by wood 2104.1.1, 2304.13 Surface bonding 2103.2.2 Veneer 1404.11, 1404.7, 2101.2.1,
2308.10.10 Wall anchorage 1604.8.2 Waterproofing 1805.3.2 Mass Notification Systems 917 Mass Timber 508, 509, 602, 703, 718, 722 Materials
Alternates 104.2.3
Aluminum Chapter 20 Concrete Chapter 19, Chapter 19A Glass and glazing Chapter 24 Gypsum Chapter 25 Masonry Chapter 21, Chapter 21A Noncombustible 703.4
Plastic Chapter 26 Steel Chapter 22, Chapter 22A Testing (see Testing) 1707 Wood Chapter 23 Materials and Construction Methods for Exterior Exposure Chapter 7A Means of Appeals 113, Appendix B Means of Egress Chapter 10, 202 Accessible 1009, 2702.2 Aircraft related 412.2.2, 412.2.5.1, 412.4.2, 412.6.1, 412.7.3 Alternating tread device 412.7.3, 1006.2.2.1, 1006.2.2.2, 1011.14 Ambulatory care facilities 422.3.1, 422.3.3 Assembly 1009.1, 1030 Atrium 404.9, 404.11, 707.3.6 Capacity 1005.3
Laboratories
Classification of 304.1, 307.1.1 Hazardous materials 414, 415 Higher education laboratories 304.4, 428 Incidental uses Table 509.1
Ladders
Boiler, incinerator and furnace
rooms 1006.2.2.1
Construction 1011.15, 1011.16, 1014.2, 1014.7, 1015.3, 1015.4 Emergency escape window wells 1031.5.2
Frequently asked questions
May I keep or reinstall original historic materials (in‑kind repairs) under the CHBC?
Yes. The CHBC expressly allows in‑kind repairs and the use or reinstallation of historical materials and methods for qualified historical buildings, provided public health and life‑safety hazards are addressed and the work follows CHBC conditions (see §8‑801 and §8‑105.1) .
How are allowable strengths and performance values for archaic materials determined?
Allowable stresses and strength levels are assigned by the architect or structural engineer in responsible charge, based on comparable codified materials or on testing; the CHBC requires a structural survey to document existing conditions and to inform those assignments (see §8‑802 and §8‑703) .
Are there specific limits or requirements for adobe and other common archaic materials?
Yes. The CHBC includes material‑specific provisions—e.g., §8‑806 addresses adobe (moisture protection, bond beams, height‑to‑thickness ratios and shear values), §8‑805 covers masonry and testing, and other sections address wood, concrete, steel/iron, tile, veneers and glazing—so consult those sections for the applicable limits and testing/anchorage requirements .