CHBC · California Historical Building Code
Wood, Concrete, Steel & Other Archaic Materials
This hub summarizes CHBC Chapter 8‑8 rules for evaluating, retaining, repairing and (when necessary) strengthening historic wood, concrete, steel and other archaic materials.
Last reviewed: July 6, 2026
Overview
This hub covers Chapter 8‑8 of the California Historical Building Code (CHBC), which governs the evaluation, retention, repair and limited replacement of historic (archaic) building materials and methods that differ from regular-code requirements. The chapter is intended to allow historically appropriate materials and assemblies to remain or be reinstalled while requiring documentation, testing and engineering judgment where needed (see §8‑801 Purpose, Intent and Scope and §8‑804 Allowable Conditions for Specific Materials) .
Material-specific guidance in this chapter addresses commonly encountered historic materials — for example wood (see §8‑807), concrete (see §8‑808), steel and iron (see §8‑809), adobe (§8‑806) and veneers and hollow‑tile (§8‑811, §8‑810) — and explains when lower-strength or nonstandard assemblies may be retained, and when evaluation, testing or strengthening is required . The CHBC expects the architect or engineer in responsible charge to assign allowable stresses, document conditions in the required structural survey (see §8‑703), and to use testing or historical evidence to support any departures from regular-code values (§8‑802) .
In this section
- How are historic steel/iron, hollow clay tile, veneers and glazing handled under CHBC?
- How does CHBC allow archaic wood framing types and fasteners to be used or assigned values?
- What shear values apply to existing wood diaphragms, lath and plaster assemblies?
- When may natural cement, rubble or low‑strength concrete remain or be used?
Code references
Grounded in the retrieved California Historical Building Code — click a citation to read the verbatim passage:
CHBC § 8-807.3 High relevance — show source text
8-807.3 Existing wood framing. Existing wood framing members may be assigned allowable stresses consistent with codes in effect at the time of construction. Existing or new replacement wood framing may be of archaic types originally used if properly researched, such as balloon and single wall. Wood joints such as dovetail and mortise and tenon types may be used structurally, provided they are well made. Lumber selected for use and type need not bear grade marks, and greater or lesser species such as low-level pine and fir, boxwood and indigenous hardwoods and other variations may be used for specific conditions where they were or would have been used.
Wood fasteners such as square or cut nails may be used with a maximum increase of 50 percent over wire nails for shear.
SECTION 8-808 — CONCRETE
8-808.1 Materials. Natural cement concrete, unreinforced rubble concrete and similar materials may be utilized wherever that material is used historically. Concrete of low strength and with less reinforcement than required by the regular code may remain in place. The architect or engineer shall assign appropriate values of strength based on testing of samples of the materials. Bond and development lengths shall be determined based on historical information or tests.
8-808.2 Detailing. The architect or engineer shall carefully evaluate all detailing provisions of the regular code which are not met and shall consider the implications of these variations on the ultimate performance of the structure, giving due consideration to ductility and reserve strength.
16 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
SECTION 8-809 — STEEL AND IRON
The hand-built, untested use of wrought or black iron, the use of cast iron or grey iron, and the myriad of joining methods that are not specifically allowed by code may be used wherever applicable and wherever they have proven their worth under the considerable span of years involved with most qualified historical buildings or structures. Uplift capacity should be evaluated and strengthened where necessary. Fixed conditions or midheight lateral loads on cast iron columns that could cause failure should be taken into account. Existing structural wrought, forged steel or grey iron may be assigned the maximum working stress prevalent at the time of original construction.
SECTION 8-810 — HOLLOW CLAY TILE
The historical performance of hollow clay tile in past earthquakes shall be carefully considered in evaluating walls of hollow clay tile construction. Hollow clay tile bearing walls shall be evaluated and strengthened as appropriate for lateral loads and their ability to maintain support of gravity loads. Suitable protective measures shall be provided to prevent blockage of exit stairways, stairway enclosures, exit ways and public ways as a result of an earthquake.
SECTION 8-811 — VENEERS
8-811.1 Terra cotta and stone. Terra cotta, cast stone and natural stone veneers shall be investigated for the presence of suitable anchorage. Steel anchors shall be investigated for deterioration or corrosion. New or supplemental anchorage shall be provided as appropriate.
8-811.2 Anchorage. Brick veneer with mechanical anchorage at spacings greater than required by the regular code may remain, provided the anchorages have not corroded. Nail strength in withdrawal in wood sheathing may be utilized to its capacity in accordance with code values.
SECTION 8-812 — GLASS AND GLAZING
CHBC § 8-801 High relevance — show source text
SECTION 8-801 — PURPOSE, INTENT AND SCOPE
8-801.1 Purpose. The purpose of the CHBC is to provide regulations for the use of historical methods and materials of construction that are at variance with regular code requirements or are not otherwise codified, in buildings or structures designated as qualified historical buildings or properties. The CHBC require enforcing agencies to accept any reasonably equivalent alternatives to the regular code when dealing with qualified historical buildings or properties.
8-801.2 Intent. It is the intent of the CHBC to provide for the use of historical methods and materials of construction that are at variance with specific code requirements or are not otherwise codified.
8-801.3 Scope. Any construction type or material that is, or was, part of the historical fabric of a structure is covered by this chapter. Archaic materials and methods of construction present in a historical structure may remain or be reinstalled or be installed with new materials of the same class to match existing conditions.
SECTION 8-802 — GENERAL ENGINEERING APPROACHES
Strength values for archaic materials shall be assigned based upon similar conventional codified materials, or on tests as hereinafter indicated. The archaic materials and methods of construction shall be thoroughly investigated for their details of construction in accordance with Section 8-703. Testing shall be performed when applicable to evaluate existing conditions. The architect or structural engineer in responsible charge of the project shall assign allowable stresses or strength levels to archaic materials. Such assigned strength values shall not be greater than those provided for in the following sections without adequate testing, and shall be subject to the concurrence of the enforcing agency.
SECTION 8-803 — NONSTRUCTURAL ARCHAIC MATERIALS
Where nonstructural historical materials exist in uses which do not meet the requirements of the regular code, their continued use is allowed by this code, provided that any public health and life safety hazards are mitigated subject to the concurrence of the enforcing agency.
SECTION 8-804 — ALLOWABLE CONDITIONS FOR SPECIFIC MATERIALS
Archaic materials which exist and are to remain in qualified historical buildings or structures shall be evaluated for their condition and for loads required by this code. The structural survey required in Section 8-703 of the CHBC shall document existing conditions, reinforcement, anchorage, deterioration and other factors pertinent to establishing allowable stresses, strength levels and adequacy of the archaic materials. The remaining portion of this chapter provides additional specific requirements for commonly encountered archaic materials.
SECTION 8-805 — MASONRY
For adobe, see Section 8-806.
8-805.1 Existing solid masonry. Existing solid masonry walls of any type, except adobe, may be allowed, without testing, a maximum ultimate strength of 9 pounds per square inch (62.1 kPa) in shear where there is a qualifying statement by the architect or engineer that an inspection has been made, that mortar joints are filled and that both brick and mortar are reasonably good. The shear stress above applies to unreinforced masonry, except adobe, where the maximum ratio of unsupported height or length to thickness does not exceed 13, and where minimum quality mortar is used or exists. Wall height or length is measured to supporting or resisting elements that are at least twice as stiff as the tributary wall. Stiffness is based on the gross section. Shear stress may be increased by the addition of 10 percent of the axial direct stress due to the weight of the wall directly above.
CHBC § 8-8 High relevance — show source text
CHAPTER 8-8 ARCHAIC MATERIALS AND METHODS OF
CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . 15
Section
8-801 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 15 8-802 General Engineering Approaches. . . . . . . . . . . . . . . . . 15 8-803 Nonstructural Archaic Materials. . . . . . . . . . . . . . . . . . 15
8-804 Allowable Conditions for Specific Materials . . . . . . . 15 8-805 Masonry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 8-806 Adobe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8-807 Wood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8-808 Concrete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8-809 Steel and Iron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8-810 Hollow Clay Tile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8-811 Veneers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8-812 Glass and Glazing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
CHAPTER 8-9 MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . 19
Section
8-901 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 19 8-902 Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8-903 Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 8-904 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
CHAPTER 8-10 QUALIFIED HISTORICAL DISTRICTS,
SITES AND OPEN SPACES . . . . . . . . . . . . . . . 23
Section
CHBC § 8-706.3 High relevance — show source text
8-706.3 Load path. A complete and continuous load path, including connections, from every part or portion of the structure to the ground shall be provided for the required forces. It shall be verified that the structure is adequately tied together to perform as a unit when subjected to earthquake forces.
8-706.4 Parapets. Parapets and exterior decoration shall be investigated for conformance with regular code requirements for anchorage and ability to resist prescribed seismic forces.
An exception to regular code requirements shall be permitted for those parapets and decorations which are judged not to be a hazard to life safety.
8-706.5 Nonstructural features. Nonstructural features of historical structure, such as exterior veneer, cornices and decorations, which might fall and create a life safety hazard in an earthquake, shall be evaluated. Their ability to resist seismic forces shall be verified, or the feature shall be strengthened with improved anchorage when appropriate.
8-706.5.1 Partitions and ceilings of corridors and stairways serving an occupant load of 30 or more shall be investigated to determine their ability to remain in place when the building is subjected to earthquake forces.
8-706.5.2 Seismic forces used to evaluate and improve nonstructural components and their anchorage, where required, shall comply with ASCE 41 or need not exceed 0.75 times the seismic forces prescribed by the requirements of the regular code.
14 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-8 ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
SECTION 8-801 — PURPOSE, INTENT AND SCOPE
8-801.1 Purpose. The purpose of the CHBC is to provide regulations for the use of historical methods and materials of construction that are at variance with regular code requirements or are not otherwise codified, in buildings or structures designated as qualified historical buildings or properties. The CHBC require enforcing agencies to accept any reasonably equivalent alternatives to the regular code when dealing with qualified historical buildings or properties.
8-801.2 Intent. It is the intent of the CHBC to provide for the use of historical methods and materials of construction that are at variance with specific code requirements or are not otherwise codified.
8-801.3 Scope. Any construction type or material that is, or was, part of the historical fabric of a structure is covered by this chapter. Archaic materials and methods of construction present in a historical structure may remain or be reinstalled or be installed with new materials of the same class to match existing conditions.
SECTION 8-802 — GENERAL ENGINEERING APPROACHES
Strength values for archaic materials shall be assigned based upon similar conventional codified materials, or on tests as hereinafter indicated. The archaic materials and methods of construction shall be thoroughly investigated for their details of construction in accordance with Section 8-703. Testing shall be performed when applicable to evaluate existing conditions. The architect or structural engineer in responsible charge of the project shall assign allowable stresses or strength levels to archaic materials. Such assigned strength values shall not be greater than those provided for in the following sections without adequate testing, and shall be subject to the concurrence of the enforcing agency.
SECTION 8-803 — NONSTRUCTURAL ARCHAIC MATERIALS
CHBC § 8-806.4 Medium relevance — show source text
8-806.4 Nonload-bearing adobe. Nonload-bearing adobe partitions and gable end walls shall be evaluated for stability and anchored against out-of-plane failure if necessary.
8-806.5 Bond beam. Where provided, a bond beam or equivalent structural element shall be located at the top of all adobe walls, and at the second floor for two-story buildings or structures. The size and configuration of the structural element shall be sufficient to provide an effective brace for the wall, to tie the building together and to connect the wall to the floor or roof.
8-806.6 Repair or reconstruction. Repair or reconstruction of wall area may utilize unstabilized brick or adobe masonry designed to be compatible with the constituents of the existing adobe materials.
8-806.7 Shear values. Existing adobe may be allowed a maximum strength level of 12 pounds per square inch (82.7 kPa) for shear.
8-806.8 Mortar. Mortar may be of the same soil composition as that used in the existing wall, or in new walls as necessary to be compatible with the adobe brick.
SECTION 8-807 — WOOD
8-807.1 Existing wood diaphragms or walls. Existing wood diaphragms or walls of straight or diagonal sheathing shall be assigned shear resistance values appropriate with the fasteners and materials functioning in conjunction with the sheathing. The structural survey shall determine fastener details and spacings and verify a load path through floor construction. Shear values of Tables 8-8-A and 8-8-B.
8-807.2 Wood lath and plaster. Wood lath and plaster walls and ceilings may be utilized using the shear values referenced in Section 8-807.1.
8-807.3 Existing wood framing. Existing wood framing members may be assigned allowable stresses consistent with codes in effect at the time of construction. Existing or new replacement wood framing may be of archaic types originally used if properly researched, such as balloon and single wall. Wood joints such as dovetail and mortise and tenon types may be used structurally, provided they are well made. Lumber selected for use and type need not bear grade marks, and greater or lesser species such as low-level pine and fir, boxwood and indigenous hardwoods and other variations may be used for specific conditions where they were or would have been used.
Wood fasteners such as square or cut nails may be used with a maximum increase of 50 percent over wire nails for shear.
SECTION 8-808 — CONCRETE
8-808.1 Materials. Natural cement concrete, unreinforced rubble concrete and similar materials may be utilized wherever that material is used historically. Concrete of low strength and with less reinforcement than required by the regular code may remain in place. The architect or engineer shall assign appropriate values of strength based on testing of samples of the materials. Bond and development lengths shall be determined based on historical information or tests.
8-808.2 Detailing. The architect or engineer shall carefully evaluate all detailing provisions of the regular code which are not met and shall consider the implications of these variations on the ultimate performance of the structure, giving due consideration to ductility and reserve strength.
16 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
SECTION 8-809 — STEEL AND IRON
CHBC § 3.1. Medium relevance — show source text
Gypsum wallboard, blocked edges|Per side: 600 lbs per foot for seismic shear
550 lbs per foot for seismic shear
200 lbs per foot for seismic shear
400 lbs per foot for seismic shear| |3. Existing footings, wood framing, structural steel and reinforcing steel
3.1. Plain concrete footings
3.2. Douglas fir wood
3.3. Reinforcing steel
3.4. Structural steel|f ′c = 1,500 psi (10.34 MPa) unless otherwise shown by
tests3
Allowable stress same as D.F. No. 13
_ft _= 40,000 lbs per square inch (124.1 N/mm2) maximum
ft= 33,000 lbs per square inch (137.9 N/mm2) maximum| |1. Material must be sound and in good condition.
2. Shear values of these materials may be combined, except the total combined value shall not exceed 900 pounds per foot (13,140 N/m).
3. Stresses given may be increased for combinations of loads as specified in the regular code.|1. Material must be sound and in good condition.
2. Shear values of these materials may be combined, except the total combined value shall not exceed 900 pounds per foot (13,140 N/m).
3. Stresses given may be increased for combinations of loads as specified in the regular code.|2025 CALIFORNIA HISTORICAL BUILDING CODE 17
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
TABLE 8-8B—STRENGTH VALUES OF NEW MATERIALS USED IN CONNECTION WITH EXISTING CONSTRUCTION Col2 NEW MATERIALS OR CONFIGURATIONS OF MATERIALS STRENGTH LEVEL CAPACITY1 1. Horizontal diaphragms2
1.1. 15/32 inch minimum plywood sheathing fastened directly over existing straight
sheathing with edges of plywood located on center of individual sheathing
boards and fastened with minimum #8x 11/4 inch wood screws or nails with
helical threads 0.13 inch min. diameter and 11/4 inch min. length at 4 inch
centers all panel edges and 12 inch centers each way in field
1.2. Same plywood and attachments as 1.1 fastened directly over existing diago-
nal sheathing
1.3. 3/8 inch plywood sheathing fastened directly over existing straight or diagonal
sheathing with ends and edges on centers of individual sheathing boards and
fastened with #6 wood screws or nails with helical threads 0.13 inch min.
diameter and 11/4 inch min. length at 6 inch centers tall panel edges and 12
inch centers each way in field1,500 lbs per foot
1,800 lbs per foot
900 lbs per foot2. Shear walls:
Plywood sheathing applied directly over wood studs. No value shall be given to
plywood applied over existing plaster or wood sheathing100 percent of the value specified in the regular code for
shear walls3. Crosswalls: (special procedure only)
3.1. Plywood sheathing applied directly over wood studs.CHBC § 8-6 Medium relevance — show source text
CHAPTER 8-6 ACCESSIBILITY . . . . . . . . . . . . . . . . . . . . . . . . 11
Section
8-601 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 11
8-602 Basic Provisions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8-603 Alternatives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8-604 Equivalent Facilitation. . . . . . . . . . . . . . . . . . . . . . . . . . 12
CHAPTER 8-7 STRUCTURAL REGULATIONS. . . . . . . . . . . . . 13
Section
8-701 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 13 8-702 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8-703 Structural Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8-704 Nonhistorical Additions and
Nonhistorical Alterations . . . . . . . . . . . . . . . . . . . . . . . 13
8-705 Structural Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8-706 Lateral Load Regulations. . . . . . . . . . . . . . . . . . . . . . . . 14
CHAPTER 8-8 ARCHAIC MATERIALS AND METHODS OF
CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . 15
Section
8-801 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 15 8-802 General Engineering Approaches. . . . . . . . . . . . . . . . . 15 8-803 Nonstructural Archaic Materials. . . . . . . . . . . . . . . . . . 15
8-804 Allowable Conditions for Specific Materials . . . . . . . 15 8-805 Masonry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 8-806 Adobe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8-807 Wood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8-808 Concrete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
CHBC § 8-804 Medium relevance — show source text
SECTION 8-804 — ALLOWABLE CONDITIONS FOR SPECIFIC MATERIALS
Archaic materials which exist and are to remain in qualified historical buildings or structures shall be evaluated for their condition and for loads required by this code. The structural survey required in Section 8-703 of the CHBC shall document existing conditions, reinforcement, anchorage, deterioration and other factors pertinent to establishing allowable stresses, strength levels and adequacy of the archaic materials. The remaining portion of this chapter provides additional specific requirements for commonly encountered archaic materials.
SECTION 8-805 — MASONRY
For adobe, see Section 8-806.
8-805.1 Existing solid masonry. Existing solid masonry walls of any type, except adobe, may be allowed, without testing, a maximum ultimate strength of 9 pounds per square inch (62.1 kPa) in shear where there is a qualifying statement by the architect or engineer that an inspection has been made, that mortar joints are filled and that both brick and mortar are reasonably good. The shear stress above applies to unreinforced masonry, except adobe, where the maximum ratio of unsupported height or length to thickness does not exceed 13, and where minimum quality mortar is used or exists. Wall height or length is measured to supporting or resisting elements that are at least twice as stiff as the tributary wall. Stiffness is based on the gross section. Shear stress may be increased by the addition of 10 percent of the axial direct stress due to the weight of the wall directly above. Higher-quality mortar may provide a greater shear value and shall be tested in accordance with Appendix A, Chapter A1 of the California Existing Building Code (CEBC) 2010 edition, and as modified by the CHBC.
8-805.2 Stone masonry.
8-805.2.1 Solid-backed stone masonry. Stone masonry solidly backed with brick masonry shall be treated as solid brick masonry as described in Section 8-805.1 and in the 2009 International Existing Building Code [®] (IEBC [®] ), provided representative testing and inspection verifies solid collar joints between stone and brick and that a reasonable number of stones lap with the brick wythes as headers or that steel anchors are present. Solid stone masonry where the wythes of stone effectively overlap to provide the equivalent header courses may also be treated as solid brick masonry.
8-805.2.2 Independent wythe stone masonry. Stone masonry with independent face wythes may be treated as solid brick masonry as described in Section 8-805.1 and the CEBC, provided representative testing and inspection verify that the core is essentially solid in the masonry wall and that steel ties are epoxied in drilled holes between outer stone wythes at floors, roof and not to exceed 4 feet (1219 mm) on center in each direction, between floors and roof. A reinforcing element shall exist or be provided at or near the top of all stone masonry walls.
2025 CALIFORNIA HISTORICAL BUILDING CODE 15
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
8-805.2.3 Testing of stone masonry. Testing of stone masonry shall be similar to the 2010 CEBC requirements for brick masonry, except that representative stones which are not interlocked shall be pulled outward from the wall and shear area appropriately calculated after the test.
CRC § 2025 Medium relevance — show source text
The prescriptive provisions of this chapter provide requirements for constructing footings and walls for foundations of wood, masonry, concrete and precast concrete. In addition to a foundation’s ability to support the required design loads, this chapter addresses several other factors that can affect foundation performance. These include controlling surface water and subsurface drainage, requiring soil tests where conditions warrant and evaluating proximity to slopes and minimum depth requirements. The chapter also provides requirements to minimize adverse effects of moisture, decay and pests in basements and crawl spaces.
Chapter 5 Floors.
Chapter 5 provides the requirements for the design and construction of floor systems that will be capable of supporting minimum required design loads. This chapter covers four different types: wood floor framing, wood floors on the ground, cold-formed steel floor framing and concrete slabs on the ground. Allowable span tables are provided that greatly simplify the determination of joist, girder and sheathing sizes for raised floor systems of wood framing and cold-formed steel framing. This chapter also contains prescriptive requirements for wood-framed exterior decks and their attachment to the main building.
Chapter 6 Wall Construction.
Chapter 6 contains provisions that regulate the design and construction of walls. The wall construction covered in Chapter 6 consists of five different types: wood framed, cold-formed steel framed, masonry, concrete and structural insulated panel (SIP). The primary concern of this chapter is the structural integrity of wall construction and transfer of all imposed loads to the supporting structure. This chapter provides the requirements for the design and construction of wall systems that are capable of supporting the minimum design vertical loads (dead, live and snow loads) and lateral loads (wind or seismic loads). This chapter contains the prescriptive requirements for wall bracing and/or shear walls to resist the imposed lateral loads due to wind and seismic activity.
Chapter 6 also regulates exterior windows and doors installed in walls. This chapter contains criteria for the performance of exterior windows and doors and includes provisions for testing and labeling, garage doors, windborne debris protection and anchorage details.
Chapter 7 Wall Covering.
Chapter 7 contains provisions for the design and construction of interior and exterior wall coverings. This chapter establishes the various types of materials, materials standards and methods of application permitted for use as interior coverings, including interior plaster, gypsum board, ceramic tile, wood veneer paneling, hardboard paneling, wood shakes and wood shingles. Chapter 7 also contains requirements for the use of vapor retarders for moisture control in walls.
2025 CALIFORNIA RESIDENTIAL CODE xv
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Exterior wall coverings provide the weather-resistant exterior envelope that protects the building’s interior from the elements. Chapter 7 provides the requirements for wind resistance and water-resistive barrier for exterior wall coverings. This chapter prescribes the exterior wall coverings as well as the water-resistive barrier required beneath the exterior materials. Exterior wall coverings regulated by this section include aluminum, stone and masonry veneer, wood, hardboard, particleboard, wood structural panel siding, wood shakes and shingles, exterior plaster, steel, vinyl, fiber cement and exterior insulation finish systems.
Chapter 8 Roof-Ceiling Construction.
CHBC § 1.5 Medium relevance — show source text
; clips C, E; reinforcement: none;1/2″ plas-
ter, 1.5:2.5 mill mix.|N/A|55 min|||3|5, 8|3/4|RESOURCE A-96 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
RESOURCE A—GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS AND ASSEMBLIES
TABLE 3.2—continued
FLOOR/CEILING ASSEMBLIES—STEEL STRUCTURAL ELEMENTSCol2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10 ITEM
CODEMEMBRANE
THICKNESSCONSTRUCTION DETAILS PERFORMANCE PERFORMANCE REFERENCE NUMBER REFERENCE NUMBER REFERENCE NUMBER NOTES REC.
HOURSITEM
CODEMEMBRANE
THICKNESSCONSTRUCTION DETAILS LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92 POST-BMS-92 POST-BMS-92 F/C-S-8 1/2″ Spec. 9′ × 4′4″; S.J. 103 bar joists, 18″ o.c.;
deck: 4 lbs rib lath base; 6″ × 6″ 10 × 10 gage
reinforcement; 2″ deck 1:2:4 gravel concrete;
membrane: furring,3/4″ C.R.S., 16″ o.c.; clips C,
E; reinforcement: none;1/2″ plaster, 1.5:2.5
mill mix.300 psf 1 hr
10 min3 2, 3, 8 1 F/C-S-9 5/8″ 10′ × 13′6″; S.J. 103, 24″ o.c.; deck: 2″
concrete, 1:2:4; membrane: furring 12″ o.c.;
clips A, B, G; Extra “A” clips reinforcement;5/8″
plaster, 1.5:2, 1.5:3.145 psf 3 hrs 3 6, 8 3 F/C-S-10 5/8″ 18′ × 13′6″; joists, S.J. 103, 24″ o.c.; deck: 4 lbs
rib lath; 6″ × 6″ 10 × 10 gage reinforcement; 2″
deck, 1:2:3.5 gravel concrete; membrane:
furring, spacing 16″ o.c.CHBC § 1403.1 Medium relevance — show source text
SECTION 1403—MATERIALS
1403.1 General. Materials used for the construction of exterior walls shall comply with the provisions of this section. Materials not prescribed herein shall be permitted, provided that any such alternative has been approved.
1403.2 Water-resistive barrier. Not fewer than one layer of water-resistive barrier material shall be attached to the studs or sheathing, with flashing as described in Section 1404.4, in such a manner as to provide a continuous water-resistive barrier behind the exterior wall veneer. The intersection between the water-resistive barrier material and fenestration openings shall be flashed and assembled in accordance with the fenestration manufacturer’s installation instructions, or other approved methods for applications not addressed by the fenestration manufacturer’s instructions. The water-resistive barrier material shall be continuous to the top of walls and terminated at penetrations and building appendages in a manner to meet the requirements of the exterior wall envelope as described in Section 1402.2.
Water-resistive barriers shall comply with one of the following:
No. 15 felt complying with ASTM D226, Type 1.
ASTM E2556, Type I or II.
14-4 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
EXTERIOR WALLS
Foam plastic insulating sheathing water-resistive barrier systems complying with Section 1402.2 and installed in accordance with manufacturer’s installation instructions.
ASTM E331 in accordance with Section 1402.2.
Other approved materials installed in accordance with the manufacturer’s installation instructions.
No. 15 asphalt felt and water-resistive barriers complying with ASTM E2556 shall be applied horizontally with the upper layer lapped over the lower layer not less than 2 inches (51 mm). Where joints occur, the upper and lower layer shall be lapped not less than 6 inches (152 mm).
[BS] 1403.3 Wood. Exterior walls of wood construction shall be designed and constructed in accordance with Chapter 23.
[BS] 1403.3.1 Basic hardboard. Basic hardboard shall conform to the requirements of ANSI A135.4.
[BS] 1403.3.2 Hardboard siding. Hardboard siding shall conform to the requirements of ANSI A135.6 and, where used structurally, shall be so identified by the label of an approved agency.
[BS] 1403.4 Masonry. Exterior walls of masonry construction shall be designed and constructed in accordance with this section and Chapter 21. Masonry units, mortar and metal accessories used in anchored and adhered veneer shall meet the physical requirements of Chapter 21. The backing of anchored and adhered veneer shall be of concrete, masonry, steel framing or wood framing. Continuous insulation meeting the applicable requirements of this code shall be permitted between the backing and the masonry veneer.
[BS] 1403.5 Metal. Exterior walls constructed of cold-formed or structural steel shall be designed in accordance with Chapter 22. Exterior walls constructed of aluminum shall be designed in accordance with Chapter 20.
[BS] 1403.5.1 Aluminum siding. Aluminum siding shall conform to the requirements of AAMA 1402.
[BS] 1403.5.2 Cold-rolled copper. Copper shall conform to the requirements of ASTM B370.
CHBC § 4.4 Medium relevance — show source text
[BS] C103.3 Material specifications for retrofits. Materials for retrofitting gable end walls shall comply with Table C103.3.
[BS] TABLE C103.3—MATERIAL SPECIFICATIONS FOR RETROFITSa Col2 Col3 Col4 COMPONENT MINIMUM SIZE OR
THICKNESSMINIMUM MATERIAL GRADE MINIMUM CAPACITY Anchor blocks, compression blocks and horizontal braces 2 × 4 nominal lumber #2 Spruce-Pine-Fir or better NA Nail plates 20 gage thickness
8d minimum nail holesGalvanized sheet steel NA Retrofit studs 2 × 4 nominal lumber #2 Spruce-Pine-Fir or better NA Gusset angle 14 gage thickness Galvanized sheet steel 350 pounds uplift
and lateral loadStud-to-plate connector 20 gage thickness Galvanized sheet steel 500 pounds uplift Metal plate connectors, straps and anchors 20 gage thickness Galvanized sheet steel NA For SI: 1 pound = 4.4 N.
NA = Not Applicable.
a. Metal plate connectors, nail plates, stud-to-plate connectors, straps and anchors shall be products approved for connecting wood-to-wood or wood-to-concrete as
appropriate.For SI: 1 pound = 4.4 N.
NA = Not Applicable.
a. Metal plate connectors, nail plates, stud-to-plate connectors, straps and anchors shall be products approved for connecting wood-to-wood or wood-to-concrete as
appropriate.For SI: 1 pound = 4.4 N.
NA = Not Applicable.
a. Metal plate connectors, nail plates, stud-to-plate connectors, straps and anchors shall be products approved for connecting wood-to-wood or wood-to-concrete as
appropriate.For SI: 1 pound = 4.4 N.
NA = Not Applicable.
a. Metal plate connectors, nail plates, stud-to-plate connectors, straps and anchors shall be products approved for connecting wood-to-wood or wood-to-concrete as
appropriate.[BS] C103.4 Twists in straps. Straps shall be permitted to be twisted or bent where they transition between framing members or connection points. Straps shall be bent only once at a given location though it is permissible that they be bent or twisted at multiple locations along their length.
[BS] C103.5 Fasteners. Fasteners shall meet the requirements of Table C103.5, Sections C103.5.1 and C103.5.2, and shall be permitted to be screws or nails meeting the minimum length requirement shown in the figures and specified in the tables of this appendix. Fastener spacing shall meet the requirements of Section C103.5.3.
Frequently asked questions
Can original wood framing types like balloon or single‑wall be reused or replaced under the CHBC?
Yes. Existing or replacement wood framing may be of archaic types originally used (for example balloon or single‑wall) provided they are properly researched and allowable stresses are assigned by the architect or engineer; see §8‑807.3 for the criteria on existing wood framing and allowable fastener values .
May low‑strength or unreinforced concrete remain in a qualified historical building?
Yes. Natural cement concrete, unreinforced rubble concrete and similar historic concretes may be utilized or remain in place; the architect or engineer must assign strength values based on testing or historical evidence and evaluate detailing and ductility implications per §8‑808.1–.2 .
How does the CHBC treat historic steel, wrought, or cast iron elements?
Historic wrought or black iron, cast or grey iron and hand‑built steel elements may be considered where historically used, but must be evaluated for uplift, lateral capacity and potential failure modes; allowable stresses are assigned by the responsible engineer with strengthening where necessary (see §8‑809) .
More in California Historical Building Code
Ask about the CHBC
Get cited, plain-English answers on the California Historical Building Code for your project — any code section, any scenario.